Perlick HC24RB, HC24RO, HC24TB, HC24TO, HC24WB Service Manual

...
SERVICE MANUAL
Residenal and Commercial Front Venng Refrigeraon
Product Series Covered in this Manual:
Residenal
HA24BB, HA24RB, HA24WB HA24FB HC24BB, HC24RB, HC24RO, HC24TB, HC24TO, HC24WB HP15, HK15 HH24 HP24, HK24, HM24 (Med Temp) HP24, HK24 (Low Temp) HP24, HK24, HM24 (Dual Zone FRZ/REF) HP24, HK24, HM24 (Dual Zone, Med Temp) HP48 HHA24, HPA24
Front Venng Commercial
HC48 HB24BS, HB24RS, HB24WS HB24FS
HC24FS, HC24RS, HC24WS HD24RS, HD24WS
Scan here to
download a pdf copy
of this manual.
Form No. Z2506
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
Table of Contents
1.0 GENERAL INFORMATION ................................................................................ 1-1
Use of Service Manual .................................................................................... 1-1
Model Families .............................................................................................. 1-1
2.0 SAFETY INFORMATION ................................................................................... 2-1
Refrigerant HFC-134a ..................................................................................... 2-1
Potential Problems with HFC-134a ................................................................... 2-1
Service Manual Safety Labels ...........................................................................2-1
3.0 TROUBLESHOOTING GUIDE ............................................................................ 3-1
Refrigeration System ...................................................................................... 3-1
Electrical System ............................................................................................ 3-4
Doors, Drawers, and Shelving ......................................................................... 3-9
Beverage Dispensing ...................................................................................... 3-10
4.0 VARIABLE SPEED COMPRESSOR SPECIFICATION .......................................... 4-1
5.0 COMPRESSOR INVERTER OPERATION ........................................................... 5-1
5.1 Compressor Start-Up ........................................................................................ 5-1
5.2 Normal Operation ............................................................................................. 5-1
6.0 TROUBLESHOOTING COMPRESSOR INVERTER .............................................. 7-1
7.0 REFRIGERATION SYSTEM REPAIR INSTRUCTIONS ........................................ 7-1
Air Inltration ............................................................................................... 7-1
System Operating Pressures .......................................................................... 7-3
7.2.1 Process Tubes and Access Valve ...................................................................... 7-4
Remove Evaporator Fan Panel ....................................................................... 7-4
De-Ice Blocked Evaporator Coil .................................................................... 7-5
Evaporator Airow by Model ......................................................................... 7-6
Air Flow Obstructions ................................................................................... 7-7
Clean Condenser Coil ................................................................................... 7-7
Ambient Temperature .................................................................................. 7-7
Compressors ............................................................................................... 7-8
Replace Condenser. Fan Motor ...................................................................... 7-9
Replace Evaporator Fan Motor ...................................................................... 7-9
Replace Compressor .................................................................................... 7-10
Leak Detection ............................................................................................ 7-10
Recharge Procedure .................................................................................... 7-10
Replace compressor starting device ............................................................. 7-11
Beverage Dispensing ................................................................................... 7-12
C0
2 gauge pressure, temperature and carbonation level reference chart .......... 7-12
Calculate ideal gague pressure of straight CO
............................................... 7-13
2
Beer Dispensing Cleaning ............................................................................ 7-13
7.20 Refrigeration System Diagrams ..................................................................... 7-15
Table of Contents Page 1
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
8.0 ELECTRICAL SYSTEM REPAIR INSTRUCTONS................................................. 8-1
Electrical Specications ................................................................................... 8-1
Wiring Diagrams ............................................................................................ 8-2
Load Operation Modes .................................................................................... 8-18
Electronic Controller ....................................................................................... 8-26
Factory Set Point ............................................................................................ 8-27
8.6.1 Dixell Controller: Reset Factory Parameter Settings ........................................... 8-30
8.6.2 Eliwell Controller: Reset Factory Parameter Settings .......................................... 8-30
8.6.3 Replacing Control Module ................................................................................ 8-30
8.6.3.1 Replacing Electro-mechanical Controller .............................................. 8-30
8.6.3.2 Replacing Digital Controller – Dixell & Eliwell ....................................... 8-30
8.6.4 Temperature Probe ......................................................................................... 8-32
LED Lighting .................................................................................................. 8-33
8.7.1 Replace LED Light Strip ................................................................................... 8-33
Replace DC Driver/Inverter ............................................................................. 8-33
8.10 Mullion Heater Hook Up .............................................................................. 8-34
9.0 SERVICE INSTRUCTIONS - DOORS, DRAWERS, AND SHELVING .................... 9-1
Proper Door and Drawer Usage ........................................................................ 9-1
Reverse Door Swing ....................................................................................... 9-1
Replace Door Hinge ........................................................................................ 9-4
Drawer & Shelf Slides ..................................................................................... 9-4
9.4.1 Shelving Adjustment ....................................................................................... 9-3
9.4.2 Cleaning/Lubricating Drawer shelf Extenders .................................................... 9-4
Replace Door & Drawer Gasket ........................................................................ 9-5
Residential Drawer Mullion Repair .................................................................... 9-5
Replace Door Handle ...................................................................................... 9-7
Lock Troubleshooting ...................................................................................... 9-7
9.9 Custom Overlay Panels
10.0 REPLACEMENT PARTS ............................................................................... 10-1
HP24 Medium Temperature Cabinets - Evaporator Compartment Service Parts .. 10-1
HP24 Low Temperature Cabinets - Evaporator Compartment Service Parts ....... 10-2
HP24 Medium Temperature Cabinets - Condenser Compartment Service Parts .. 10-3
HP24 Low Temperature Cabinets - Condenser Compartment Service Parts ........ 10-4
HP24 Cabinets – Door Service Parts ............................................................... 10-6
HP24 Cabinets - Shelving Service Parts .......................................................... 10-7
HP24 Cabinets - Drawer Service Parts ............................................................ 10-8
HP15 Cabinets – Evaporator Compartment Service Parts ................................. 10-9
HP15 Cabinets - Condenser Compartment Service Parts .................................. 10-10
HP15 Cabinets - Door Service Parts ............................................................. 10-12
HP15 Cabinets - Shelving Service Parts ........................................................ 10-13
HP15 Cabinets - Drawer Service Parts .......................................................... 10-14
HA24 Medium Temperature Cabinets - Evaporator Compartment Service Parts 10-15
Table of Contents Page 2
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
HA24 Low Temperature Cabinets - Evaporator Compartment Service Parts ....... 10-16
HA24 Medium Temperature Cabinets - Condenser Compartment Service Parts .. 10-17
HA24 Low Temperature Cabinets - Condenser Compartment Service Parts ........ 10-19
HA24 Cabinets - Door Service Parts ................................................................ 10-21
HA24 Cabinets - Shelves Service Parts ............................................................ 10-22
HA24 Cabinets - Drawers Service Parts ........................................................... 10-23
HH24 Cabinets - Evaporator Compartment Service Parts .................................. 10-24
HH24 Cabinets - Condenser Compartment Service Parts .................................. 10-25
HH24 Cabinets - Door Service Parts ............................................................... 10-27
HH24 Cabinets - Shelving Service Parts .......................................................... 10-28
HC24BB, HC24RB, HC24WB, HC24RO, HC24TB & HC24TO Cabinets - Evaporator
Compartment Service Parts ..................................................................................... 10-29
HC24BB, HC24RB, HC24WB, HC24RO, HC24TB & HC24TO Cabinets - Condenser
Compartment Service Parts ..................................................................................... 10-30
HC24 Cabinets - Door Service Parts ............................................................... 10-32
HC24 Cabinets - Shelving Service Parts........................................................... 10-33
HC24 Cabinets - Drawer Service Parts ............................................................ 10-34
HC24RS & HC24WS Cabinets - Evaporator Compartment Service Parts ............. 10-35
HC24FS Cabinets - Evaporator Compartment Service Parts .............................. 10-36
HC24RS &HC24WS Cabinets - Condenser Compartment Service Parts .............. 10-37
HC24FS Cabinets - Condenser Compartment Service Parts .............................. 10-38
HC24 Commercial Cabinets - Door Service Parts ............................................. 10-39
HC24 Commercial Cabinets - Shelving Service Parts ........................................ 10-40
Table of Contents Page 3
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
Table of Figures
Figure 1-1. Information Plate ........................................................................................... 1-1
Figure 7-1. Sealing Compound at Wiring Pass-through – Back ............................................ 7-1
Figure 7-2. Sealing Compound at Wiring Pass-through – Inside .......................................... 7-2
Figure 7-3. Evaporator Condensate Drain .......................................................................... 7-2
Figure 7-4. Process Tubes ................................................................................................ 7-4
Figure 7-5. Remove Shelves ............................................................................................. 7-4
Figure 7-6. Remove Shelf Slide ......................................................................................... 7-4
Figure 7-7. Remove Pilaster ............................................................................................. 7-4
Figure 7-8. Evaporator Fan Panel Screw Locations ............................................................. 7-5
Figure 7-9. Remove Evaporator Fan Panel ......................................................................... 7-5
Figure 7-10. Deicing Evaporator ....................................................................................... 7-5
Figure 7-11. Check for Obstructions ................................................................................. 7-7
Figure 7-12. Remove Front Grille ...................................................................................... 7-7
Figure 7-13. Clean Condenser Coils .................................................................................. 7-7
Figure 7-14. Condenser Fan Mounting Hardware ............................................................... 7-9
Figure 7-15. Dual Zone F-R Gen 3 Refrigeration System Diagram ....................................... 7-15
Figure 7-16. Dual Zone Med Temp Gen 3 Refrigeration System Diagram ............................. 7-16
Figure 7-17. Freezer Refrigeration System Diagram............................................................ 7-17
Figure 7-18. Med Temp Refrigeration System Diagram ...................................................... 7-18
Figure 8-1. HC24RS & HC24WS Wiring Diagram ................................................................ 8-2
Figure 8-2. HC24FS Wiring Diagram ................................................................................. 8-3
Figure 8-3. HP48 Signature Series Wiring Diagram ............................................................ 8-4
Figure 8-4. HP24 Signature Series Wiring Diagram ............................................................ 8-5
Figure 8-5. HP Freezers Wiring Diagram ........................................................................... 8-6
Figure 8-6. HA Freezers Wiring Diagram ........................................................................... 8-7
Figure 8-7. HP15 Signature Series Wiring Diagram ............................................................ 8-8
Figure 8-8. HC & HH Wiring Diagram ................................................................................ 8-9
Figure 8-9. HA Wiring Diagram ........................................................................................ 8-10
Figure 8-10. HB24BS, HB24RS & HB24WS Wiring Diagram ................................................. 8-11
Figure 8-11. HB24FB & HB24FS ADA Series Wiring Diagram ............................................... 8-12
Figure 8-12. HPA & HHA Wiring Diagram .......................................................................... 8-13
Figure 8-13. HC Wiring Diagram ....................................................................................... 8-14
Figure 8-14. HC48RS, HC48WS, HC48RW & HC48WW Wiring Diagram ................................ 8-15
Figure 8-15. HP24ZS/ZO Wiring Diagram .......................................................................... 8-16
Figure 8-16. HP24CS/CO/DS/DO Wiring Diagram ............................................................... 8-17
Figure 8-17. Temperature Probe ....................................................................................... 8-31
Figure 8-18. Interior LED Light ......................................................................................... 8-32
Figure 9-1. Door Removal ................................................................................................ 9-1
Figure 9-2. Hinge Removal ............................................................................................... 9-2
Table of Figures Page 4
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
Figure 9-3. Hinge Installation ........................................................................................... 9-2
Figure 9-4. Door Brackets ................................................................................................ 9-2
Figure 9-5. Removing Front Panel ..................................................................................... 9-3
Figure 9-6. Bearing and V-Block ....................................................................................... 9-3
Figure 9-7. Door Hinges ................................................................................................... 9-3
Figure 9-8. Installing V-Block ........................................................................................... 9-4
Figure 9-9. Installing Door ............................................................................................... 9-4
Figure 9-10. Shelf Locking Mechanism .............................................................................. 9-4
Figure 9-11. Removing/Installing Shelf ............................................................................. 9-5
Table of Contents Page 5
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
Table of Tables
Table 7-1. System Operating Pressures ............................................................................. 7-1
Table 7-2. Compressor Data............................................................................................. 7-2
Table 7-3. C0
Table 8-1. Electrical Specications .................................................................................... 8-1
Table 8-2. HA24BB, RB, WB Load Operation Modes .......................................................... 8-18
Table 8-3. HA24FB Load Operation Modes........................................................................ 8-18
Table 8-4. HB24BS, RS, WS Load Operation Modes ........................................................... 8-18
Table 8-5. HB24FS Load Operation Modes ........................................................................ 8-19
Table 8-6. HC24BB, RB, RO, TB, TO WB Load Operation Modes ......................................... 8-19
Table 8-7. HC24FS Load Operation Modes ........................................................................ 8-19
Table 8-8. HC24RS, WS Load Operation Modes ................................................................ 8-20
Table 8-9. HD24RS, WS Load Operation Modes ................................................................ 8-20
Table 8-10. HH24BO, BS, RO, RS, WO, WS Load Operation Modes ..................................... 8-20
Table 8-11. HP15BO, BS, RO, RS, TO, TS, HK15BO, RO, TO Load Operation Modes ............. 8-21
Table 8-12. HP15WO, WS, HK15WO Load Operation Modes .............................................. 8-21
Table 8-13. HP24BO, BS, RO, RS, TO, TS, HK24BO, RO, TO, HM24RO, TO Load Operation
Modes ........................................................................................................................... 8-22
Table 8-14. HP24WO, WS, HK24WO Load Operation Modes .............................................. 8-22
Table 8-15. HP24FO, FS, HK24FO Load Operation Modes .................................................. 8-22
Table 8-16. HP24CO, CS, DO, DS, HK24CO, DO, HM24CO Load Operation Modes ................ 8-23
Table 8-17. HP24ZO, ZS, HK24ZO, HM24ZO Load Operation Modes ................................... 8-24
Table 8-18. HC48RS, RW, WS, WW Load Operation Modes ................................................ 8-25
Table 8-19. HP48WO-S, WW-S Load Operation Modes ...................................................... 8-25
Table 8-20. Factory Temperature Settings ........................................................................ 8-27
Table 8-21. Temperature Resistance Values ...................................................................... 8-32
Table 9-1. Door Hinges .................................................................................................... 9-1
2 equilibrium pressure given volumes of C02 and temperature ......................... 7-1
Table of Tables Page 6
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
1.0 General Information
Use of Service Manual
This service manual is intended for use by a quali-
ed service technician. It is provided as a guide to
diagnose and repair service issues for the product models listed on the cover.
If you have any questions or require additional assistance, contact Perlick Customer Service during regular hours of operation.
Model Families
This manual contains specic instructions for
servicing the Perlick Residential and Front Venting Commercial Series refrigeration products, which include the following families:
RESIDENTIAL FRONT VENTING
COMMERCIAL
HA HC HH
HC HB HD
HK
HM HP HHA HPA
The model and serial numbers can be found on the Ceiling of the refrigerated space. See Figure 1-1.
Figure 1-1. Information Plate
Return to Table of Contents
General Information Page 1-1
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
2.0 Safety Information
Refrigerant HFC-134a
All self-contained models covered in this service manual are manufactured using refrigerant HFC­134a.
Potential Problems with HFC-134a
HFC-134a compressors are manufactured with a synthetic based ester oil charge.
The hygroscopic (water attraction) property of ester oil is many times greater than that of the mineral oils previously used with CFC-12.
High system moisture causes the formation of acids and alcohol, which can damage the compressor.
Systems or components of the refrigeration system should not be left open to atmosphere for more than (15) minutes at any time as humidity from the air will enter the system and be absorbed by the oil.
To ensure system dehydration:
System should be evacuated to a level less than 250 microns
Flux must not be used on any brazed joints.
Anytime a Perlick Refrigeration System is being serviced:
It is recommended that the drier be changed
using the exact same style and size within the
system to avoid possible charge problems or contaminant issues.
Service Manual Safety Labels
PLEASE READ all instructions completely before at­tempting to service the unit. Take particular note of the DANGER, WARNING and CAUTION information in this manual. The information is important for the
safe and efcient service, operation and care of the
Perlick unit.
HAZARD!!
Indicates hazardous situation that will result in death or serious injury if not avoided.
When isolated, shall not exceed 500 microns for a minimum of 10 minutes.
Vacuum pump oil must never be allowed to enter the refrigeration system.
No leak detection dyes are authorized for use
within any Perlick Refrigeration Products.
Use of these materials will void complete sys tem warranty and place the burden on the service company for down-line service issues.
Cleanliness of the system is extremely important.
The presence of residue (Chlorinated or greasy residues, mineral oil, or impurities) can lead to capillary tube restrictions, oil return prob lems and compressor damage.
A nitrogen purge should be utilized when brazing.
Indicates hazardous situation that may result in death or serious injury if not avoided.
-
Caution indicates hazardous situation that could result in minor or moderate injury and property damage.
­Caution without symbol indicates unsafe practice
situation that could result in property damage only.
Return to Table of Contents
Safety Information Page 2-1
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
3.0 Trouble Shooting Guide
Refrigeration System
Use this diagnostic guide to identify issues and to locate applicable instructions within this service manual. This diagnostic guide can be used for any of Perlick’s Residential and Front Venting Commercial Series Re frigeration Products.
ELECTROCUTION HAZARD!! Never attempt to repair or perform maintenance on the unit until the Main electrical power has been disconnected.
PROBLEM CAUSE SOLUTION
Refrigerator does not run. No power to the unit. Check circuit protection devices. Fuses,
breakers, GFI). Restore power to unit.
Refer to information plate. See and
Table 8-1.
Section 1.2
-
Incorrect control settings or faulty control.
Refrigerator is too warm. Power
No power to unit.
Incorrectly wired internal wiring connec tions.
Fans
Evaporator fan is not running. Refer to Evaporator fan is not running
Coils
Evaporator coil has iced over.
Condensing coil is not clean. Clean with soft brush and vacuum.
Fins are bent or damaged. Straighten ns.
Control
No power to control. Refer to Control not functioning
Control is not calling for cooling. Refer to Control not functioning
Return to factory settings (see
Check outlet for voltage. Check power cord connection to machine compartment harness.
Verify wiring per wiring diagram. See
-
Section 8.2.
Reconnect wires if needed.
Remove ice. See
Section 7.4
Section 8.6).
Return to Table of Contents
Troubleshooting Guide - Refrigeration System Page 3-1
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
PROBLEM CAUSE SOLUTION
Probe failure.
Refrigerator is too warm. (continued)
Refrigerator is too cold.
Probe is not connected to the control.
Air Inltration
Sealing compound does not form a com plete seal.
Door gasket is damaged or out of place.
Condensate drain line/air trap is not positioned properly.
Incorrect control settings.
Probe failure.
Refer to place probe if needed. See Section 8.6.4.
Reconnect probe. See
-
Refer to
Refer to
Reposition in loop. See
Return to factory settings. See
Table 8-21 for resistance values. Re-
Section 8.6.4.
Section 7.1.
Sections 7.1 and 9.5.
Figure 7-3.
Section 8.6.
Table 8-21 for resistance values. Replace
probe if needed. See Section 8.6.4.
Control failure. Refer to Electrical System
Refrigerator runs continu ously.
-
Condensing coil is dirty. Clean with soft brush and vacuum.
Incorrect control settings.
Probe failure.
Return to factory settings.
Section 8.6.
See
Table 8-21 for resistance values. Replace
Evaporator coil has iced over.
Sealing compound does not form a com plete seal.
Door gasket is damaged or out of place.
Condensate drain line/air trap is not posi tioned properly.
Extreme ambient conditions.
probe if needed. See
Remove ice per
-
Refer to
Refer to
-
Reposition in loop. See
Refer to
Section 7.1.
Section 7.1 and 9.5.
Section 7.8.
Section 8.6.4.
Section 7.4.
Figure 7-3.
Return to Table of Contents
Troubleshooting Guide - Refrigeration System Page 3-2
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
PROBLEM CAUSE SOLUTION
Water on the oor outside
of unit.
Water on the oor outside
of unit. (continued)
Refrigeration/Charge level is too low.
High ambient temperature and high am bient humidity conditions coupled with frequent door opening.
Condensate pan overowing.
Unit is not level.
Sealing compound does not form a com plete seal.
Door gasket is damaged.
Evaporator coil has iced over.
Evaporator pan and/or drain line restricted. Remove restriction.
Check for leaks, repair, and recharge per
Section 7.13 and 7.14.
Ensure doors close completely.
-
Remove excess water. Check for the following:
Air inltration. See
Doors close completely and seals are
intact. See
Ice buildup. See
Unit must be level front-to-back and side-to­side for water to drain properly.
-
Refer to
Refer to
Remove ice. Refer to
Section 9.0.
Section 7.1.
Sections 7.1 and 9.5.
Section 7.1.
Section 7.4.
Section 7.4
Water on the oor inside
of unit.
Unit is not level.
Evaporator coil has iced over.
Unit must be level front-to-back and side-to­side for water to drain properly.
Remove ice. Refer to
Section 7.4
Return to Table of Contents
Troubleshooting Guide - Refrigeration System Page 3-3
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
Electrical System
PROBLEM CAUSE SOLUTION
Compressor is not running.
Condenser fan is not run­ning.
No power to compressor.
No call for cooling from control.
Incorrectly wired connections in machine compartment.
Incorrect control settings.
Faulty control.
Starting device is not operational (start relay/capacitor).
Faulty compressor.
No power to fan
Incorrectly wired.
Check wiring to compressor. Check where power is interrupted between
controller and compressor.
Check control settings or for bad control.
Verify wiring per wiring diagram,
Section 8.2.
Return to factory settings.
Section 8.6.
See
Refer to Control not functioning.
Replace compressor electrical components.
Check compressor, see
Restore power to unit. Refer to information plate. See
Section 7.9
Section 1.0 and Table 8-1
Verify wiring per wiring diagram,
Section 8.2.
Remove obstructions.
Replace condenser fan per
Check wiring and continuity of switch con tacts. Replace switch if defective.
Install bracket and/or align.
Restore power to unit. Refer to information plate. See
Section 7.0.
Evaporator fan is not run ning.
Fan is obstructed.
Fan still does not run.
-
Faulty/defective door switch or wiring to door switch.
Missing or misaligned door switch plunger bracket.
No power to evaporator fan motor.
Section 1.0 and Table 8-1
Fan is obstructed.
Incorrectly wired.
Remove obstruction.
Verify wiring per wiring diagram,
Section 8.2.
Return to Table of Contents
Troubleshooting Guide - Electrical System Page 3-4
-
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
PROBLEM CAUSE SOLUTION
Control not functioning
Lights not functioning
If Evaporator fan is still not running
No power to/from DC inverter/driver (12V).
No power to unit.
Incorrectly wired harness.
No call for cooling.
Light switch in off position.
No power to light.
Faulty LED strip
Faulty/defective door switch or wiring to door switch.
Replace evaporator fan per
If no power: restore power, replace. Refer to
Section 7.11.
Section 1.1.
Restore power to unit. Refer to information plate. See and
Table 8-1
Verify wiring per wiring diagram, Reconnect wires if needed.
Check probe connections and verify resistance readings. Check control settings. Replace control.
Turn on light switch.
Verify wiring per wiring diagram,
Replace LED strip.
Check wiring for continuity of switch contacts. Replace switch if faulty.
Section 1.0
Section 8.2.
Section 8.2.
Light stays on when door is closed.
Eliwell Control: LED
Controller display is ash
ing “E1”
-
Door switch plunger bracket missing or misaligned.
Manual switch is on. Turn off manual switch.
Faulty/defective door switch or wiring to door switch.
Door switch plunger bracket missing or misaligned.
Probe 1 error. Reading out-of-range of operating values.
Install bracket and/or align properly.
Check wiring and continuity of switch contacts. Replace switch if faulty.
Install bracket and/or align properly.
Check probe connections to control.
Check probe resistance readings per
Table 8-21.
Check probe wiring.
Return to Table of Contents
Troubleshooting Guide – Beverage Dispensing Page 3-5
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
PROBLEM CAUSE SOLUTION
Eliwell Control: LED
Controller display is ash
ing “AH1”
Eliwell Control: LED
Controller display is ash
ing “AH1” (continued)
-
-
Probe 1 HIGH temperature alarm.
Control
Incorrect control settings.
Power
Incorrectly wired.
Fans
Evaporator fan is not running.
Coils
Evaporator coil has iced over.
Coils
(continued)
Condensing coil is not clean.
Fins are bent or damaged.
Replace probe per Section 8.6.3.
Return to factory settings. See
Verify wiring per wiring diagram,
Section 8.2.
Refer to Evaporator fan is not running.
Remove ice. See
Clean with soft brush and vacuum.
Straighten ns.
Section 7.4
Section 8.6.
Eliwell Control: LED
Controller display is ash
ing “AL1”
Probe
Probe is not connected to control.
Air Inltration
Sealing compound does not form a complete seal.
Door gasket is damaged or not seated properly.
Condensate drain line/air trap is not positioned properly.
Refrigeration/Charge level is too low.
Probe 1 LOW temperature alarm.
­Incorrect control settings.
Reconnect probe.
See Section 8.6.4.
Refer to
Refer to
Reposition in loop.
Check for leaks, repair, and recharge. See
This is a critically charged system, re charging should only be done when all other options have been thoroughly checked.
Section 7.1.
Section 7.1 and 9.5.
Section 7.13 and 7.14.
Return to factory settings. See
Sections 8.6.
-
Return to Table of Contents
Troubleshooting Guide – Beverage Dispensing Page 3-6
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
PROBLEM CAUSE SOLUTION
Dixell Control: LED
Controller display is ash
ing “P1”.
Dixell Control: LED
Controller display is ash
ing “HA”. Maximum tem­perature alarm.
Dixell Control: LED
Controller display is ash
ing “HA”. Maximum tem­perature alarm. (continued)
Probe failure.
Control failure. Refer to Control not functioning
Probe failure.
­Probe disconnected from control. Plug in probe connector.
Internal compartment has exceeded the high temperature alarm preset value for
­over 30 minutes.
Control
Incorrect control settings.
Power
-
Incorrectly wired.
Fans
Evaporator fan is not running.
Coils
Table 8-21 for resistance values.
Refer to
Table 8-21 for resistance values
Return to factory settings. See
Section 8.6.
Verify wiring per wiring diagram,
Section 8.2.
Refer to Evaporator fan is not running
Evaporator coil has iced over.
Condensing coil is not clean.
Fins are bent or damaged.
Probe
Probe is not connected to the control.
Air Inltration
Sealing compound does not form a com plete seal.
Door gasket is damaged or out of place.
Condensate drain line/air trap is not positioned properly.
Remove ice per
Clean with soft brush and vacuum.
Straighten ns.
Reconnect probe per
-
Refer to
Refer to
Reposition in loop. See
Section 7.1.
Section 7.1 and 9.5.
Section 7.4.
Section 8.6.4.
Figure 7-3.
Return to Table of Contents
Troubleshooting Guide – Beverage Dispensing Page 3-7
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
PROBLEM CAUSE SOLUTION
Check for leaks, repair, and recharge per
Refrigeration/Charge level is too low.
Section 7.13 and 7.14.
Dixell Control: LED
Controller display is ash
ing “LA”. Minimum tem­perature alarm.
Internal compartment has exceeded the low temperature alarm preset value for over 30 minutes.
­Incorrect control settings.
Probe failure.
This is a critically charged system, recharging should only be done when all other options have been thoroughly checked.
Return to factory settings. See
Section 8.6.
Table 8-21 for resistance values.
Return to Table of Contents
Troubleshooting Guide – Beverage Dispensing Page 3-8
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
Doors, Drawers and Shelving
PROBLEM CAUSE SOLUTION
Key won’t come out after
door is locked.
Hinge problems, door misaligned.
Door handles loose
Condensation on glass doors.
Key not in proper position.
Improper door mounting
Excessive wear
Improper handle mounting
Excessive wear
High ambient temperature, high humidity and environmental conditions.
Frequent door opening.
Cabinet temperature too low.
Rotate key to the proper position and remove.
Verify proper mounting. Refer to
Section 9.2.
Replace worn parts. Refer to
Verify proper mounting. Refer to
Replace worn parts. Refer to
Refer to
Condensation may build up on interior of glass from frequent door openings as the cabinet comes back down in temperature condensation will evaporate.
Adjust temperature. Refer to Factory Temperature Settings.
Section 9.2.
Section 9.7.
Section 9.7.
Section 7.8.
Table 8-20.
Return to Table of Contents
Table of Contents Troubleshooting Guide - Doors, Draws and Shelving Page 3-9
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
Beverage Dispensing
DIRECT DRAW SYSTEMS
PROBLEM CAUSE SOLUTION
Beer Foaming
Temperature too warm
(should be 36° F)
Temperature too cold/frozen beer in lines (should be 36° F)
Adjust temperature control or call qualied
service person
Adjust temperature control or call qualied
service person
Kinked beer line Change beer line
Wrong diameter or length beer line (should be
Change beer line
6.5 ft. of 3/16” vinyl tubing or possibly even
longer)
2 regulator to brewer’s specication
Applied pressure too high (should be 12 to 14 psi for most beers)
Adjust C0 (If CO2 pressure has been too high, kegged product may be over-carbonated and be bad and not correctable).
Applied pressure too low (should be 12 to 14 psi for most beers)
Adjust C0
2 regulator to brewer’s specication
Coupler washers bad Replace coupler washers
Faucet washer bad Replace faucet washers
System dirty Clean system or call customer’s line cleaning
service
2 leaks or out of C02 Check ttings, clamps, shut-offs and regulators,
C0
replace as necessary
Beer foaming in jumper - keg valve seal torn or ripped
If seal is ripped/torn, gas enters the liquid ow
stream causing foaming. Replace keg and report defective keg to distributor
Beer foaming in jumper - physical obstructions at coupler-valve junction
Remove any physical obstructions or debris (e.g. a piece of a dust cover) that could allow
gas to enter the liquid ow
Beer foaming at faucet - clogged vent hole(s) (If applicable to the faucet being used)
No Beer at Faucet Empty C0
2 bottle Replace with full C02 bottle
Disassemble and clean faucet, or call line cleaning service
Regulator shutoff closed Open shutoff
2 bottle main valve turned off Tum on C02 bottle main valve
C0
Keg empty Replace with full keg
Coupler not engaged Tap keg properly and engage coupler
Check ball in coupler stuck (If applicable) Free check ball
Line/faucet dirty Clean line/faucet
Return to Table of Contents
Troubleshooting Guide – Beverage Dispensing Page 3-10
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
4.0 Variable Speed Compressor Specication
Never connect compressor directly to AC power!
Always use specied inverter when testing
compressor!
The compressors employed within many of Perlick’s cabinets are on the cutting edge of technology for reciprocating hermetic compressors. The compressors are variable speed models developed and man
ufactured by Embraco. Depending on the model of the cabinet, either a VEMY3H, VEMY6H or VEGY7H
will be found powering the refrigeration system. The compressor itself looks like a standard fractional horsepower hermetic reciprocating compressor. The electrical, overload, relay and capacitor, which are normally found connected to the compressor pins has been replaced by an electronic box which is called the inverter.
-
The inverter is an electronic board, which controls the compressor and has to have power to it at all times for it to function properly. It controls the starting of the compressor and the speed at which it is
running at from 1600 rpm to 4500 rpm. A normal hermetic reciprocating compressor runs at a con stant 3600 rpm. The Digital Temperature Control controls a separate power circuit used as the power
to the inverter driver circuit, which turns the compressor on and off.
The inverter is powered by 115-127V 50-60Hz 1 Ph AC. The inverter driver circuit power is also 115- 127V 50-60Hz 1Ph AC power. The inverter converts this to 230V 53-150Hz 3 Ph power to drive the
compressor. The resistance between any combination of the three compressor pins for the HP24”
Series is 16.07 ohms, and the HP48 & HP72” series is 6.4 ohms. The inverter has a plastic 3-pin recep
tacle which gets plugged onto the compressor pins (can only be installed one way for proper orienta­tion). The inverter also comes with a ground wire, which gets plugged onto the compressor ground lug. The inverter is then mounted to the compressor fence by sliding it down and tipping to the vertical position. A single fastener is then used to mount it to the fence (do not over tighten as it is fastening into the plastic inverter housing).
-
-
Return to Table of Contents
Refrigeration System Repair Instructions Page 4-1
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
5.0 Compressor Inverter Operation
Upon initial power to the inverter, the electronic board is checked for problems or malfunctioning
components. If a problem is detected, the inverter will not allow power to the compressor and will
wait 8 minutes until it will repeat the process to see if it has been corrected.
If the inverter power circuit is interrupted or reduced to a level below operation level, the inverter will
not allow continued operation of the power circuit to the compressor.
Compressor Start-Up
Upon the temperature control calling for cooling, the inverter will wait 1-3 seconds before applying
current to the compressor motor for the rst time. In case of any abnormality in trying to start the
compressor (unequal pressures, locked rotor condition or open winding, etc.), the inverter will wait
6 seconds before establishing a new start-up trial.
The maximum number of start-up trials is 12. If the compressor does not start after 12 trials, a
start-up error is set, and the system will wait for 8 minutes to repeat the starting procedure.
During start-up of the compressor, the current is limited in accordance with the type of motor
connected to the inverter. The compressor always starts in its minimum rpm condition (1600 rpm)
to conserve energy and alleviate noise associated with a standard compressor start-up.
During initial power being applied to the refrigerated cabinet, the compressor will always start in its
minimum rpm condition (1600 rpm) and remain at this speed for 7 minutes. After this time has
passed the program will move the compressor to its maximum rpm level until the initial controller cut-out temperature has been achieved.
Normal Operation
During running condition, the speed is measured each shaft turn and the result is compared with the desired speed. If the actual speed is lower than desired, the inverter will increase the power applied to the motor, which in turn will increase the shaft speed until the equilibrium is achieved. The opposite can happen likewise, in that if the actual speed is higher than the desired speed, the inverter will decrease the power applied to the motor, which in turn will decrease the shaft speed until the equilibrium is achieved.
The compressor will generally run at its slowest speed (1600 rpm) during normal cycling conditions with
out added load to the cabinet or door openings. This is done to conserve energy and reduce noise. A typ­ical refrigeration system is designed for high load, high ambient conditions, meaning the compressor is
typically oversized for normal daily operation. It has been shown in residential equipment that a refriger ator or freezer or combination of the two with standard reciprocating compressor is typically designed for
conditions it sees less than 25% of the time (high load/high ambient). While employing the variable speed
compressor the equipment has been designed for the conditions it sees 75% of the time while still having
the capacity to cover the conditions it sees 25% of the time.
-
-
Return to Table of Contents
Troubleshooting Guide – Beverage Dispensing Page 5-1
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
6.0 Troubleshooting Compressor Inverter
Ensure the inverter has 120V applied to the two pin connector on the inverter. If no power,
check where power is interrupted.
If temperature control is calling for cooling, check inverter signal circuit for 120V, typically the red lead. If no power, check where power is interrupted. If there is power, disconnect power to the entire unit and wait 5 minutes to ensure internal system pressures are
equalized. Plug in unit and feel top of compressor to see if it is trying to start (see in-
formation from section Compressor Start-Up above). If compressor is trying to start, but unable to, the system could have a restriction, the inverter may not be applying the correct power to the compressor pins (check pins to see if getting 120V to each pin).
Resistance between all pins should be the same. Dependent upon temperature of the com-
pressor, resistance could be different than the resistance specied at the standard tem­perature.
7.0 Refrigeration System Repair Instructions
Air Inltration
Air inltration can occur in several locations.
Note: Unit may manifest longer than normal run
times caused by the additional loads that
air inltration presents.
Signs of air inltration include:
Presence of water, moisture or ice
Condensation on glass or metal surfaces
STEP 1. Door Gaskets
Check door gaskets for rips, cracks, or oth er damage.
The door gasket should be pushed in rmly and lay at.
Ensure gasket forms a complete seal around door.
-
STEP 2. Sealing Compound
Sealing compound is used to seal wiring and line set pass-through between the con denser and the evaporator compartments.
See Figure 7-1 and Figure 7-2.
Check for voids and ensure sealing
compound completely lls the space.
Figure 7-1. Sealing Compound at Wiring Pass-through –
-
Back
Return to Table of Contents
Troubleshooting Guide – Beverage Dispensing Page 7-1
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
Figure 7-2. Sealing Compound at Wiring Pass-through –
Inside
STEP 3. Drain
Check that the evaporator condensate drain is
secure and connected. Figure 7-3.
Figure 7-3. Evaporator Condensate Drain
Note: Drain tube should be routed through metal bracket and end of tube should be retained by metal
insert to create a trap. This trap should be lled with
water to prevent air from moving through the tube and into the cabinet. Sometimes, gurgling sounds will be heard upon the door closing as the internal cabinet pressure changes requiring air to be pushed out which happens through the drain tube trap.
Return to Table of Contents
Refrigeration System Repair Instructions Page 7-2
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
System Operating Pressures
Note: To check operating pressures, you must install access valves onto the process tubes. See Section
7.2.1.
Values in
Table 7-1
represent a range of normal pressures. The measured pressure can vary depending on
ambient conditions and at the point at which unit is in the refrigeration cycle.
Operating pressures shown in Table 7-1 are nominal and dependent on many factors (box temperature, position in the refrigeration cycle, cleanliness of the condenser, etc.), should only be used as reference.
Never add or remove charge based on the operating pressures in Table 7-1. These prod
­ucts are critically charged and must have the refrigerant charge weighed into the system with accurate equipment to plus/minus 2 grams.
Table 7-1. System Operating Pressures
70° F
Ambient
90° F 105° F
Models Low/High Low/High Low/High
Freezer 4” Hg/105 PSIG 3” Hg/145 PSIG 2” Hg/185 PSIG
Medium Temp* 15 PSIG /110 PSIG 16 PSIG /150 PSIG 17 PSIG /190 PSIG
Dual Zone Frz/Ref 5” Hg/105 PSIG 4” Hg/145 PSIG 3” Hg/185 PSIG
Dual Zone Medium Temp** 12 PSIG /110 PSIG 13 PSIG /150 PSIG 14 PSIG /190 PSIG
*Medium Temp = Refrigerator, Beverage Center, Wine Reserve, Beer Dispenser
**Dual Zone Medium Temp = Ref/Wine and Wine/Wine
Return to Table of Contents
Refrigeration System Repair Instructions Page 7-3
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
7.2.1 Process Tubes and Access Valve
Refrigerant system is hermetically sealed. Use access tubes to charge unit and check pressure.
Note: Access valves (saddle valves) are not
provided and may vary.
Access valves should never be left on the
equipment permanently as they tend to leak over time. Install Schrader valves any time the system has been accessed.
Shelf Lock
Figure 7-5. Remove Shelves
Saddle
Valve
Figure 7-4. Process Tubes
Remove Evaporator Fan Panel STEP
STEP 1.
Remove shelves, shelf slides and pilasters from refrigerator section nearest the evaporator coil.
To remove a full extension shelf, pull shelf out so it is fully extended, release lock mechanism on each
slide and pull out shelf. See Figure 7-5.
To remove the slides, lift up on front of slide and pivot slightly inward to remove from the front pilaster key slot. Pull slide forward to remove slide
from rear pilaster key slot. See Figure 7-6.
Remove screws from pilasters and remove. See
Figure 7-7.
Figure 7-6. Remove Shelf Slide
Figure 7-7. Remove Pilaster
Return to Table of Contents
Refrigeration System Repair Instructions Page 7-4
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
STEP 2.
Remove Evaporator Fan panel by removing 2 (or
4) Phillips head screws from around the evaporator
fan. See Figure 7-8.
Figure 7-8. Evaporator Fan Panel Screw Locations
STEP 3.
Pull outward from fan cutouts using a small screwdriver, tilt panel top out towards you.
Pull up on panel to release anges from the
bottom inner liner of cabinet.
Carefully remove panel from cabinet.
De-Ice Blocked Evaporator Coil
Use towels to absorb water to avoid damage to ma-
chine compartment or surrounding ooring. Machine compartment condensate pan may overow if manu-
ally defrosted without use of towels.
STEP 1.
Remove evaporator fan panel. See Section 7.3.
STEP 2.
Using a fan or heat gun to gently direct warm air
over ice to remove. See Figure 7-10.
Figure 7-9. Remove Evaporator Fan Panel
Figure 7-10. Deicing Evaporator
DO NOT use any tools to chip at or physically remove ice!
STEP 3. When ice has been removed:
Check sealing compound. Re-forming, if necessary, to close any gaps around wire harness and piping.
Check for other potential sources of air inltration. See Section 7.1.
STEP 4.
Reverse steps in Section 7.3 to close the
evaporator fan panel.
Return to Table of Contents
Refrigeration System Repair Instructions Page 7-5
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
Evaporator Airow by Model
Standard-In at the bottom through louvers, out at the top through fan.
Model
Evaporator Airow
Direction
HA24BB Standard HA24FB Standard HA24RB Standard HA24WB Standard HB24BS Standard HB24FS Standard HB24RS Standard HB24WS Standard HC24FS Standard HC24RS Standard HC24WS Standard HC48RS Standard HC48RW Standard RC48WS Standard HC48WW Standard HD24RS Standard HD24WS Standard HH24BO Standard HH24BS Standard HH24RO Standard HH24RS Standard HH24WO Standard HH24WS Standard HHA24BO Standard HHA24RO Standard HHA24WO Standard HK24BO Standard HK24FO Standard HK24RO Standard HK24TO Standard HK24WO Standard HM24RO Standard HM24TO Standard HP24BO Standard HP24BS Standard HP24FO Standard HP24FS Standard HP24RO Standard
Return to Table of Contents
Return to Table of Contents Refrigeration System Repair Instructions Page 7-6
HP24RS Standard HP24TO Standard HP24TS Standard HP24WO Standard HP24WS Standard HPA24BO Standard HPA24RO Standard HPA24WO Standard HP48WO-S Standard HP48WW-S Standard
Reverse-In at the top through fan, out at the bottom through louvers
Model Evaporator Airow Direction
HC24BB Reverse HC24RB Reverse HC24RO Reverse HC24TB Reverse HC24TO Reverse HC24WB Reverse HK15BO Reverse HK15RO Reverse HK15TO Reverse HK15WO Reverse HK24CO Reverse HK24DO Reverse HK24ZO Reverse HM24CO Reverse HP15BO Reverse HP15BS Reverse HP15RO Reverse HP15RS Reverse HP15TO Reverse HP15TS Reverse HP15WO Reverse HP15WS Reverse HP24CO Reverse HP24CS Reverse HP24ZO Reverse HP24ZS Reverse
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
Air Flow Obstructions
The unit must have free air ow to front grille to
operate properly.
Restricted air ow results in high head pressures and reduction in efciency due to longer run times.
Proper air ow through condenser and evaporator is necessary for efcient operation.
Never obstruct air ow in and out of the
machine compartment.
The front grille must be free from obstructions, dust, and debris.
Never obstruct air ow to Evaporator Fan.
Make sure higher temperature ambient air from
another unit is not directed to condenser coil (i.e. another heat source directly across from the unit).
Figure 7-12. Remove Front Grille
Figure 7-11. Check for Obstructions
Clean Condenser Coil
ELECTROCUTION HAZARD!! Never attempt to repair or perform maintenance on the unit until the Main electrical power has been dis connected.
Perlick’s warranty does not cover cleaning of con denser.
The condenser is located directly behind the front
grille. See Figure 7-11 through Figure 7-13.
-
-
Figure 7-13. Clean Condenser Coils
Condenser coils that are covered with dust and de-
bris restrict air ow. This results in high head pres­sures and lower efciency due to longer run times.
Use soft brush and vacuum to clean coil every 90 days, or more often if conditions require.
Ambient Temperature
High ambient temperature and high humidity condi­tions may result in performance issues and/or refrig­eration system failure.
The unit must be protected from precipitation.
Do not subject to direct solar load.
Under extreme temperature and/or relative humidity conditions the front face, gasket and/or glass door may show signs of condensation. When temperature and/or relative humidity conditions return to normal condensation will disappear.
Return to Table of Contents
Refrigeration System Repair Instructions Page 7-7
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
Compressors
Table 7-2. Compressor Data
START
WINDING
COMPRESSOR
MODEL HP
EM30HHR 1/10 RSIR 20.9 5.5 14.5
EM65HHC 1/6+ RSCR 3.7 3.2 15.0 PTC
EM20HSC 1/10 RSCR 13.2 9.3 5.2 TSD2-115V
EM3D50HLT 1/5 RSCR 5.9 5.4 8.0
VEGY3H 1/10 BPM 16.1 16.1 2.1 Inverter Inverter N/A
VEGY7H 1/4 BPM 6.4 6.4 3.3 Inverter Inverter N/A
MOTOR
TYPE
RESISTANCE
Ω AT 77°F
(+/-8%)
RUN
WINDING
RESISTANCE
Ω AT 77°F
(+/-8%)
LOCKED
ROTOR
AMPERAGE
(LRA)
STARTING
DEVICE
Current
Relay
TSD2-
115V0.6
MOTOR
PROTECTION
4TM575MFBYY-
53
4TM427NFBYY-
53
4TM189KFBYY-
53
4TM302KFBYY-
53
CAPACITOR (Run/Start)
(uF/VAC Minimum)
Run (20/170)
Run (5/175)
Run (15/200 or
N/A
12/200)
Return to Table of Contents
Refrigeration System Repair Instructions Page 7-8
Residential Refrigeration and Front Venting Commercial Refrigeration Service Manual
Replace Condenser Fan Motor
STEP 1.
Remove equipment compartment rear cover.
STEP 2.
Unplug the fan power leads. See Figure 7-14.
STEP 3.
Note orientation of fan motor (air should be pulled through the condenser). Remove fan motor by removing 2 Phillips head screws that hold the fan bracket. The condensate pan may need to be removed to access the screws (condensate pan is installed using double sided tape). If the conden sate pan is removed, reinstall properly to prevent vibration/noise issues.
-
Replace Evaporator Fan Motor
STEP 1.
Remove evaporator fan panel. See Section 7.3.
STEP 2.
Note orientation of the fan motor so when re-in
stalled, the unit has the correct direction of airow.
Remove 2 Phillips head screws that hold fan to bracket.
NOTE: The evaporator fan bracket may need to be removed from the rear wall of the cabinet (4 screws) to access the fasteners holding the fan in place.
-
Power
Leads
Figure 7-14. Condenser Fan Mounting Hardware
STEP 4.
Install new fan motor using 2 Phillips head screws and connect power leads. Use only original Perlick OEM parts.
STEP 5.
Install equipment compartment rear cover.
Return to Table of Contents
Refrigeration System Repair Instructions Page 7-9
Loading...
+ 95 hidden pages