Perfect Aire 2PAMSH09A-17, 2PAMSH12B-17.5, 2PAMSH09B-17, 2PAMSH12A-17.2, 2PAMSH18B-17.7 Installation Manual

...
DUCTLESS MINI-SPLIT SYSTEM
17 SEER, HEAT PUMP
INSTALLATION MANUAL
115V SYSTEMS:
2PAMSH09A-17 2PAMSH12A-17.2
208/230V SYSTEMS:
SINGLE ZONE
Before using your air conditioner please read this manual carefully and keep it for future reference, along with your receipt.
Table of Contents
Installation Manual
Safety Precautions ..........................................................................................1
Accessories .....................................................................................................3
Installation Summary - Indoor Unit................................................................5
Unit Parts..........................................................................................................7
Indoor Unit Installation ...................................................................................8
4.1 Select installation location.................................................................................. 8
4.2 Attach mounting plate to wall .............................................................................9
4.3 Drill wall hole for connective piping .................................................................... 9
4.4 Prepare refrigerant piping ................................................................................ 11
4.5 Connect drain hose .......................................................................................... 12
4.6 Connect signal cable........................................................................................ 14
4.7 Wrap piping and cables.................................................................................... 15
4.8 Mount indoor unit .............................................................................................15
Outdoor Unit Installation ..............................................................................17
5.1 Select installation location................................................................................ 17
5.2 Install drain joint ............................................................................................... 18
5.3 Anchor outdoor unit.......................................................................................... 19
5.4 Connect signal and power cables .................................................................... 20
Refrigerant Piping Connection.....................................................................22
6.1 Note on pipe length .......................................................................................... 22
6.2 Connection instructions - Refrigerant Piping.................................................... 22
STEP 1: Cut pipe .............................................................................................22
STEP 2: Remove burrs .................................................................................... 23
STEP 3: Flare pipe ends .................................................................................. 23
STEP 4: Connect pipes.................................................................................... 24
Air Evacuation ...............................................................................................26
7.1 Evacuation instructions .................................................................................... 26
7.2 Note on adding refrigerant ...............................................................................27
Electrical and Gas Leak Checks ..................................................................28
Test Run..........................................................................................................29
Page 1
This symbol indicates that ignoring instructions may cause death or serious injury.
This symbol indicates that ignoring instructions may cause moderate injury to your person, or damage to your unit or other property
Safety Precautions
Read Safety Precautions Before Installation
Incorrect installation due to ignoring or not following installation and usage instructions can cause serious
damage or injury. The seriousness of potential damage or injuries is classified as either a WARNING
or CAUTION.
WARNING
CAUTION
WARNING
When connecting refrigerant piping, do not let substances or gases other than the specified refrigerant
enter the unit. The presence of other gases or substances will lower the unit’s capacity and can cause
Do not allow children to play with the air conditioner. Children must be supervised around the unit at
all times.
1. Installation must be performed by an authorized dealer or certified HVAC specialist. Defective or incorrect installation can cause water leakage, electrical shock, or fire.
2. Installation must be performed according to the installation instructions. Improper installation can cause water leakage, electrical shock, or fire. (In North America, installation must be performed in accordance with the requirement of NEC and CEC by authorized personnel or a certified HVAC contractor only.)
3. Contact an authorized HVAC service technician for repair or maintenance of this unit.
4. Only use the included accessories, parts, and specified parts for installation. Using non-standard parts can cause water leakage, electrical shock, fire, and can cause the unit to fail.
5. Install the unit in a firm location that can support the unit’s weight. If the chosen location cannot support the unit’s weight, or the installation is not done properly, the unit may fall and cause serious injury and damage.
This symbol indicates that you must never perform the action indicated.
abnormally high pressure in the refrigeration cycle. This can cause explosion and injury.
NEVER splice any electrical connection. A poor electrical connection, poor insulation or voltage which is higher than permitted can cause fire.
WARNING (continued)
6. For all electrical work, follow all local and national wiring standards, regulations, and the Installation Manual. You must use an independent circuit and single phase to supply power. Do not connect other appliances to the same outlet. Insufficient electrical capacity or defects in electrical work can cause electrical shock or fire.
7. For all electrical work, use the specified cables. Connect cables tightly, and clamp them securely to prevent external forces from damaging the terminal. Improper electrical connections can overheat and cause fire, and may also cause shock.
8.9. All wiring must be properly arranged to ensure that the control board cover can close properly. If the control board cover is not closed properly, it can lead to corrosion and cause the connection points on the terminal to heat up, catch fire or cause electrical shock.
In certain functional environments, such as kitchens, server rooms, etc., the use of specially designed air-conditioning units is highly recommended.
CAUTION
For units that have an auxiliary electric heater, do not install the unit within 3 feet (1 meter) of any
combustible materials.
Do not install the unit in a location that may be exposed to combustible gas leaks. If combustible gas
gas accumulates around the unit, it may cause fire.
Do not operate your air conditioner in a wet room such as a bathroom or laundry room. Too much
exposure to water can cause electrical components to short circuit.
1. The product must be properly grounded at the time of installation or electrical shock may occur.
2. Install drainage piping according to the instructions in this manual. Improper drainage may cause water damage to your home and property.
Note about Fluorinated Gasses
1. This air conditioning unit contains fluorinated gasses. For specific information on the type of gas an
the amount, please refer to the relevant label on the unit itself.
2.
Installation, service, maintenance and repair of this unit must be performed by a certified HVAC technician.
3. Product uninstallation and recycling must be performed by a certified HVAC technician.
4.
If the system has a leak-detection system installed, it must be checked for leaks at least every 12 months.
5. When the unit is checked for leaks, proper record-keeping of all checks is strongly recommended.
Page 2
1
1
1
1
(for cooling & heating
models only)
Clip anchor
Mounting plate fixing
screw ST3.9 X 25
Remote control
Fixing screw for remote control holder ST2.9 x 10
Remote control holder
Dry battery AAA.LR03
Air freshening filter
Seal
Drain joint
Mounting plate
1
Accessories
The air conditioning system comes with the following accessories. Use all of the installation parts
electrical shock and fire, or cause the equipment to fail.
5
5
2
1
Optional Parts
2
Page 3
and accessories to install the air conditioner. Improper installation may result in water leakage,
NAME
ILLUSTRATION QUANTITY
.
Page 4
Installation manual
Remote control user manual
Connecting pipe assembly
Liquid Side
Φ6.35 (1/4 in.)
Φ9.52 (3/8 in.)
Φ9.52 (3/8 in.)
Φ12.7 (1/2 in.)
Φ16 (5/8 in.)
Gas Side
User manual
1
1
1
NAME
ILLUSTRATION QUANTITY
These parts must be purchased separately. Consult the dealer about the pipe size.
----------
----------
----------
Select Installation Location
(Page 8)
Attach Mounting Plate
(Page 9)
Drill Wall Hole
(Page 9)
Installation
Overview
Determine Wall Hole Position
(Page 8)
1 2
3 4
4.75 in. (12 cm)
90.55 in. (2.3 m)
4.75 in.
(12 cm)
5.9 in. (15 cm)
Page 5
2
Installation Summary - Indoor Unit
Mount Indoor Unit
(Page 15)
STEP
8
Wrap Piping and Cable
(Page 15)
LNS
Connect Piping
(Page 22)
Connect Wiring
(Page 14)
Prepare Drain Hose
(Page 11)
5 6 7
8
9
Page 6
Installation
Overview
Fig. 2.1
NOTE ON ILLUSTRATIONS
All the illustrations in this manual are for explanation purposes only. Unit purchased may be slightly different.
Wall Mounting Plate
Power Cable (Some Units)
Refrigerant Piping
Signal Cable
Remote Control (Some Units)
Drainage Pipe
Louver
Remote Holder
Functional Filter
(On Front of Main Filter - Some Units)
Front Panel
Outdoor Unit Power Cable (Some Units)
Page 7
Unit Parts
3
Unit Parts
Installation Instructions – Indoor Unit
PRIOR TO INSTALLATION
Before installing the indoor unit, refer to the label on the product box to make sure that the model number of the indoor unit matches the model number of the outdoor unit.
Step 1: Select installation location
Before installing the indoor unit, you must choose an appropriate location. The following standards will help you choose an appropriate location for the unit.
Proper installation locations meet the following standards:
Good air circulation
Convenient drainage
Noise from the unit will not disturb
other people
Firm and solid—the location will not vibrate
Strong enough to support the weight of
A location at least 40 in. (one meter) away
from all other electrical devices (e.g., TV, radio, computer)
DO NOT install unit in the following
locations:
Near any source of heat, steam, or
combustible gas
Near flammable items such as curtains
or clothing
Near any obstacle that might block air
circulation
Near the doorway
In a location subject to direct sunlight
NOTE ABOUT WALL HOLE:
If there is no fixed refrigerant piping:
While choosing a location, be aware that you should leave ample room for a wall hole (see “Drill Wall Hole for Connective Piping” step) for the signal cable and refrigerant piping that connect the indoor and outdoor units. The default position for all piping is the right side of the indoor unit (while facing the unit). However the unit can accommodate piping to both the left and right.
Page 8
4
Indoor Unit Installation
Indoor Unit
Installation
the unit