Perlick DZS36 Service Manual

Scan here to
download a pdf copy
of this manual.
SERVICE MANUAL
Commercial Back Bar Refrigeration
Self-Contained and Remote
BBS60
(w/glass door option shown)
BBR96
(w/glass door and solid stainless steel door
options shown)
Product Series Covered in this manual:
Self-Contained
BBS
BBSN
PTS
DZS
SDBS
SDPS
BBSLP
DDC
DDS
Remote
BBR
BBRN
PTR
SDBR
SDPR
BBRLP
SELF-CONTAINED
REMOTE
BBS
BBR
BBSN
BBRN
PTS
PTR
DZS
SDBR
SDBS
SDPR
SDPS
BBRLP
BBSLP
DDC
DDS
HAZARD!! Indicates hazardous situation that will result in death or serious injury if not avoided.
Indicates hazardous situation that may result in death or serious injury if not avoided.
Caution indicates hazardous situation that could result in minor or moderate injury and property damage.
Caution without symbol indicates unsafe practice situation that could result in property damage only.
ELECTROCUTION HAZARD!! Never attempt to repair or perform maintenance on the unit until the Main electrical power has been disconnected.
PROBLEM
CAUSE
SOLUTION
Refrigerator does not run.
No power to the unit.
Check circuit protection devices. Fuses, breakers, GFI).
Restore power to unit. Refer to information plate. See Section 1.0
and Table 7-1.
Incorrect control settings or faulty control.
Return to factory settings (see Sections
7.5.1 and 7.5.2) or replace control.
Refrigerator is too warm.
Power
No power to unit.
Restore power to unit. Refer to information plate. See Section 1.0
and Table 7-1.
Incorrectly wired internal wiring connections.
Verify wiring per wiring diagram. See Section 7.2.
Reconnect wires if needed.
Fans
Evaporator fan is not running.
Refer to Evaporator fan is not running
Coils
Evaporator coil has iced over.
Remove ice. See Section 6.5
Condensing coil is not clean.
Clean with soft brush and vacuum.
Fins are bent or damaged.
Straighten fins.
Control
No power to control.
Refer to Control not functioning
Control is not calling for cooling.
Refer to Control not functioning
Probe failure.
Refer to Table 7-5 for resistance values. Replace probe if needed. See Section
7.5.4.
PROBLEM
CAUSE
SOLUTION
Probe is not connected to the control.
Reconnect probe. See Section 7.5.4.
Refrigerator is too warm. (continued)
Air Infiltration
Sealing compound does not form a complete seal.
Refer to Section 1.1.
Door gasket is damaged or out of place.
Refer to Sections 1.1 and 8.6.
Condensate drain line/air trap is not positioned properly.
Reposition in loop. See Figure 6-3.
Refrigerator is too cold.
Incorrect control settings.
Return to factory settings. See Sections 7.5.1 and 7.5.2.
Probe failure.
Refer to Table 7-5 for resistance values. Replace probe if needed. See Section
7.5.4.
Control failure.
Refer to Troubleshooting Guide – Electrical System
Refrigerator runs continuously.
Condensing coil is dirty.
Clean with soft brush and vacuum.
Incorrect control settings.
Return to factory settings. See Sections 7.5.1 and 7.5.2.
Probe failure.
Refer to Table 7-5 for resistance values. Replace probe if needed. See Section
7.5.4.
Evaporator coil has iced over.
Remove ice per Section 6.5.
Sealing compound does not form a complete seal.
Refer to Section 1.1. Door gasket is damaged or out of place.
Refer to Section 1.1 and 8.6.
Condensate drain line/air trap is not positioned properly.
Reposition in loop. See Figure 6-3.
Extreme ambient conditions.
Refer to Section 6.8.
Refrigeration/Charge level is too low.
Check for leaks, repair, and recharge per Section 6.13 and 6.16.
Water on the floor outside of unit.
High ambient temperature and high ambient humidity conditions coupled with frequent door opening.
Ensure doors close completely.
PROBLEM
CAUSE
SOLUTION
Condensate pan overflowing.
Remove excess water. Check for the following:
Air infiltration. See Section 6.1.
Doors close completely and seals are
intact. See Section 8.6.
Ice buildup. See Section 6.5.
Unit is running properly. Repair if
needed.
Water on the floor outside of unit. (continued)
Unit is not level.
Unit must be level front-to-back and side­to-side for water to drain properly.
Sealing compound does not form a complete seal.
Refer to Section 1.1. Door gasket is damaged.
Refer to Sections 1.1 and 8.6.
Remote ONLY: Floor drain plumbed incorrectly.
Check to make sure drain path makes sense. Refer to installation manual.
Evaporator coil has iced over.
Remove ice. Refer to Section 6.5
Water on the floor inside of unit.
Evaporator pan and/or drain line restricted.
Remove restriction.
Unit is not level.
Unit must be level front-to-back and side­to-side for water to drain properly.
Evaporator coil has iced over.
Remove ice. Refer to Section 6.5
PROBLEM
CAUSE
SOLUTION
Compressor is not running.
No power to condensing unit.
Check condensing unit is plugged in. Check power at internal receptacle.
No call for cooling from control.
Check control settings or for bad control.
Incorrectly wired connections in condensing unit.
Verify wiring per wiring diagram, Section
7.2. Reconnect wires if needed.
Incorrect control settings.
Return to factory settings. See Sections 7.5.1 and 7.5.2.
No power to compressor.
Restore power to unit. Refer to information plate. See Section
1.2 and Table 7-1
Faulty control.
Refer to Control not functioning.
Starting device is not operational (start relay/capacitor).
Replace compressor electrical components.
Faulty compressor.
Replace compressor per Section 6.14.
Condenser fan is not running.
No power to fan
Restore power to unit. Refer to information plate. See Section
1.0 and Table 7-1
Incorrectly wired harness.
Verify wiring per wiring diagram, Section
7.2. Reconnect wires if needed.
Fan is obstructed.
Remove obstructions.
Fan still does not run.
Replace condenser fan per Section 6.13.
Evaporator fan is not running.
No power to evaporator fan motor.
Restore power to unit. Refer to information plate. See Section
1.0 and Table 7-1
Fan is obstructed.
Remove obstruction.
Incorrectly wired harness.
Verify wiring per wiring diagram, Section
7.2. Reconnect wires if needed.
If Evaporator fan is still not running…
Replace evaporator fan per Section 6.13.
BBSLP series ONLY: No power to/from DC inverter/driver (12V).
If no power: restore power, replace. Refer to Section 1.1.
PROBLEM
CAUSE
SOLUTION
Control not functioning
No power to unit.
Restore power to unit. Refer to information plate. See Section
1.0 and Table 7-1
Incorrectly wired harness.
Verify wiring per wiring diagram, Section
7.2. Reconnect wires if needed.
No call for cooling.
Replace controller
Lights not functioning
Light switch in off position.
Turn on light switch.
No power to DC driver.
See unit info plate for voltage. Check output of DC driver (12V).
No power to light switch. (12V)
Check wiring back to DC driver, replace if needed.
Incorrectly wired lighting switch.
Verify wiring per wiring diagram, Section
7.2. Reconnect wires if needed.
No power to LED strips? (12V)
Check wiring backwards to light switch.
Faulty LED strip
Replace LED strip.
Light stays on when door is closed.
Manual switch is on.
Turn off manual switch.
Eliwell Control: LED Controller display is flashing “E1”
Probe 1 error. Reading out-of-range of operating values.
Check probe connections to control.
Check probe resistance readings per Table 7-5.
Check probe wiring.
Replace probe per Section 7.5.3.
Eliwell Control: LED Controller display is flashing “AH1”
Probe 1 HIGH temperature alarm.
Control
Incorrect control settings.
Return to factory settings. See 7.5.1 and 7.5.2.
Power
Incorrectly wired harness.
Verify wiring per wiring diagram, Section 7.2. Reconnect wires if needed.
Fans
Evaporator fan is not running.
Refer to Evaporator fan is not running.
Coils
Evaporator coil has iced over.
Remove ice. See Section 6.5
PROBLEM
CAUSE
SOLUTION
Eliwell Control: LED Controller display is flashing “AH1” (continued)
Coils
(continued)
Condensing coil is not clean.
Clean with soft brush and vacuum.
Fins are bent or damaged.
Straighten fins.
Probe
Probe is not connected to control.
Reconnect probe. See Section 7.5.4.
Air Infiltration
Sealing compound does not form a complete seal.
Refer to Section 1.1.
Door gasket is damaged or not seated properly.
Refer to Section 1.1 and 8.6.
Condensate drain line/air trap is not positioned properly.
Reposition in loop. See Control not functioning.
Refrigeration/Charge level is too low.
Check for leaks, repair, and recharge. See Section 6.13 and 6.16.
This is a critically charged system, recharging should only be done when all other options have been thoroughly checked.
Eliwell Control: LED Controller display is flashing “AL1”
Probe 1 LOW temperature alarm.
Incorrect control settings.
Return to factory settings. See Sections 7.5.1 and 7.5.2.
Probe failure.
Refer to Table 7-5 for resistance values. Replace probe if needed.
See Section 7.5.4.
Control failure.
Refer to Control not functioning
Dixell Control: LED Controller display is flashing “P1”.
Probe failure.
Contact dealer.
Probe disconnected from control.
Plug in probe connector.
Dixell Control: LED Controller display is
flashing “HA”. Maximum
temperature alarm. Internal compartment has exceeded
the high temperature alarm preset value for over 30 minutes.
Control
Incorrect control settings.
Return to factory settings. See Sections 7.5.1 and 7.5.2.
PROBLEM
CAUSE
SOLUTION
Dixell Control: LED Controller display is
flashing “HA”. Maximum
temperature alarm. (continued)
Power
Incorrectly wired harness and/or internal wiring connections.
Verify wiring per wiring diagram, Section 7.2. Reconnect wires if needed.
Fans
Evaporator fan is not running.
Refer to Evaporator fan is not running
Coils
Evaporator coil has iced over.
Remove ice per Section 6.5.
Condensing coil is not clean.
Clean with soft brush and vacuum.
Fins are bent or damaged.
Straighten fins.
Probe
Probe is not connected to the control.
Reconnect probe per Section 7.5.4.
Air Infiltration
Sealing compound does not form a complete seal.
Refer to Section 1.1.
Door gasket is damaged or out of place.
Refer to Section 1.1 and 8.6.
Condensate drain line/air trap is not positioned properly.
Reposition in loop. See Figure 6-3.
Refrigeration/Charge level is too low.
Check for leaks, repair, and recharge per Section 6.13 and 6.16.
This is a critically charged system, recharging should only be done when all other options have been thoroughly checked.
Dixell Control: LED Controller display is
flashing “LA”. Minimum
temperature alarm.
Internal compartment has exceeded the low temperature alarm preset value for over 30 minutes.
Incorrect control settings.
Return to factory settings. See 7.5.1 and 7.5.2.
Probe failure.
Refer to Table 7-5 for resistance values. Replace probe if needed. See Section
7.5.4.
Control failure.
Refer to Control not functioning
PROBLEM
CAUSE
SOLUTION
Key won’t come out
after door is locked.
Key not in proper position.
Rotate key to the proper position and remove.
Sliding doors not closing.
Replace spring and/or torpedo assembly.
Refer to Section 8.4.3.
Hinge problems, door falling off.
Improper door mounting
Verify proper mounting. Refer to Section 8-4.
Excessive wear
Replace worn parts. Refer to Section 8-4.
Door handles falling off
Improper handle mounting
Verify proper mounting. Refer to diagram.
Excessive wear
Replace worn parts. Refer to diagram.
Condensation on glass doors.
High ambient temperature, high humidity and environmental conditions.
Refer to Section 6.7. Frequent door/drawer opening.
Refer to Section 8.1.
Cabinet temperature too low.
Adjust temperature. Refer to Table 7-4. Factory Temperature Settings.
Sliding doors dragging or binding
Debris in track.
Remove doors Clean tracks and lube with NSF
approved food grade lube.
Must be hooked up to an external floor drain, not floor inside unit or floor under unit.
RUNNING PRESSURE
Low Side
15-20 PSIG
High Side
120-180 PSIG
Fully Left
Back seated with flow from refrigeration system closed.
Middle
Allows flow from the refrigeration system to the service port.
Fully Right
Front seated with flow to the service port closed.
DO NOT use any tools to chip at or physically remove ice!
ELECTROCUTION HAZARD!! Never attempt to repair or perform maintenance on the unit until the Main electrical power has been disconnected.
Supply Air
Plenum
Product
Guard
Air Intake
MODEL
/FAMILY
HP
WIRING
START WINDING
RESISTANCE
Ω AT 77°F
RUN WINDING
RESISTANCE
Ω AT 77°F
RUN/START
BBS36
1/5
RSIR
8.85
3.85
12.70
BBS60
1/4
CSIR
4.15
1.55
5.70
BBS84
1/3
CSIR
3.87
1.04
4.91
BBS108
1/3
CSIR
3.87
1.04
4.91
BBSN32
1/5
RSIR
8.85
3.85
12.70
BBSN52
¼
CSIR
4.15
1.55
5.70
BBSN72
1/3
CSIR
3.87
1.04
4.91
BBSN92
1/3
CSIR
3.87
1.04
4.91
PTS36
1/5
RSIR
8.85
3.85
12.70
PTS60
1/4
CSIR
4.15
1.55
5.70
PTS84
1/3
CSIR
3.87
1.04
4.91
DZS36
1/5
RSIR
8.85
3.85
12.70
DZS60
1/4
CSIR
4.15
1.55
5.70
SDBS60
1/4
CSIR
4.15
1.55
5.70
SDBS108
1/3
CSIR
3.87
1.04
4.91
SDPS60
1/4
CSIR
4.15
1.55
5.70
BBSLP36
1/5
RSIR
8.85
3.85
12.70
BBSLP60
¼
CSIR
4.15
1.55
5.70
BBSLP84
1/3
CSIR
3.87
1.04
4.91
BBSLP108
1/3
CSIR
3.87
1.04
4.91
DDC68
1/4
CSIR
4.15
1.55
5.70
DDC92
1/3
CSIR
3.87
1.04
4.91
DDS36
1/5
RSIR
8.85
3.85
12.70
DDS60
1/4
CSIR
4.15
1.55
5.70
DDS84
1/3
CSIR
3.87
1.04
4.91
DDS108
1/3
CSIR
3.87
1.04
4.91
Fully Left
Back seated with flow from refrigeration system closed.
Middle
Allows flow from the refrigeration system to the service port.
Fully Right
Front seated with flow to the service port closed.
Once charge level has been set, avoid installing gauges as part of regular service. System should be kept sealed.
Starting device
Capacitor
Unit Type
Model Number
Running Load Amps
Electrical Supply
Electrical Connection
Self-Contained
BBS36
3.2
120 VAC/60 Hz/1 Ph
Cord Connected
BBS60
5.5
BBS84
6.3
BBS108
6.3
BBSLP36
3.0
BBSLP60
5.3
BBSLP84
6.7
BBSLP108
6.7
BBSN32
3.2
BBSN52
5.5
BBSN72
6.3
BBSN92
6.3
DDS36
3.2
DDS60
5.5
DDS84
6.3
DDS108
6.3
DDC68
5.5
DDC92
6.3
DZS36
3.2
DZS60
5.5
PTS36
3.2
PTS60
5.5
PTS84
6.3
SDBS60
5.5
SDBS108
6.3
SDPS60
5.5
Remote
BBR24
1.1
120 VAC/60 Hz/1 Ph
Hard Wired
BBR48
1.6
BBR72
2
BBR96
2.5
BBRLP48
1.6
BBRLP72
2
BBRLP96
2.5
BBRN40
1.6
BBRN60
2
BBRN80
2.5
PTR48
1.6
PTR72
2
SDBR48
1.6
SDBR96
2.5
SDPR48
1.6
Loading...
+ 56 hidden pages