Pepperl+Fuchs VBG-PN-K30-DMD-S16-EV, VBG-PN-K30-DMD-S16, VBG-PN-K30-D-S16, VBG-PNS-K30-DMD User Manual

Page 1
MANUAL
AS-I 3.0 PROFINET
ATEWAY WITH INTEGR.
G
AFETY MONITOR
S
FACTORY AUTOMATION
Page 2
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
With regard to the supply of products, the current issue of the following document is applicable: The
Central Association of the Electrical Industry (Zentralverband Elektrotechnik und Elektroindustrie
(ZVEI) e.V.) in its most recent version as well as the supplementary clause: "Expanded reservation
of proprietorship"
Page 3
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Table of contents
Table of contents
1 Introduction...........................................................................................8
2 Declaration of conformity ....................................................................9
2.1 Declaration of conformity................................................................................ 9
3 Safety...................................................................................................10
3.1 Symbols relevant to safety............................................................................ 10
3.2 General notes on safety ................................................................................10
3.3 Disposal .......................................................................................................... 10
4 General ................................................................................................11
4.1 Product information....................................................................................... 11
4.1.1 AS-i 3.0 PROFINET Gateway with integr. Safety Monitor ..........................................11
4.1.2 AS-i 3.0 Gateway PROFINET via PROFIsafe ............................................................... 12
4.2 New Generation of AS-i Gateways with ethernet diagnostics interface ... 13
4.3 Brief description............................................................................................. 14
5 Specifications - AS-i/PROFINET Gateways......................................16
5.1 Technical data ................................................................................................ 16
5.2 Safety-relevant characteristic data............................................................... 17
5.2.1 Overview of parameter for determining the failure rates ........................................... 18
5.3 Reaction times................................................................................................ 19
5.3.1 Sensor -> local relay output..........................................................................................19
5.3.2 Sensor -> local electronic output ................................................................................. 19
5.3.3 Sensor -> AS-i relay output........................................................................................... 20
5.3.4 Sensor -> AS-i electronic output .................................................................................. 20
5.3.5 System reaction times – example calculations ..........................................................21
5.4 Scope of delivery ........................................................................................... 24
6 Specifications - AS-i/PROFIsafe Gateway........................................25
6.1 Technical data ................................................................................................ 25
6.2 Safety-relevant characteristic data............................................................... 26
6.3 Reaction times................................................................................................ 27
6.3.1 Ethernet (PROFIsafe) -> local relay output.................................................................. 27
6.3.2 Ethernet (PROFIsafe) -> local electronic output ......................................................... 27
6.3.3 Ethernet (PROFIsafe) -> AS-i relay output................................................................... 28
6.3.4 Ethernet (PROFIsafe) -> AS-i electronic output ..........................................................28
27.9.2013
3
Page 4
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Table of contents
7 Installation...........................................................................................29
7.1 Dimensions .................................................................................................... 29
7.2 Connections................................................................................................... 29
7.3 Installing in the control cabinet.................................................................... 30
7.4 Removing ....................................................................................................... 30
7.5 Commissioning.............................................................................................. 31
7.5.1 Switching to advanced display mode .......................................................................... 31
7.5.2 Setting the PROFINET properties ................................................................................31
7.5.3 Setting the PROFIsafe address .................................................................................... 32
7.5.4 Connecting AS-i Slaves ................................................................................................ 33
7.5.5 Quick setup .................................................................................................................... 34
7.5.6 Error tracing ...................................................................................................................35
7.5.6.1 Faulty slaves.................................................................................................................35
7.5.6.2 Error display (last error) ................................................................................................35
7.6 Addressing..................................................................................................... 36
7.6.1 Assigning address 15 to slave currently at address 2............................................... 36
7.7 Local parameter setting of safe AS-i Gateways and Monitors .................. 37
7.8 Replacing a defective safety-related AS-i slave ......................................... 39
7.9 Replacing the chip card ................................................................................ 40
7.10 Replacing a defective device........................................................................ 40
7.10.1 Teaching the group manager after replacing a device ..............................................43
7.11 Replacing the monitor................................................................................... 44
7.12 Safe configuration using ASIMON 3 G2 ..................................................... 47
8 Maintenance ........................................................................................49
8.1 Checking for safe turn-off............................................................................. 49
9 Electrical connection..........................................................................50
9.1 Overview of terminals, indicators and operating elements....................... 50
9.1.1 VBG-PN-K30-D-S16, VBG-PN-K30-DMD-S16, VBG-PNS-K30-DMD, VBG-PN-K30­DMD-S16-EV50
9.2 AS-i bus connection...................................................................................... 51
9.3 Information about the device types ............................................................. 51
9.4 AS-i and power supply terminal assignments ............................................ 51
9.4.1 Electrical connection VBG-PN-K30-D-S16 .................................................................52
9.4.2 Electrical connection VBG-PN-K30-DMD-S16-EV .......................................................53
9.4.3 Electrical connection VBG-PN-K30-DMD-S16, VBG-PNS-K30-DMD ........................ 54
9.5 Diagnostics interface .................................................................................... 55
9.5.1 Diagnostics port RS 232 ...............................................................................................55
9.6 PROFINET interface...................................................................................... 55
9.7 Safe coupling via Ethernet ............................ (VBG-PN-K30-DMD-S16-EV)56
9.8 Chip card ........................................................................................................ 56
4
27.9.2013
Page 5
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Table of contents
9.9 Release circuits.............................................................................................. 57
9.9.1 Wiring overview - safety unit ........................................................................................57
9.10 Indicators and operating elements............................................................... 58
9.10.1 LED indicators – master................................................................................................ 58
9.10.2 LED indicators - safety unit .......................................................................................... 59
9.10.3 Buttons ........................................................................................................................... 60
10 Function and startup of the Safety Monitor .....................................61
10.1 Powering up the device ................................................................................. 61
10.2 Configuration of the safety functions .......................................................... 61
10.2.1 Description of configuration using ASIMON 3 G2 software ...................................... 62
10.2.2 Description of configuration using chip card with master configuration ................63
10.2.3 Configuration using a chip card with complete configuration.................................. 63
10.3 Safety-relevant documentation of the application ...................................... 64
10.4 Diagnostic data .............................................................................................. 64
10.4.1 Diagnostics of release circuits 1-4 via the binary data ............................................. 65
10.5 Switch-off history........................................................................................... 65
10.5.1 Diagnostic values in the IDI ..........................................................................................66
10.6 Password protection...................................................................................... 67
10.6.1 Procedure for configuring and teaching code sequences ........................................ 68
10.6.2 Function of the ESC/Service key..................................................................................69
10.7 Safe coupling slaves on the AS-i circuits .................................................... 69
10.8 Chip card......................................................................................................... 69
10.8.1 Unsafe data ....................................................................................................................69
10.8.1.1 Card unformatted ..........................................................................................................69
10.8.1.2 Data not compatible ......................................................................................................70
10.8.1.3 Card empty ................................................................................................................... 70
10.8.1.4 Data compatible ............................................................................................................70
10.8.1.5 Data in the device and on the chip card identical .........................................................70
10.8.1.6 Data in the device and on the chip card not identical ...................................................70
10.8.2 Safe data .........................................................................................................................71
10.8.2.1 Data incompatible ......................................................................................................... 71
10.8.2.2 Data compatible ............................................................................................................71
10.8.2.3 Complete configuration.................................................................................................72
10.8.2.4 Data on the chip card and in the device are identical ...................................................72
10.8.2.5 Data not identical ..........................................................................................................72
10.8.2.6 Operating the chip card from the menu ........................................................................73
10.8.3 Working with multiple memory banks ......................................................................... 73
11 Operation in advanced display mode ...............................................75
12 Advanced Diagnostics for AS-i Masters...........................................76
12.1 List of corrupted AS-i Slaves (LCS) ............................................................. 76
12.2 Protocol analysis: Counters for corrupted data telegrams ....................... 76
12.3 Offline Phase for Configuration Errors ........................................................ 77
12.4 Functions of the AS-i Fault Detector ............................................................ 77
12.4.1 Duplicate address detection .........................................................................................77
12.4.2 Earth/Ground Fault Detector ........................................................................................ 78
27.9.2013
5
Page 6
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Table of contents
12.4.3 Noise Detector ............................................................................................................... 78
12.4.4 Over-voltage Detector ................................................................................................... 78
12.5 Functions of the new generation of AS-i Gateways ................................... 79
12.5.1 C-programmable Gateways ..........................................................................................79
12.5.2 Interchangeable memory card......................................................................................79
12.5.3 Earth fault monitor......................................................................................................... 79
12.5.4 Current can be read directly on the unit......................................................................80
12.5.5 Self-resetting fuses ....................................................................................................... 81
12.5.6 AS-i Power24V capable ................................................................................................. 81
12.5.7 Ethernet diagnostics interface with web server .........................................................82
12.5.8 Transitionless operating mode changes ..................................................................... 82
13 Configuration of AS-i/PROFINET Gateways.....................................83
13.1 Projecting PROFINET network ..................................................................... 83
13.2 Logical slots................................................................................................... 83
13.2.1 Options ........................................................................................................................... 83
13.2.2 32 bytes digital AS-i I/O data (A and B slaves) ...........................................................86
13.2.3 16 bytes digital AS-i I/O data (A slaves only)..............................................................88
13.2.4 16 bytes digital AS-i I/O data (B slaves only)..............................................................88
13.2.5 4 words analog AS-i input data .................................................................................... 89
13.2.6 4 Words analog AS-i output data .................................................................................91
13.2.7 36 bytes command interface ........................................................................................ 92
13.2.8 34 bytes command interface ........................................................................................ 93
13.2.9 12 byte command interface .......................................................................................... 94
13.3 Executing of command interface commands ............................................. 94
13.4 PROFINET diagnostics.................................................................................. 95
13.4.1 Channel error codes ...................................................................................................... 95
13.4.2 Manufacturer specific diagnostic................................................................................. 96
13.4.3 Safety Control/Status .................................................................................................... 99
13.4.3.1 Diagnostics in the cyclic channel (10 Byte SafeLink.Diag.) ........................................101
13.5 Device-specific parameters ........................................................................ 102
13.6 Media Redundancy Protocol MRP ............................................................. 103
14 System startup using AS-i Control Tools.......................................104
15 Configuration with Windows Software ASIMON 3 G2 ...................107
16 Status indication, faults and fault elimination ...............................108
16.1 Spontaneous display of faults from the safety unit ................................. 108
16.2 Replacing a defective safety-configured AS-i slave................................. 109
16.3 Replacing a defective AS-i Safety Monitor ................................................ 110
16.4 Forget the password? What do I do now? ................................................ 110
17 Safe Link............................................................................................112
17.1 General introduction .................................................................................. 112
17.2 Configuration ............................................................................................... 113
17.2.1 Configuration using ASIMON ..................................................................................... 114
6
27.9.2013
Page 7
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Table of contents
17.3 Diagnostics .................................................................................................. 115
18 Glossary ............................................................................................117
19 Appendix, Examples.........................................................................120
19.1 Startup on a Siemens NC control ............................................................... 120
19.1.1 Setting in the S7 configuration...................................................................................120
19.1.2 Setting in the NC control .............................................................................................121
19.1.3 Setting “PROFISAFE_IN_ADDRESS“ ........................................................................121
19.1.4 Setting “PROFISAFE_OUT_ADDRESS“ ....................................................................121
19.1.5 Setting “PROFISAFE_IN_ASSIGN“ ............................................................................121
19.1.6 Setting “PROFISAFE_OUT_ASSIGN" ........................................................................ 122
19.1.7 Setting “PROFISAFE_IN_FILTER" .............................................................................122
19.1.8 Setting “PROFISAFE_OUT_FILTER" .........................................................................122
19.2 Safety diagnostics in the input data image (IDI) ....................................... 123
19.2.1 Representation of the diagnostic information ..........................................................123
19.2.2 Other representation variants .................................................................................... 124
19.2.3 Changing the default setting ......................................................................................124
20 Reference List...................................................................................127
20.1 Manual: “ASIMON 3 G2 Configuration Software“ .....................................127
20.2 Sources ......................................................................................................... 127
21 Codes indicated by the display.......................................................128
27.9.2013
7
Page 8
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Introduction

1. Introduction

Congratulations
You have chosen a device manufactured by Pepperl+Fuchs. Pepperl+Fuchs de­velops, produces and distributes electronic sensors and interface modules for the market of automation technology on a worldwide scale.
Before installing this equipment and put into operation, read this manual carefully. This manual containes instructions and notes to help you through the installation and commissioning step by step. This makes sure bring such a trouble-free use of this product. This is for your benefit, since this:
ensures the safe operation of the device
helps you to exploit the full functionality of the device
avoids errors and related malfunctions
avoids costs by disruptions and any repairs
increases the effectiveness and efficiency of your plant Keep this manual at hand for subsequent operations on the device. After opening the packaging please check the integrity of the device and the
number of pieces of supplied.
Symbols used
The following symbols are used in this manual:
Information!
This symbol indicates important information.
Attention!
This symbol warns of a potential failure. Non-compliance may lead to interruptions of the device, the connected peripheral systems, or plant, potentially leading to total mal­functioning.
Warning!
This symbol warns of an imminent danger. Non-compliance may lead to personal inju­ries that could be fatal or result in material damages and destruction.
Contact
If you have any questions about the device, its functions, or accessories, please contact us at:
Pepperl+Fuchs GmbH Lilienthalstraße 200 68307 Mannheim Telephone: +49 621 776-4411 Fax: +49 621 776-274411 E-Mail: fa-info@pepperl-fuchs.com
27.9.2013
8
Page 9
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Declaration of conformity

2. Declaration of conformity

2.1 Declaration of conformity

This product was developed and manufactured under observance of the applica­ble European standards and guidelines.
Information!
A Declaration of Conformity can be requested from the manufacturer.
The product manufacturer, Pepperl+Fuchs GmbH, D-68307 Mannheim, has a certified quality assurance system that conforms to ISO 9001.
27.9.2013
9
Page 10
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Safety

3. Safety

3.1 Symbols relevant to safety

Information!
This symbol indicates important information.
Attention!
This symbol warns of a potential failure. Non-compliance may lead to interruptions of the device, the connected peripheral systems, or plant, potentially leading to total mal­functioning.
Warning!
This symbol warns of an imminent danger. Non-compliance may lead to personal inju­ries that could be fatal or result in material damages and destruction.

3.2 General notes on safety

Only instructed specialist staff may operate the device in accordance with the op­erating manual.
User modification and or repair are dangerous and will void the warranty and ex­clude the manufacturer from any liability. If serious faults occur, stop using the de­vice. Secure the device against inadvertent operation. In the event of repairs, re­turn the device to your local Pepperl+Fuchs representative or sales office.
The connection of the device and maintenance work when live may only be car­ried out by a qualified electrical specialist.
The operating company bears responsibility for observing locally applicable safe­ty regulations.
Store the not used device in the original packaging. This offers the device optimal protection against impact and moisture.
Ensure that the ambient conditions comply with regulations.

3.3 Disposal

Information!
Electronic waste is hazardous waste. Please comply with all local ordinances when disposing this product!
The device does not contain batteries that need to be removed before disposing it.
10
27.9.2013
Page 11
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
General

4. General

4.1 Product information

This system manual applies to the following Pepperl+Fuchs equipment:

4.1.1 AS-i 3.0 PROFINET Gateway with integr. Safety Monitor

Article No.
VBG-PN-K30-DMD-S16
VBG-PN-K30-D-S16
VBG-PN-K30-DMD-S16­EV
1. power supply, 1 gateway for 2 AS-i networks, inexpensive power supplies:
- "yes, max. 4A/AS-i network": Cost-effective power for 2 AS-i networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply).
- "no, max. 8A/AS-i network, redundant supply": 1 power supply per AS-i network. Gateway is powered in normal operation from one of the two AS-i power supplies. Should one AS-i power supply fail, switching to the other AS-i power supply allows all the diagnostics functions to be maintained and the unaffected AS-i network continues to operate. "no, max. 8A/AS-i network": 1 power supply per AS-i network
2. Ethernet fieldbus + RS 232: Access to AS-i master and safety monitor via Pepperl+Fuchs proprietary software over Ethernet fieldbus interface or RS 232 interface and adapter cable.
3. AS-i Power24V capable:
- VBG-PN-K30-DMD-S16-EV device can be operated directly on a 24V (PELV) power supply
- with integrated data coupling coils and adjustable self-resetting fuses for safe use also of powerful 24V power sup­plies.
27.09.2013
Type
Safety,
PROFI­NET
Safety,
PROFI­NET
Safety,
PROFI­NET
Inputs safety, expandable to
max. 62 x 2 chan­nels
max. 62 x 2 chan­nels
max. 62 x 2 chan­nels, max. 1922 in max. configu­ration
Outputs Safety, SIL 3, cat. 4
Safety outputs,
independent according to SIL 3,
Safety communication
Number of AS-i networks,
number of AS-i Master
1 power supply,
4 release circuits; 2 x relay, 2 x fast electronic safe outputs 4 release circuits; 2 x relay, 2 x fast electronic safe outputs
4 release circuits; 2 x relay, 2 x fast electronic safe outputs
Tab. 4-1. Funcion range "AS-i 3.0 PROFINE T Gateway with integr. Safety Monitor"
max. 16
max. 16
max. 32, max. 992 in max.
confi­gura­tion
-
-
Safe Link
2 AS-i net­works, 2 AS-i Masters
2 AS-i net­works, 1 AS-i Master
2 AS-i net­works, 2 AS-i Masters
1 gateway for 2 AS-i networks1Diagnostic and
no, max. 8A/AS-i network, redundant supply
no, max. 8A/AS-i network, redundant supply
no, max. 4A/AS-i Kreis
Power24V
Ethernet fieldbus + RS 232
Ethernet fieldbus + RS 232
Ethernet fieldbus + RS 232
3
configuration interface2Programming in C
no
no
optio­nal
11
Page 12
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
General
The AS-i 3.0 PROFINET Gateway with integr. Safety Monitor combines two de­vices in one housing: an AS-i/PROFINET Gateway and a Safety Monitor for 2 AS­i circuits.
The safety unit provides 4 inputs which can be defined as either EDM or as START inputs.
AS-i/PROFINET-Gateways serve to connect AS-i systems to the superordinate PROFINET controller. It acts as a master for AS-i and as a slave on field bus lev­el.
Commissioning, debugging and setting up of the AS-i parameters can be accom­plished with the use of the display, but it can also be handled via the diagnostic in­terface and the field bus.

4.1.2 AS-i 3.0 Gateway PROFINET via PROFIsafe

VBG-PNS-K30-DMD
12
Article No.
PROFI­safe, PROFI­NET
Type
max. 62 x 2 channels
Inputs safety, expandable to
Outputs Safety, SIL 3, cat. 4
Safety outputs,
independent according to SIL 3,
Safety communication
Number of AS-i networks,
number of AS-i Master
1 power supply,
4 release circuits; 2 x relay, 2 x fast electronic safe out­puts
max. 16
Tab. 4-2. Funcion range "AS-i 3.0 Gateway PROF INET via PROFIsafe"
PROFI safe (F-CPU)
2 AS-i net­works, 2AS-i Masters
1 gateway for 2 AS-i networks
no, max. 8A/AS-i network, redun­dant sup­ply
Diagnostic and
configuration interface
RS 232 + Ethernet
no
The AS-i 3.0 Gateway PROFINET via PROFIsafe is a combination of an AS-i/ PROFINET Gateway with a PROFIsafe F-device. It is used for transmitting of safety related data to/from SaW slaves via the standard field bus PROFINET.
The gateway supports 64 release circuits. The integrated safety unit provides 4 non-safety inputs. PROFIsafe transfers input status data to F-Host.
Information!
PROFIsafe is a certified acc. to IEC 61508 profile for PROFIBUS and PROFINET. With SIL 3 (Safety Integrity Level) or category 4 acc. to EN 954-1 fulfills PROFIsafe the highest safety requirements for the process- and manufacturing industry. Both safety related and standard communication are possible via one and the same cable.
AS-i/PROFINET-Gateways serve to connect AS-i systems to the superordinate PROFINET controller. It acts as a master for AS-i and as a slave on field bus lev­el.
Programming in C
27.09.2013
Page 13
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
General
Commissioning, debugging and setting up of the AS-i parameters can be accom­plished with the use of the display, but it can also be handled via the diagnostic in­terface and the field bus.

4.2 New Generation of AS-i Gateways with ethernet diagnostics interface

The plus points of the new Gateway generation at a glance:
Gateways now programmable in C
Ethernet diagnostics interface for remote diagnostics
Integrated web server: diagnostics for the Gateways and the AS-i circuits over Ethernet possible with no additional software
GSD configuration files already stored in the web server
Earth fault monitor distinguishes between AS-i cable and sensor cable
Current from both AS-i circuits in the "1 Gateway, 1 power supply for 2 AS-i circuits" version can now be read directly on the unit
Self-resetting fuses in the "1 Gateway, 1 power supply for 2 AS-i circuits" ver­sion
Device temperature display
AS-i Power24V capable
Interfaces for virtually every bus system and Ethernet solution
Information!
See also section <Functions of the new generation of AS-i Gateways> for further infor­mation.
27.09.2013
13
Page 14
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
General

4.3 Brief description

The actuator-sensor interface (AS-i) has established itself as a system for net­working primarily binary sensors and actuators at the lowest level of the automa­tion hierarchy. The high number of installed systems, the ease of use and the reli­able operating behaviour also make the AS-i interesting in the area of machine safety.
The safety AS-i system is intended for safety applications up to Category 4/SIL 3. Mixed operation of standard components and safe components is possible.
AS-i 3.0 Gateway PROFINET via PROFIsafe
The safety unit monitors within an AS-i system the safe slaves which have been assigned according to the configuration specified by the user with the configura­tion software. This safety information is transmitted to PROFIsafe.
SPS
1.13
2.13+24 V
0 V +
2.Y2
2.Y1
Aux
AS-i Safety
Integrated
1.Y1
1.Y2
2.Y1
2.Y2
K1
K2
K3
K4
1.Y2
1.Y1 +
Mode
2.14
3.14
4.14+1.14
ESC
OK
Service
Set
ASI +PWR+ASI
+ASI 1
1
2
+ASI
Safety In
Adr. 1
Analog In
Adr. 3
Analog In
Adr. 10
OEM 3O Adr. 22A
OEM 4I/4O
Adr. 26
Abb. 4-1. Safe and standard components in an AS-i network
Analog In Adr. 4
Analog In Adr. 11
OEM Safety Adr. 21
OEM 3O Adr. 23A
OEM Safety Adr. 24
OEM 2I/2O Adr. 27
Safety In
Adr. 6
Safety In
Adr. 12
Safety Out
Adr. 4/7B
2.13+24 V
0 V+1.13
2.Y2
2.Y1
Aux
AS-i Safety
Integrated
1.Y1
1.Y2
2.Y1
2.Y2
K1
K2
K3
K4
1.Y2
1.Y1
Mode
2.14+4.14+1.14
3.14
ESC
OK
Service
Set
ASI +PWR+ASI
+ASI 1
1
2
+ASI
Safety In Adr. 13
Safety Out Adr. 2/7A
14
27.09.2013
Page 15
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
General
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
The AS-i/PROFINET Gateway monitors within an AS-i system the safe slaves which have been assigned according to the configuration specified by the user with the configuration software. In the event of a stop request or a defect, the AS­i/PROFINET Gateway switches off the system in protective operation mode with a maximum reaction time of 40 ms.
AS-i coupling circuit
Analog In
Adr. 10
OEM 3O Adr. 22A
OEM 4I/4O
Adr. 26
Safety In
Adr. 1
Analog In
Adr. 3
coupling slave Adr. 1
Analog In Adr. 11
OEM Safety Adr. 21
OEM 3O Adr. 23A
OEM Safety Adr. 24
OEM 2I/2O Adr. 27
lightgrids 1
coupling slave Adr. 2 emergency-stop circuit 1
Safety In
Adr. 6
Safety In
Adr. 12
Safety Out
Adr. 4/7B
1.13
2.13+24 V
0 V +
2.Y2
2.Y1
Aux
AS-i Safety
Integrated
1.Y1
1.Y2
2.Y1
2.Y2
K1
K2
K3
K4
1.Y2
1.Y1 +
Mode
2.14
3.14
4.14+1.14
ESC
OK
Service
Set
Safety In Adr. 13
Safety Out Adr. 2/7A
1.13
2.13+24 V
0 V +
2.Y2
2.Y1
Aux
AS-i Safety
Integrated
1.Y1
1.Y2
2.Y1
2.Y2
K1
K2
K3
K4
1.Y2
1.Y1 +
Mode
2.14
3.14
4.14+1.14
ESC
OK
Service
Set
Analog In Adr. 4
coupling slave Adr. 6 silent running
coupling slave Adr. 7 emergency-stop circuit 2
Abb. 4-2. Safe and standard components in an AS-i network
Multiple AS-i Safety Monitors can be used within an AS-i system. In this way, a safe slave can be monitored by multiple AS-i Safety Monitors.
27.09.2013
15
Page 16
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Specifications - AS-i/PROFINET Gateways

5. Specifications - AS-i/PROFINET Gateways

5.1 Technical data

The technical data are placed in the data sheet. Please view the current version on the web page: http://www.pepperl-fuchs.com.
Attention!
The AS-I power supply for the AS-I components must have isolation per IEC 60 742 and be able to handle momentary power interruptions of up to 20 ms. The power sup­ply for the 24 V supply must also have isolation per IEC 60 742 and be able to handle momentary power interruptions of up to 20 ms. The maximum output voltage of the power supply must also be less than 42 V in case of a fault.
16
27.9.2013
Page 17
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Specifications - AS-i/PROFINET Gateways

5.2 Safety-relevant characteristic data

Characteristic data Value Standard
Safety category 4 EN 954-1
Safety category 4 EN ISO 13849-1: 2008
Performance Level (PL) e
Safety Integrity Level (SIL) 3 EN 61508: 2001
Lifespan (TM) in years 20 EN ISO 13849-1: 2008
Maximum switch-on time in months 12 EN 61508: 2001
Max. system reaction time in milliseconds
Attention!
In addition to the system reaction time of max. 40 ms, the reaction times of the safe AS­interface sensor slave, of the sensor being used for monitoring, of the safe AS-interface actuator slave and of the actuator used for this purpose must still be added. Please note that additional reaction times may likewise arise through the configuration of the safety monitor.
Notice!
Refer to the technical data for the slaves as well as to that for the sensors and actuators for the reaction times to be added.
40 EN 61508: 2001
Tab. 5-3.
Attention!
The system reaction times of the daisy-chained AS-interface components are added up.
27.9.2013
17
Page 18
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Specifications - AS-i/PROFINET Gateways

5.2.1 Overview of parameter for determining the failure rates

nop/y switching intervals
t
[s]
cycle
B10d value
electromechanics Standard
MTTFd [years] PFH [1/h]
105.120 300 2.500.000 237,82
52.560 600 475,65
8.760 3600 2853,88
nop/y switching
intervals t
cycle
105.120 300 2.500.000
B10d value
electronics PFH
-09
4,76 E
electromechanics PFH
MTTFdPFH
237,82
52.560 600 475,65
8.760 3600 2853,88
-9
9,908 x 10
-9
4,853 x 10
-10
9,054 x 10
total
1,12 x 10-81,6 x 10
5,09 x 10-99,85 x 10
-10
7,82 x 10
5,54 x 10
-8
-9
-9
EN ISO 13849-1
Tab. 5-4.
Standard
EN 62061 EN 61508
Tab. 5-5.
18
27.9.2013
Page 19
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Specifications - AS-i/PROFINET Gateways

5.3 Reaction times

5.3.1 Sensor -> local relay output

Sensor
t
t
s
ts = maximal reaction time of the sensor (see data sheet) t
= maximal system reaction time
react
react
= 40ms
1.13
2.13
1.14
2.14

5.3.2 Sensor -> local electronic output

Sensor
t
s
ts = maximal reaction time of the sensor (see data sheet) t
= maximal system reaction time
react
27.9.2013
t
react
24V
3.14
4.14
= 30ms
19
Page 20
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Specifications - AS-i/PROFINET Gateways

5.3.3 Sensor -> AS-i relay output

1.13
1.14
1.23
1.24
Sensor
t
s
ts = maximal reaction time of the sensor (see data sheet) t
= maximal system reaction time
react

5.3.4 Sensor -> AS-i electronic output

Sensor
t
s
ts = maximal reaction time of the sensor (see data sheet) t
= maximal system reaction time
react
t
react
t
react
Relay output
= 85ms
24V
1.14
2.14
Electronic output
= 85ms
20
27.9.2013
Page 21
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Specifications - AS-i/PROFINET Gateways
5.3.5 System reaction times – example calculations
System components:
AS-i network 1
ASI1
AS-i network 2
ASI2
Safe sensor slave (EMERGENCY-OFF switch: t
S1-1
Safe sensor slave (safety light barrier: t
S1-2
Safe sensor slave (EMERGENCY-OFF switch: t
S2-1
Safe actuator slave (motor starter: t
A2-1
SM1-1 Safety monitor with 16 relais circuits and one safe AS-i output in AS-i
network 1
SM1-2 Safety monitor with 2 relais circuits and one safe AS-i output in AS-i
network 1
SM2-1
Safety monitor with 16 relais circuits and one safe AS-i output in AS-i
network 2
System configuration - example 1: Calculation of the system reaction time
RA2-1
= 18 ms)
RS1-2
= 50ms)
RS1-1
RS2-1
= 100 ms)
= 100ms)
Tab. 5-6.
27.9.2013
21
Page 22
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Specifications - AS-i/PROFINET Gateways
System configuration - example 1: Calculation of the system reaction time
SM1-1
AS-i Safety Monitor
M
S1-1
SM1-2
AS-i Safety Monitor
M
S1-2
AS-i 1
SM2-1
M
AS-i Safety Monitor
S2-1
M
AS-i 2
Upon activation of safety light barrier S1-2, the relay safety output of safety moni­tor SM1-2 is controlled.
Calculation of the AS-i relevant system reaction time:
t
System total a)
= t
R S1-2
+ t
= 18ms + 40ms = 58ms
R System
System configuration - example 2: Calculation of the system reaction time
I–
I+
I1
I2
Run
1 I
Pwr
Prg
1.13
1.14
ASI+
ASI–
I+
I+
1.Y1
1.Y2
Prg
I2
1.Y2
1.Y1
Alarm
Fault
Out
1.23
1.24
nc
nc
A2-1
22
27.9.2013
Page 23
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Specifications - AS-i/PROFINET Gateways
System configuration - example 2: Calculation of the system reaction time
SM1-1
AS-i Safety Monitor
M
S1-1
SM1-2
AS-i Safety Monitor
M
S1-2
AS-i 1
SM2-1
M
AS-i Safety Monitor
S2-1
M
AS-i 2
Upon locking of the EMERGENCY-OFF switch S2-1, the motor starter is control­led via the safe AS-interface output of safety monitor SM2-1.
Calculation of the AS-interface-relevant system reaction time:
t
System total b)
= t
R S2-1
+ t
R System
+ t
= 100ms + 40ms + 50ms = 190ms
R A2-1
System configuration - example 3: Calculation of the system reaction time
I– I1
Run
Prg
1.13 ASI+
I+
I+
I+
I2
1.Y1
1.Y2
Prg
1 I
I2
1.Y2
1.Y1
Alarm
Pwr
Fault Out
1.14
1.23
1.24
ASI–
nc
nc
A2-1
27.9.2013
23
Page 24
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Specifications - AS-i/PROFINET Gateways
System configuration - example 3: Calculation of the system reaction time
SM1-1
AS-i Safety Monitor
M
S1-1
SM1-2
AS-i Safety Monitor
M
S1-2
AS-i 1
SM2-1
M
AS-i Safety Monitor
S2-1
M
AS-i 2
Upon locking of the EMERGENCY-OFF switch S1-1, the relay output of safety monitor SM2-1 is controlled via the coupling of the safe AS-interface output of safety monitor SM1-1.
Calculation of the AS-i relevant system reaction time:
t
System total c)
= t
R S1-1
+ t
R System ASI1
+ t
R System ASI2
40ms = 180ms
I+
I+
I+
I–
1.Y2
1.Y1
I2
I1
A2-1
Run
Prg
1 I
I2
1.Y2
1.Y1
Alarm
Pwr
Fault
Out
Prg
1.24
1.23
1.14
1.13 nc
nc
ASI–
ASI+
= 100ms + 40ms +

5.4 Scope of delivery

The basic unit consists of: AS-i 3.0 PROFINET Gateway with integr. Safety Monitor. The following accessories are available: Software CD with
ASIMON 3 G2 communication software for Microsoft Windows 7/Windows 8
System manual in PDF format (Adobe® Reader® Version 7.x or newer is required for viewing the files)
24
®
Windows XP/Vista/
®
27.9.2013
Page 25
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Specifications - AS-i/PROFIsafe Gateway

6. Specifications - AS-i/PROFIsafe Gateway

6.1 Technical data

The technical data are placed in the data sheet. Please view the current version on the web page: http://www.pepperl-fuchs.com.
Attention!
The AS-I power supply for the AS-I components must have isolation per IEC 60 742 and be able to handle momentary power interruptions of up to 20 ms. The power sup­ply for the 24 V supply must also have isolation per IEC 60 742 and be able to handle momentary power interruptions of up to 20 ms. The maximum output voltage of the power supply must also be less than 42 V in case of a fault.
27.9.2013
25
Page 26
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Specifications - AS-i/PROFIsafe Gateway

6.2 Safety-relevant characteristic data

Characteristic data Value Standard
Safety category 4 EN 954-1
EN ISO 13849-1: 2008
Performance Level (PL) e EN ISO 13849-1: 2008
Safety Integrity Level (SIL) 3 IEC 61508: 2001
Lifespan (TM) in years 20 EN ISO 13849-1: 2008
Maximum switch-on time in months 12 IEC 61508: 2001
PFD
PFH
D
(probability of a dangerous failure per hour)
Max. system reaction time in milliseconds
PROFIsafe local relay output 15
PROFIsafe local electronic output 5
PROFIsafe AS-i relay output 60
PROFIsafe AS-i electronic output 50
AS-i PROFIsafe 30
PROFINET local output 40
PROFINET AS-i
AS-i local output
AS-i AS-i
AS-i PROFINET 50
Attention!
In addition to the system reaction time in the gateway, eventually reaction times of other daisy-chained safe AS-i and PROFIsafe componentshave to be added too. Please note that additional reaction times may likewise arise through the configuration of the safety unit.
< 9,25 x 10
< 5,36 x 10
-6
IEC 61508: 2001, EN 62061: 2005
-9
IEC 61508: 2001, EN 62061: 2005
IEC 61508: 2001
Tab. 6-7.
26
27.9.2013
Page 27
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Specifications - AS-i/PROFIsafe Gateway

6.3 Reaction times

6.3.1 Ethernet (PROFIsafe) -> local relay output

1.13
2.13
1.14
2.14
t
ethernet
t
= reaction time PROFIsafe type 150ms
ethernet
t
= maximal system reaction time
react

6.3.2 Ethernet (PROFIsafe) -> local electronic output

t
ethernet
t
= reaction time PROFIsafe type 150ms
ethernet
t
= maximal system reaction time
27.9.2013
react
t
= 15ms
react
24V
1.14
2.14
t
= 5ms
react
27
Page 28
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Specifications - AS-i/PROFIsafe Gateway

6.3.3 Ethernet (PROFIsafe) -> AS-i relay output

1.13
1.14
1.23
1.24
Relay output
t
ethernet
t
= reaction time PROFIsafe type 150ms
ethernet
t
= maximal system reaction time
react

6.3.4 Ethernet (PROFIsafe) -> AS-i electronic output

t
react
t
ethernet
t
= reaction time PROFIsafe type 150ms
ethernet
t
= maximal system reaction time
react
t
react
= 60ms
24V
1.14
2.14
Electronic output
= 50ms
27.9.2013
28
Page 29
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Installation

7. Installation

7.1 Dimensions

80
96
Warning!
Cover the top of the gateway when doing any drilling work above the unit. No particles, especially metal chips, should be allowed to enter the housing, since this could cause a short circuit.
Information!
Please refer to installation instruction for this device for detailed mounting information.

7.2 Connections

10
10
AWG 24 ... 12
Attention!
The power supply for the AS-I components must have isolation per IEC 60 742 and be able to handle momentary power interruptions of up to 20 ms. The power supply for the 24 V supply must also have isolation per IEC 60 742 and be able to handle momentary power interruptions of up to 20 ms. The maximum output voltage of the power supply must also be less than 42 V in case of a fault.
110
0,2 ... 2,5 mm
0,2 ... 2,5 mm
120
2
2
27.9.2013
29
Page 30
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Installation

7.3 Installing in the control cabinet

The AS-I/Gateway is installed in the control cabinet on 35mm DIN rails per DIN EN 50 022.
Information!
The enclosure of the AS-I/Gateway is made of stainless steel. The unit is also sui­table for exposed wall mounting.
To install, place the unit on the upper edge of the DIN rail and then snap in the lower edge.
[1]
-
-
+-+
+
[2]

7.4 Removing

To remove, press the holding clamps [2] down using a screwdriver [1], press the unit firmly against the upper rail guide and lift out.
30
-
-
+-+
+
3
1
2
27.9.2013
Page 31
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Installation

7.5 Commissioning

7.5.1
classical display

Switching to advanced display mode

advanced display mode
OK
LCD
1.12A
UNKNOWN SLAVE
ESC/Service

7.5.2 Setting the PROFINET properties

PROFINET QUICK SETUP AS-I SAFETY DIAGNOSIS
LCD
(OK
(OK oder/or/ou/o/o
PROFINET TCP/IP ETHERNET
TCP/IP ACTUAL VALUES CONFIGURATION
Restart the Gateway for changes to become effective
LCD
menu structure see additional page
CONFIGURATION STATIC
IP ADDRESS
192.168.42.53 NETMASK
255.255.255.0 GATEWAY
192.168.42.53
CONFIGURATION PROFINET ONLY
27.9.2013
31
Page 32
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Installation
(OK
(OK
(OK
PROFINET TCP/IP ETHERNET
ETHERNET: PORT 1 MODE: 100BASE-TX FDX PORT 2 MODE: NO CONNECTION MAC ID DEVICE: 00-16-77-10­ AF-8C MAC ID PORT 1: 00-16-77-10­ AF-8D MAC ID PORT 2: 00-16-77-10­ AF-8E
PROFINET TCP/IP ETHERNET
PROFINET QUICK SETUP
DIAGNOSIS
SLAVE ADDR TOOL
oder/or/ou/o/o
OK
ESC
100BASE-TX FDX
100BASE-TX HDX
10BASE-T FDX
10BASE-T HDX
NO CONNECTION
TCP/IP ACTUAL VALUES CONFIGURATION
ACTUAL VALUES: IP ADDRESS
192.168.42.53 NETMASK
255.255.255.0 GATEWAY
192.168.42.53 SOURCE STATIC CONFIG

7.5.3 Setting the PROFIsafe address

Information!
Available only with AS-i PROFIsafe Gateways.
32
27.9.2013
Page 33
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Installation
PROFINET QUICK SETUP SAFETY ...
PROFINET QUICK SETUP SAFETY ...
OK
ASI SAFETY SAFE OUTPUT CH PROFISAFE START/STOP ...

7.5.4 Connecting AS-i Slaves

AS-i
Power
PROFINET
Config error
U AS-i
AS-i active
prg enable
prj mode
AS-i Master
AS-i
Power
PROFINET
Config error
U AS-i
AS-i active
prg enable
prj mode
PROFISAFE ADDR. Status
OK
PROFISAFE ADDR. 06
OK
PROFISAFE ADDR. 17
LCD
1. 1
AS-i Master
0.5s
AS-i
AS-i Slave 1
AS-i Slave 5
27.9.2013
1. 41
SEARCHING SLAVES
LCD
Slave 1
AS-i Slave 5
1. 5
0.5s
33
Page 34
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Installation

7.5.5 Quick setup

config error
OK
1. 5
1xOK
PROFINET QUICK SETUP ASI SAFETY DIAGNOSIS
OK
WARNING: OUTPUTS MAY BE RESET
OK
LCD
STORE AS-I CONFIGURATION OK STORE +PRJ MODE
config error
LCD
CONFIGURATION OK
10s
Host error
no connection
1: ON 2: OFF
LCD
LCD
LCD
LCD
STORE AS-I CONFIGURATION STORE +RUN STORE +PRJ MODE
34
LCD
27.9.2013
Page 35
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Installation

7.5.6 Error tracing

7.5.6.1 Faulty slaves
Power
PROFINET
Config error
U AS-i
AS-i
AS-i active
prg enable
prj mode
AS-i Master
1.1
MISSING SLAVE
LCD
AS-i Slave 1
AS-i Slave 5
AS-i Slave 24
7.5.6.2 Error display (last error)
Power
PROFINET
Config error
U AS-i
AS-i active
prg enable
prj mode
AS-i
AS-i Slave 1
AS-i Slave 5
AS-i Slave 24
AS-i Master
Power
PROFINET
Config error
U AS-i
AS-i active
prg enable
prj mode
AS-Interface
AS-i Slave 1
AS-i Slave 5
AS-i Slave 24
2s
1.24
MISSING SLAVE
2s
AS-i Master
set/
LCD
LCD
PROFINET error No connection 1: ON 2: OFF
24
27.9.2013
35
Page 36
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Installation

7.6 Addressing

7.6.1 Assigning address 15 to slave currently at address 2

1. 41
SEARCHING SLAVE
OK
LCD
4x
OK
SLAVE ADR TOOL OLD ADDRESS 2 NEW ADDRESS 0 PRG
6x
OK
1x
QUICK SETUP AS-I SAFETY DIAGNOSIS
SLAVE ADDR TOOL
OK
AS-I CIRCUIT 1 AS-I CIRCUIT 2
OK
SLAVE ADR TOOL CONNECT NEW SLAVE
OLD ADDRESS
NEW ADDRESS
OK
Master Slave
Connect module
Hinweis!
Weitere Informationen finden Sie im Kap. <Bedienung im erweiterten Anzeigemodus>.
2 x ESC
SLAVE ADR TOOL OLD ADDRESS 2 NEW ADDRESS 15 PRG
SLAVE ADR TOOL OLD ADDRESS 2 NEW ADDRESS 15
PRG
OK
SLAVE ADR TOOL CONNECT NEW SLAVE OLD ADDRESS NEW ADDRESS
1. 15
UNKNOWN SLAVE
36
27.9.2013
Page 37
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Installation

7.7 Local parameter setting of safe AS-i Gateways and Monitors

CHIPCARD AND
DATA
DIFFERENT
CARD->MASTER
MASTER->CARD
CONTINUE
Daten kopieren
Keine Aktion erforderlich
CHIPCARD FOUND
DATA WILL
BE SYNCHRONIZED
Keine Aktion erforderlich
Master->Karte
Karte->Master oder
/No action required/
/Aucune action requise/
/No action required/
/Aucune action requise/
Unsichere Daten / Non-safe data/
Données non-sécurisées/
Dati non sicuri / Datos no seguros/
Geräte+Chipdaten ungleich
(Werkskonfiguration geändert)
/Device+card data not equal
(Factory configuartion changed)
Fehlermeldung:
/Error message/
Geräte+Chipdaten gleich
/Device data+card data equal/
Keine Meldung
Karte leer + formatiert
/Card empty + formatted/
Daten werden synchronisiert:
/No message/
/Data being synchronized/
/Copy data Card->Master
or Master->Card/
/Copier données Carte->Maître ou
Maître-Carte/
/Copiare dati Chipcard->Master o
copiare dati Master->Chipcard/
/Copiar datos TarjetaChip->Maestro
o Maestro ->TarjetaChip/
/Nessuna azione richiesta/
/Ninguna acción requrida/
/Nessuna azione richiesta/
/Ninguna acción requrida/
konfiguration)
en kompatibel
(Werks
Dat
/Data compatible (factory
Daten nicht kompatibel
/Data not compatible/
/
Card not formatted
Karte nicht formatiert
/
27.9.2013
DATA FROM
Daten werden übernommen:
/Data being acepted/
configuration)/
CHIPCARD NOT
COMPATIBLE
Fehlermeldung:
/Error message/
NEW CHIPCARD
WILL BE FORMATTED
Karte wird formatiert:
/Formatting card /
CHIPCARD TAKEN
DATA WILL BE
SYNCHRONIZED
Keine Aktion erforderlich
/No action required/
/Aucune action requise/
/Nessuna azione richiesta/
/Ninguna acción requrida/
Karte löschen
/Clear the card/
/Supprimer carte/
/Cancellare chipcard/
/Borrar tarjeta chip/
Keine Aktion erforderlich
/No action required/
/Aucune action requise/
/Nessuna azione richiesta/
/Ninguna acción requrida/
37
Page 38
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Installation
ERROR.
CHIPCARD AND
SAFETY DATA
DIFFERENT.
DELETE CHIPCARD
Stamm-/Vollständige
Konfiguartion auf der Chipkarte
enthalten
/Master configuration or
complete configuration on the
card
Sichere Daten / Safe data/
Données sécurisées/
Dati sicuri / Datos seguros
Stamm-/Vollständige
Konfiguartion auf der Chipkarte
/Master configuration or
complete configuration on the
Gerät enthält keine validierte
Konfiguration
/No validated configuration in
Gerät enthält validierte
Konfiguration, Daten ungleich
/There is a validated
configuration on the card, data
not equal
card
Gerät enthält validierte
Konfiguration
/There is a validated
configuration on the card
the device/
Stamm-/Vollständige
Konfiguartion auf der Chipkarte
/Master configuration or
complete configuration on the
card
Beide Konfigurationen ungleich/
Both configurations not equal
Fehlermeldung:
/Error message/
Beide Konfigurationen gleich/
Both configurations identical
Keine Meldung
/No message/
COPY BANK A TO
Datenfreigabe per
MONITOR
Release-Code notwendig:
/Data release via release code
required/
OR SAFETY DATA
...
RELEASE CODE:
1BDF
---------------
TYPE CODE
1BDF OK
Daten löschen
/Clear data/
/Supprimer données /
/Cancellare dati
Keine Aktion erforderlich
/No action required/
/Aucune action requise/
/Nessuna azione richiesta/
Konfiguration per
Release-Code freigeben
/Validate the configuration
via release code/
/Borrar datos
/Ninguna acción requrida/
/Respecter les indications
de sécurité exposées
dans le manuel ASIMON
/Osservare le istruzioni di
sicurezza riportate nel
manuale ASIMON
/Habilitar la configuración
vía código de liberación/
38
CHIPCARD FOUND
SAFETY DATA WILL
Validierte Konfiguration im
Gerät, Chipkarte leer
/Validated configuration
in the device, chip card empty/
Keine validierte Konfiguration im
Gerät + Chipkarte
/No validated configuration in
the device + chip card/
Sichere Daten auf der
Chipkarte nicht kompatibel
zum Gerät
/Safe data on the chip card
not compatible to the device/
BE SYNCHRONIZED
Daten werden synchronisiert:
/Data being synchronized/
CHIPCARD FOUND
SAFETY DATA WILL
BE SYNCHRONIZED
Daten werden synchronisiert:
/Data being synchronized/
CHIPCARD NOT
COMPATIBLE
Fehlermeldung:
/Error message/
For further information see manual, section <Chip card>
Keine Aktion erforderlich
/No action required/
/Aucune action requise/
/Nessuna azione richiesta/
/Ninguna acción requrida/
Keine Aktion erforderlich
/No action required/
/Aucune action requise/
/Nessuna azione richiesta/
/Ninguna acción requrida/
Karte löschen
/Clear the card/
/Supprimer carte/
/Cancellare chipcard/
/Borrar chip/
27.9.2013
Page 39
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Installation

7.8 Replacing a defective safety-related AS-i slave

The new slave must be able to send code sequences and must have the same address as the old one. The addressing of the new slave is carried out automatically by default for all Pepperl+Fuchs AS-i Masters. Only one missing slave is allowed!
[2]
ESC/Service (3 seconds)
[1]
27.9.2013
CONNECT NEW SLAVE 17 THEN PRESS SERVICE
[4]
ESC/Service (3 seconds)
[3]
39
Page 40
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Installation

7.9 Replacing the chip card

Always turn off power before inserting or removing the card!
[1]
[2]
old
[3]

7.10 Replacing a defective device

If Safe Link is used, it is necessary to teach the group manager after replacing a defective device (see next section)!
40
new
27.9.2013
Page 41
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Installation
[1]
[2]
old
new
[3]
27.9.2013
41
Page 42
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Installation
|COPY BANK A |
|COPY BANK A |
|TO MONITOR |
|TO MONITOR |
|MASTER |
|MASTER |
|CONFIGURATION
|CONFIGURATION
↓ |
|
... |RELEASE CODE | |FFFF | |----------------| |TYPE CODE ? | | |
|RELEASE CODE | |FFFF | |----------------| |TYPE CODE ? | |0000 OK|
|RELEASE CODE | |FFFF |
|----------------| |TYPE CODE |
OK
|0000 OK|
42
|START MONITOR | | | | |
|
|OK
Press OK for Menu Output Circuit 1:ON 2:ON 3:ON 4:ON
OK
OK
27.9.2013
Page 43
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Installation

7.10.1 Teaching the group manager after replacing a device

|QUICK SETUP | |SAFETY | |DIAGNOSIS | |SLAVE ADR TOOL |
|AS-SAFETY | |SAFE OUTPUT CH | |START/STOP | |CLEAR SAFE CFG | |PIN | |PROTECT | |SWITCH CYCLES | |CROSS COMM. |
|INTERFACE | |NODE STATUS | |NODE OVERVIEW | |TEACH IN |
|WARNING | |SAFE CROSS COMM.| |WILL BE STOPPED |
|NUMBER OF | |REPLACED NODES | |1 | |OK |
OK
OK
OK
OK
OK
|WARNING | |SAFE CROSS COMM.|
OK
|WILL BE STARTED |
PRESS OK FOR MENU
OUTPUT CIRCUIT
esc
1:ON 2:ON 3:ON 4:ON
27.9.2013
43
Page 44
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Installation

7.11 Replacing the monitor

"1"+
"1"
Monitor
AS-i 1 AS-i 2
[1]
Monitor
"2"
"2"+
"2"
Monitor
AS-i 1 AS-i 2
[2]
"1"+
Monitor
"1"
Monitor
+ "2"
"1""2"
Monitor
+ "2"
+ "1"
44
"1"+
"2"
Monitor
AS-i 1 AS-i 2
Monitor
+ "2"
"1"
27.9.2013
Page 45
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Installation
Safety configuration + AS-i configuration different!
+ "1"
"2"
Monitor
|Error: |Chip Card and |
ESC
|Safety Data | |Different. | |Delete Chip | |Card or Safety | |Data |
|Chipcard and | |AS-i Data |
|Different | |Chipcard->Master |Master->Chipcard |Continue
| |
OK
ESC
Press OK for Menu
Output Circuit
OK
1:OFF 2:OFF 3:OFF 4:OFF
|QUICK SETUP | |SAFETY | |DIAGNOSIS
|
|SLAVE ADR TOOL |
OK↓OK
|TEST |
|SAFE CHIPCARD | |ACTIVE: BANK A |
|VIEW | |CARD -> MONITOR |
OK |MONITOR -> CARD | |CLEAR CODES
|
|LCD CONTRAST |
27.9.2013
45
Page 46
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Installation
|ENTER PIN | |0000 | | |
|
|OK
|SELECT BANK |
|
|A | | |OK |
|STOP MONITOR | | | | |
|
|OK
|COPY BANK A to | |MONITOR | |RELEASE DATE: | |2006/06/17 18:43 | |BY: | |ROLF BECKER | |CONFIG NAME: | |TEST SOFTWARE | |INSTALLATION | |INSTRUCTION V1.00 | |RELEASE CODE: | |1BDF | |-------------------| |TYPE CODE | |1BDF OK |
|START MONITOR | | | | |
|
|OK
OK
OK
OK
OK↓OK
OK
ESC
46
Press OK for Menu Output Circuit 1:ON 2:ON 3:ON 4:ON
OK
27.9.2013
Page 47
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Installation
Safety configuration + AS-i configuration identic!
AS-i 1 AS-i 2

7.12 Safe configuration using ASIMON 3 G2

ASIMON 3 G2 Software
Start
Before commissioning the safety unit, put the gateway into operation!
ASIMON 3 G2 Software
Change the preset password during the first use of the device (Monitor/change password)!
ASIMON 3 G2 Software
Create the desired configuration.
ASIMON 3 G2 Software
Download the configuration with MONITOR / PC-> MONITOR into the device. Enter the password for this purpose.
27.9.2013
47
Page 48
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Installation
ASIMON 3 G2 Software
You can acknowledge the request TEACH CODE SEQUENCES? selecting "Yes", or you can do it later via display selecting "No".
ASIMON 3 G2 Software
Check the configuration log (respect instructions in <chap. 5.8> of the ASIMON manual!).
ASIMON 3 G2 Software
Validate the configuration with MONITOR –> VALIDATION.
ASIMON 3 G2 Software
Start the monitor with MONITOR–> START.
PRESS OK FOR MENU
OUTPUT CIRCUIT
Press OK for Menu
Output Circuit
1:ON 2:OFF
1:ON 2:ON
3:ON 4:ON
The device is in the protected mode now.
48
If you have assigned the safety monitor its own address in the software ASIMON 3 G2, adjust the configuration in the AS-i master (Quick Setup)! This is also valid when using simulated slaves. /
Please consider notes on safety in the software manual ASIMON 3 G2!
27.9.2013
Page 49
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Maintenance

8. Maintenance

8.1 Checking for safe turn-off

The safety representative is responsible for checking flawless function of the AS-i Safety Monitor within the safety system.
Safe turn-off when an associated safe sensor or switch is triggered must be checked at least once a year.
Attention!
To do this, actuate each safe AS-i slave and observe the switching behavior of the output circuits of the AS-i Safety Monitor.
Attention!
Note the maximum turn-on duration and the overall turn-on operating duration. These values depend on the PFD value selected (see section <Safety-relevant characteristic data>).
When the maximum turn-on duration is reached (three, six or twelve months), check the complete safety system and its proper function.
When the total operating time (20 years) has been reached, the device must be returned to the manufacturer to check for proper function.
27.9.2013
49
Page 50
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Electrical connection

9. Electrical connection

9.1 Overview of terminals, indicators and operating elements

9.1.1 VBG-PN-K30-D-S16, VBG-PN-K30-DMD-S16, VBG-PNS-K30-DMD, VBG-PN­K30-DMD-S16-EV
[1]
[6]
[2]
[3]
[1]
[4]
[5]
-
-
+-+
+
[6]
[7]
[8]
Legend:
[1] LEDs [2] PROFINET interface [3] LC display [4] Buttons [5] Terminals: Supply voltage and AS-i circuit [6] Terminals: Safety unit [7] Chip card slot [8] RS 232 diagnostics port
1
10
0,2 ... 2,5 mm
10
0,2 ... 2,5 mm
AWG 24 ... 12
2
2
50
1. Only together with ASIMON 3 G2 Software or AS-i Control Tools
27.9.2013
Page 51
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Electrical connection

9.2 AS-i bus connection

Blue AS-i-
Brown AS-i+
Blue AS-i-
Brown AS-i+
Yellow ASi ribbon cable
2-conductor AS-i round cable (Recommended: flexible power cable H05VV-F2x1,5 per DIN VDE 0281)
Information!
Electrical work is to be performed only by electrical technicians.

9.3 Information about the device types

Information!
A listing of the individual devices and their features can be found in section <Product information>.

9.4 AS-i and power supply terminal assignments

Information!
The cable indicated by grey must not have slaves or repeaters connected to it.
The yellow cable must not have AS-i power suppliers or additional masters connected to it.
Information!
The function ground can be connected either to the grounding screw or to the terminal.
The function ground should be made with as short a cable as possible to ensure good EMC characteristics.
Therefore function grounding using the grounding screw is preferred.
Attention!
The AS-I power supply for the AS-I components must have isolation per IEC 60 742 and be able to handle momentary power interruptions of up to 20 ms. The power sup­ply for the 24 V supply must also have isolation per IEC 60 742 and be able to handle momentary power interruptions of up to 20 ms. The maximum output voltage of the power supply must also be less than 42 V in case of a fault.
+AS-i 2– (Connection to 2nd AS-i Circuit)
More information about the additional slave circuit can be found in section <Safe cou­pling slaves on the AS-i circuits>.
27.9.2013
51
Page 52
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Electrical connection

9.4.1 Electrical connection VBG-PN-K30-D-S16

M4
5 mm max!
Function ground
Gateway Safety Unit
+ASI 1
-
+-+
+ASI 1–
+ASI 1–
ASI 1 +PWR– (max. 8A)
+
+ASI 2– / 24V, 0V
ASI 1
+ASI 2-
+PWR-+ASI 1
24V 0V
-
-
+
+
Terminal Signal / Description
+ASI 1–
ASI 1 +PWR–
+ASI 2 – / 24 V, 0 V
FG
Connection to AS-i Circuit 1
Supply voltage for AS-i Circuit 1 (max. 8 A)
Connection to AS-i Circuit 2; 24 V supply optional
Function ground
Information!
For additional information, please refer to the section <AS-i and power supply terminal assignments>.
52
27.9.2013
Page 53
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Electrical connection

9.4.2 Electrical connection VBG-PN-K30-DMD-S16-EV

Gateway Safety Unit
M4
5 mm max!
Function ground
+ASI 1–
+ASI 1–
+ASI 2–
+
ASI +PWR– (max. 8A) / 24V, 0V
+ASI PWR-
+ASI
+ASI 1
1
2
+ASI
24V 0V
-
-
-
+-+
+
+
Terminal Signal / Description
+ASI 1–
+AS-i 2–
ASI +PWR– /
24 V, 0 V
FG
1. The gateway is AS-i Power24V capable and can be operated directly on a 24V (PELV) power sup­ply.
Connection to AS-i Circuit 1
Connection to AS-i Circuit 2
Supply voltage for AS-i Circuits (max. 8 A) /
Power 241 supply optional
Function ground
Information!
AS-i Circuit 1 and 2 are both powered from a
Pepperl+Fuchs GmbH power supply!
No other power supplies are approved!
Attention!
Earth fault detector sensor without function when using AS-i Power24!
Information!
For additional information, please refer to the sections: <AS-i and power supply termi­nal assignments> and <AS-i Power24V capable>.
27.9.2013
53
Page 54
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Electrical connection

9.4.3 Electrical connection VBG-PN-K30-DMD-S16, VBG-PNS-K30-DMD

Gateway Safety Unit
M4
5 mm max!
-
-
+-+
+
Function ground
+ASI 1–
ASI 1 +PWR– (max. 8A)
+ASI 2–
+
ASI 2 +PWR– (max. 8A)
Terminal Signal / Description
+ASI 1–
+ASI 2–
ASI 1 +PWR–
ASI 2 +PWR–
FG
Connection to AS-i Circuit 1
Connection to AS-i Circuit 2
Supply voltage for AS-i Circuit 1 (max. 8 A)
Supply voltage for AS-i Circuit 2 (max. 8 A)
Function ground
Information!
AS-i Circuits 1 and 2 are powered by separate power supplies.
Information!
For additional information, please refer to the section <AS-i and power supply terminal assignments>.
54
27.9.2013
Page 55
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Electrical connection

9.5 Diagnostics interface The service and diagnostics interface (in conjunction with AS-i Control Tools or

ASIMON 3 G2 software) is used for communication between the PC and the unit.

9.5.1 Diagnostics port RS 232

The service and diagnostics interface is configured as a mini DIN-6 female and it is placed on the front plate, on the left hand side.

9.6 PROFINET interface

LEDs
RJ45 socket
2 1
RJ45 socket
LEDs
Connection to an Ethernet network is carried out using the one of the two RJ45 sockets on the left housing side (see section <Overview of terminals, indicators and operating elements>).
The two sockets lead to an integrated real-time switch. They are based on MDI/ MDI-X (auto-crossover) and support 100Base-TX und 10Base-T networks in each case with full- and half duplex (auto negotiation).
Information!
The switch will operate only if supply voltage (± PWR) is present.
LEDs in the sockets (2 per socket):
Port (green)
LED flashes green: ethernet connection active (i.e. cable plugged in).
Activity (yellow)
LED flashes yellow: transmitting/receiving active.
27.9.2013
55
Page 56
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Electrical connection

9.7 Safe coupling via Ethernet (VBG-PN-K30-DMD-S16-EV)

The device supports Safe Link via Ethernet. In order to establish a safe coupling between several devices, they should be connected via the ethernet diagnostics interface to a switch.
Switch
ASIMON 3 G2
...
Information!
Please refer here to the information in the section <Safe Link>.

9.8 Chip card

56
The configuration is stored in a fixed installed EEPROM and can be overwritten by the chip card. The chip card does not have to be inserted in operation.
Warning!
Power must always be turned off when removing or inserting the chip card!
27.9.2013
Page 57
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Electrical connection

9.9 Release circuits

9.9.1 Wiring overview - safety unit

1.13
2.13+324 V
0 V
+4
2.Y2
2.Y1
Aux
1.Y1
1.Y2
2.Y1
2.Y2
K1
K2
K3
K4
1.Y2
1.Y1
2.14+24.14+11.14
3.14
1.Y1 (EDM 1/Start 1), 2.Y1 (EDM 2/Start 2), 1.Y2 (EDM 3/Start 3),
2.Y2 (EDM 4/Start 4)
The safety unit provides 4 inputs. The EDM & START inputs can be defined freely. The inputs may not be connected to other potentials, but rather only directly or through potential-free switches to + (for EDM/START). Switching current static 4 mA at 24 V, dynamic 30 mA at 24 V (T=100 µs).
3.14, 4.14
Semiconductor outputs. Max. contact load: 0.5 A DC-13 at 30 V.
1.13, 1.14; 2.13, 2.14
Potential-free relay contacts. Safety relay with one contact set for read-back. Max. contact load: 3 A AC-15 at 30 V, 3 A DC-13 at 30 V.
0V, 24V
Semiconductor outputs are powered by separate 24 V DC.
+1, +2, +3, +4 (for EDM/Start)
Output supply, powered by AS-i. May not be connected to other potentials, but rather only directly or through potential-free switches to one of the EDM or START inputs. Voltage 30 ... 15 VDC.
27.9.2013
57
Page 58
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Electrical connection

9.10 Indicators and operating elements

9.10.1 LED indicators – master
PROFINET
The LED’s on the front panel of the device indicate:
Power
The master is receiving sufficient power.
PROFINET
Green: PROFINET controller connected (otherwise LED flashes red)
config error
Configuration error. At least one configured slave is missing, or at least one detected slave is not config­ured, or for at least one configured and detected slave the actual configuration data does not match the nominal configuration data, or the master is in the startup pro­cess. This LED flashes if a peripheral fault has been detected for at least one AS-i slave on the AS-i network. If there are configuration errors as well as periphery faults, only the configuration error is displayed.
U AS-i
The AS-i network is sufficiently powered.
AS-i active
Normal operation is active
prg enable
Automatic single node replacement is enabled. Exactly one slave is missing in the protected operating mode. The slave can be replaced by another slave of the same type with address zero. The master automat­ically addresses the new slave to the faulty address and thus corrects the configura­tion error
prj mode
The AS-i master is in configuration mode.
58
27.9.2013
Page 59
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Electrical connection

9.10.2 LED indicators - safety unit

1.13
2.Y2
Aux
1.Y1
2.Y1
K1
K3
1.14
2.13+324 V
0 V
+4
2.Y1
1.Y2
2.Y2
K2
K4
1.Y2
1.Y1
+1
2.14+24.14
3.14
The LED’s on the safety unit indicate:
Aux
24 V supply for the semiconductor outputs is present.
1Y.1, 1Y2, 2Y.1, 2Y.2
Input 1.Y1 (EDM 1/Start 1), 2.Y1 (EDM 2/Start 2), 1.Y2 (EDM 3/Start 3),
2.Y2 (EDM 4/Start 4) is turned on.
K1, K2
Contact sets 1.13, 1.14 (K1) resp. 2.13, 2.14 (K2) closed.
K3, K4
semiconductor output 3.14 (K3) resp.4.14 (K4) is turned on.
Information!
If there is no auxiliary voltage connection available, LEDs are turned off, even if the corresponding release circuit is turned on.
27.9.2013
59
Page 60
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Electrical connection

9.10.3 Buttons

The buttons are used for the following:
Mode/
Switching between configuration mode and protected operating mode, and saving the current AS-i configuration as the nominal configuration.
Set/⇓
Selecting the address of and assigning an address to a slave.
OK
Change to extended mode.
ESC/Service
For teaching the code table for a new safe slave, when exactly one safe slave is being replaced, and for unlocking the Safety Monitor. This button is also used to exit extended mode.
For additional information see:
•<Section <Function of the ESC/Service key>
•<Section <Replacing a defective safety-configured AS-i slave>
•<Section <Operation in advanced display mode>.
60
27.9.2013
Page 61
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Function and startup of the Safety Monitor

10. Function and startup of the Safety Monitor

Configuration and startup of the AS-i Safety Monitor is accomplished using a PC/ Notebook and the ASIMON 3 G2 configuration software.
The operating language of the device can be set for the respective country (see section <Operation in advanced display mode>).
Information!
The description of the ASIMON 3 G2 software and startup of the AS-i Safety Monitor can be found in the manual “ASIMON 3 G2 AS-i Safety Monitor Configuration Software for Microsoft®-Windows®“.
The software manual is an important component of the operating manual for the AS-i Safety Monitor. It is not possible to configure and start up the AS-i Safety Monitor with­out the ASIMON 3 G2 software.
Configuration may be performed only by a safety authorized person. All safety-re­lated commands are password protected.

10.1 Powering up the device

As soon as supply voltage is present on the device an internal system test is start­ed. This operating state is indicated by lighting of the upper LED row.

10.2 Configuration of the safety functions

The device can be configured in several ways:
1. Using ASIMON 3 G2 software
The ASIMON 3 G2 software represents the most universal method of con­figuring the Safety Monitor. Here the behavior of the Safety Monitor can be determined by linking various monitoring modules. After being sent to the Safety Monitor, this configuration is verified and can then be validated. For additional information, refer to the separate manual for the ASIMON 3 G2 configuration software.
2. Using a chip card with the master configuration
Configurations stored on the chip card, which are validated but which do not contain any code sequences, can be sent to the device. The code sequences must then be taught to the corresponding safety AS-i slaves. This procedure is useful when you want to use a safety program in several safety monitors without any changes.
Information!
For additional information refer to section <Description of configuration using chip card with master configuration>.
27.9.2013
61
Page 62
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Function and startup of the Safety Monitor
3. Using a chip card with complete configuration
In contrast to the master configuration, the complete configuration also con­tains the code sequences for all included slaves. Sending the complete con­figuration from the chip card to the Safety Monitor can make replacement of the device enormously simpler and faster.
Information!
For additional information refer to <Configuration using a chip card with complete con­figuration>.

10.2.1 Description of configuration using ASIMON 3 G2 software

The following description represents a short guide to configuring the AS-i Safety Monitor. For a detailed description of the ASIMON 3 G2 software, refer to the cor­responding manual for the ASIMON 3 G2 configuration software.
The ASIMON 3 G2 software is responsible for the following:
Configuring the AS-i Safety Monitor
Documenting the device configuration
Starting up the AS-i Safety Monitor
Diagnosing the AS-i Safety Monitor
Information!
The description of the ASIMON 3 G2 program can be found in the separate software manual.
62
Proceed as follows:
Install the program on your PC.
Apply power to the AS-i Safety Monitor
Information!
To prevent ESD damage, we recommend grounding at an appropriate location before plugging in the interface cable to the Safety Monitor.
Connection of monitors with a RS 232 diagnostics interface
To connect, plug the diagnostic cable end with the PS2 connector into the socket of the diagnostic interface (RS 232) of the monitor and the other end with the 9-pin Sub-D socket connector to a free COM port (serial RS232 interface) on your PC (see section “Connection between the AS-i Safety Monitor and the PC" in the software manual).
Configure the AS-i Safety Monitor and start it up as described in the software manual.
Attention!
Before starting up the device you must adapt the device configuration to your application. This means configuring the AS-i Safety Monitor according to the soft­ware manual so that the location to be protected is in fact protected by the device.
27.9.2013
Page 63
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Function and startup of the Safety Monitor

10.2.2 Description of configuration using chip card with master configuration

Generating a master configuration:
Generate a configuration using the ASIMON 3 G2 software
Load the configuration into the device
Release (validate) the configuration, but do not teach the code sequences
The code sequences will be taught on the physical AS-i circuit
Attention!
Safety advisory:
Ensure that the chip card contains the configuration intended for and released for the application!
This can be done by comparing the release codes on the display (section <Ope­ration in advanced display mode>):
The safety representative who generated and validated the release code stores the release code for the master configuration and approves use of the configuration for specific equipment.
The person performing the startup reads out the release code on the display before teaching the code and compares it with the release code stored and approved for the equipment.
After the chip card has been used to load the configuration into the device, the safety functions of the device must be checked in the equipment.
Checking of the release code and testing the system must be documented in wri­ting and is part of the system documentation.

10.2.3 Configuration using a chip card with complete configuration

The chip card contains the complete configuration if:
An empty chip cared is plugged into an AS-i Safety Monitor which already contains a complete configuration, or
The chip card is already inserted while the configuration is being written into the device using ASIMON 3 G2 software and before validating the code sequences.
If the AS-i Safety Monitor needs to be replaced, the stored configuration can be transferred by simply plugging the chip card from the old device into the new one.
27.9.2013
63
Page 64
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Function and startup of the Safety Monitor
Attention!
Safety advisory:
Power must always be turned off when removing or inserting the chip card!
Ensure that the chip card contains the configuration intended for and released for the application!
This can be done by comparing the release codes on the display (section <Ope­ration in advanced display mode>):
The safety representative who generated and validated the release code stores the release code for the master configuration and approves use of the configuration for specific equipment.
The person performing the startup reads out the release code on the display before starting the equipment and compares it with the release code stored and approved for the equipment.
After the chip card has been used to load the configuration into the device, the safety functions of the device must be checked in the equipment.
Checking of the release code and testing the system must be documented in wri­ting and is part of the system documentation.

10.3 Safety-relevant documentation of the application

Information!
The detailed description of the safety-relevant documentation of the configuration for your application can be found in the separate software manual.
Proceed as follows:
Create the configuration of the AS-i Safety Monitor for your application.
Validate the configuration (done by the safety supervisor).
Print out the final configuration protocol and optionally the configuration over­view (see Section "Configuration documentation" in the software manual).
Sign the final configuration protocol (done by the safety supervisor).
Take the protocol for the safety-relevant documentation for your application (machine documentation) and keep it in a safe place.

10.4 Diagnostic data

Information!
A detailed description of the setting for diagnostics mode is described in the section “Setting diagnostics type” in the separate manual "AS-i 3.0 Command Inteface".
Diagnostics data can be obtained in any of 4 ways:
•Display
Diagnostic interface
1. Only together with ASIMON 3 G2 Software or AS-i Control Tools
64
1
27.9.2013
Page 65
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Function and startup of the Safety Monitor
Fieldbus interface
1

10.4.1 Diagnostics of release circuits 1-4 via the binary data

If monitor slaves with base address +1 and +2 exist, the state of several OSSDs is transmitted there.
Monitor base address+1 assignment
Data bit Content
D0
D1
D2
D3
State of output circuit 1
State of message output 1
State of output circuit 2
State of message output 2
Monitor base address+2 assignment
Data bit Content
D0
D1
D2
D3
State of output circuit 3
State of message output 3
State of output circuit 4
State of message output 4

10.5 Switch-off history

The switch-off history, accessible from the menu DIAGNOSTICS->INT MONI­TOR->LAST DIAGNOSTIC, is intended to make reconstruction of the reason for switch-off easier for the user. The states of all safety-relevant AS-i slaves and all devices at the time the state change on the output device (change from green to another color) are stored.
Information!
Available only with AS-i/PROFINET Gateways.
27.9.2013
65
Page 66
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Function and startup of the Safety Monitor

10.5.1 Diagnostic values in the IDI

IDI diagnostics can be optionally enabled for the following devices:
VBG-PN-K30-D-S16 ident. no. 15050
VBG-PN-K30-DMD-S16 ident. no.
15051
The input values for safety-relevant input slaves can be substituted in various ways. This makes the diagnostics information available directly in the cyclical I/O data. The default setting is the "substitution values" for the two input channels. Setting diagnostics values also sends 2 bits of color information for the associated safety-relevant component in addition to the input channels. The substitution pos­sibilities are defined in the following tables:
Bit 3 Bit 2 Bit 1 Bit 0 Description
0 0 0 0 Both channels off
0 0 1 1 2nd channel off, 1st channel on
1 1 0 0 2nd channel on, 1st channel off
1 1 1 1 Both channels on
VBG-PNS-K30-DMD ident. no.
15054
VBG-PN-K30-DMD-S16-EV ident. no.
Tab. 10-8. Default status substitution values
15216
66
Bit 3 Bit 2 Bit 1 Bit 0 Description
0 0 Both channels off
0 1 2nd channel off, 1st channel on
1 0 2nd channel on, 1st channel off
1 1 Both channels on
00 Device color: red, green or blue
01 Device color yellow: ("wait")
10 Device color: yellow flashing ("test")
11 Device color: red flashing ("error")
Tab. 10-9. Diagnostic values
Information!
The switching state of channel 1 and channel 2 (channel 1, channel 2 'on' or 'off', bit 0, bit 1) is sent at optimal speed. The device colors (bit 2, bit 3) have device-internal lower priority and can be sent slower.
The diagnostic values bit 0/1 and 2/3 are not synchronized. The states of the input channels and the resulting color can be sent at different times.
27.9.2013
Page 67
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Function and startup of the Safety Monitor
Information!
The color and thereby the status of the component do not always have to agree with the switching state of the input channels. In case of lost telegrams, untaught slaves or non-synchronous switching of the two channels, error and test states may result (red flashing and yellow flashing).

10.6 Password protection

All safety-related commands are password protected. These include:
Loading configurations into the Monitor
•Stopping
Learning code sequences
Releasing
Changing the password
Information!
No new release is necessary if when using safety-configured AS-i slaves code sequences have been newly learned using the ESC/Service key.
27.9.2013
67
Page 68
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Function and startup of the Safety Monitor

10.6.1 Procedure for configuring and teaching code sequences

The configuration is created using ASIMON 3 G2 software, loaded into the safety unit and released. The name of the person releasing and the date are stored at this moment. If code sequences controlled through the display are newly taught, this is secured by a PIN to prevent unintended/unauthorized changing of the code sequences.
Information!
For additional information see section<Replacing a defective safety-configured AS-i slave>.
A PIN is a 4-digit number and can only be changed from the display, not via the ASIMON 3 G2 software.
After entering the PIN, the display can be used to start a teaching procedure for the code sequences. The monitor stops immediately after entering the PIN. After teaching, the monitor starts after a prompt and acknowledgement on the display.
Action ASIMON Software On AS-i Safety Monitor
Configure and load into Safety Monitor
Stopping ••
Releasing •−
Starting ••
Teaching code sequences ••
Changing the password ••(only from chip card)
Changing the PIN −•
Legend: "•" = possible; "–" = not possible
Code sequences for releasing a configuration do not necessarily have to have been successfully learned. It is also possible to release without code sequences, which must then be learned at a later time.
Teaching the code sequences is simple to perform:
Using the ESC/Service key (See section <Replacing a defective safety-con­figured AS-i slave>)
or
Using the display (See section <Operation in advanced display mode>).
•• (only from chip card)
Tab. 10-10.
68
27.9.2013
Page 69
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Function and startup of the Safety Monitor

10.6.2 Function of the ESC/Service key

In traditional (classical) display mode, the ESC/Service key takes on two kinds of functions:
Briefly pressing the ESC/Service key unlocks the Safety Monitor when red is flashing
A longer press (3s) starts the teach procedure for a slave.
Information!
For additional information see section <Replacing a defective safety-configured AS-i slave>.

10.7 Safe coupling slaves on the AS-i circuits

The two AS-i circuits are capable of emulating a total of up to sixteen safe cou­pling slaves.
The assignment of the coupling slaves addresses to the release circuits is made using the ASIMON software.

10.8 Chip card

The chip card is divided into two areas. One area is reserved for unsafe data and administration, the other for safe data.
Warning!
Always turn off power before inserting or removing the card.

10.8.1 Unsafe data

This section describes the system behavior of the unsafe system section when using the chip card.
10.8.1.1 Card unformatted
If an unformatted card is found when the device is started, the following is dis­played:
The chip card is formatted and then the data copied to the chip card.
27.9.2013
NEW CHIPCARD WILL BE FORMATED AS-I DATA WILL BE SYNCHRONIZED
69
Page 70
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Function and startup of the Safety Monitor
10.8.1.2 Data not compatible
If a card is found whose data are incompatible with the device, the following error message is displayed:
CHIPCARD NOT COMPATIBLE
10.8.1.3 Card empty
The following message is displayed for an empty card:
CHIPCARD FOUND AS-I DATA WILL BE SYNCHRONIZED
From this time on all changes are made both in the device and on the chip card.
10.8.1.4 Data compatible
When starting with an empty device (e.g. after a factory reset) a non-empty card is found whose data are compatible with the device, the following message is dis­played:
AS-I DATA FROM CHIPCARD TAKEN
The card configuration is written to the device. From this time on all changes are made both in the device and on the chip card.
10.8.1.5 Data in the device and on the chip card identical
If the card and device are not empty at start and the data are identical, no mes­sage is displayed.
10.8.1.6 Data in the device and on the chip card not identical
If the card and device are not empty at start and the data are not identical, an er­ror message is displayed and the card is not synchronized with the device. The following menu is then automatically opened:
70
27.9.2013
Page 71
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Function and startup of the Safety Monitor
CHIPCARD AND AS-I DATA DIFFERENT CARD->MASTER MASTER->CARD CONTINUE
Description
CHIP CARD>MASTER: Chip card data are copied to the master
MASTER->CHIPCARD: Master data are copied to the chip card
NEXT: No change to the data
The menu can be exited by pressing the ESC/Service key without changing the data.

10.8.2 Safe data

This section describes the system behavior of the safe unit when using the chip card.
In general the safe part of the chip card has 4 memory banks (A…D). A bank is referred to as an active bank. Unless otherwise stated, the operations described in the following are always performed on the active bank.
10.8.2.1 Data incompatible
If a card with incompatible data is found, the following error message is output:
10.8.2.2 Data compatible
If a card with an empty active memory bank is found, the safety configuration in­cluding code sequences is written to the card and in future all changes are made in the card and in the device at the same time. The following message is dis­played on the device:
27.9.2013
CHIPCARD NOT COMPATIBLE
CHIPCARD FOUND. SAFETY DATA WILL BE SYNCHRONIZED
71
Page 72
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Function and startup of the Safety Monitor
10.8.2.3 Complete configuration
If when starting with an empty device a card with a released safety configuration including code sequences is found (Complete safety configuration) in the active memory bank, this configuration is written to the device, then the menu for releas­ing using Release Code is opened:
COPY BANK A TO MONITOR RELEASE DATE: 2006/06/17 18:43 BY: ROLF BECKER CONFIG NAME: L3040 MIT LADEVO RRICHTUNG LINKU ND PALETTENWECHS LER V1.23 RELEASE CODE: 1BDF
- - - - - - - - -
- - - - - ­TYPE CODE 0 0 0 0
OK
If the active bank contains a Complete Configuration and if the data in the active bank on the memory card and the data in the device are identical (e.g. both emp­ty), in future all changes are made in the card and in the device at the same time.
10.8.2.4 Data on the chip card and in the device are identical
If the card and device are not empty at start and the data are identical, no mes­sage is displayed.
10.8.2.5 Data not identical
If the active bank on the memory card and in the device are not empty at start and the data are not identical, the following message is displayed:
ERROR. CHIPCARD AND SAFETY DATA DIFFERENT. DELETE CHIPCARD OR SAFETY DATA
72
27.9.2013
Page 73
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Function and startup of the Safety Monitor
The safety unit will not operate in this case. You must either clear the device or the active bank via menu.
10.8.2.6 Operating the chip card from the menu
The data on the chip card can, as described in section <SAFE CHIPCARD>, be exchanged between the Monitor and the chip card. Note however the following:
In order to store a configuration on the chip card as a master configuration (i.e. without code sequences), proceed as follows:
Write the released configuration into the Monitor without code sequences.
Copy the configuration into a memory bank using the menu. For additional information, see section <CARD –>MONITOR (copy card data to
the Monitor)>. To convert a master configuration on the memory card to a Complete Configura-
tion, this configuration must be overwritten by a Complete Configuration. This is done as follows:
Copy the card data to the Monitor.
Teach the code sequences
Write the data from the Monitor to the card.

10.8.3 Working with multiple memory banks

The chip card has four memory banks, each of which may contain a configuration (Complete or Master configuration). One of the banks is the active bank.
The AS-i 3.0 PROFINET Gateway with integr. Safety Monitor always independ­ently utilizes the active bank. Menu commands can however be used to copy the other memory banks to the AS-i Safety Monitor.
The corresponding memory bank thereby becomes the active bank. If configurations from another memory bank are copied, a few safety rules need to
be followed:
27.9.2013
73
Page 74
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Function and startup of the Safety Monitor
Attention!
Safety advisory:
Ensure that the configuration intended for and released for the application is used!
This can be done by comparing the release codes on the display (See section <MONITOR CONFIG>):
The safety representative who generated and validated the configuration stores the release code for the configuration (Complete or Master) stores the release code for the configuration and approves use of the configuration for specific equipment.
The person performing the startup reads out the release code on the display before starting the equipment or before teaching the code sequences in the case of master configurations and compares it with the release code released for the equipment.
After the chip card has been used to load the configuration into the device, the safety functions of the device must be checked in the equipment.
Checking of the release code and testing the system must be documented in wri­ting and is part of the system documentation.
74
27.9.2013
Page 75
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Operation in advanced display mode

11. Operation in advanced display mode

Information!
You will find a description of the display menu in the separate document
"Display_Menue".
27.9.2013
75
Page 76
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Advanced Diagnostics for AS-i Masters

12. Advanced Diagnostics for AS-i Masters

The advanced AS-i diagnostics is intended to localize occasionally occurring con­figuration errors and to determine the quality of data transmission on AS-i without using additional diagnostics tools.
AS-i Control Tools, a MS-Windows software designed to simplify AS-i installation and used to program AS-i Control, enables operation of the advanced diagnostics functions (LCS, error counters, and LOS).

12.1 List of corrupted AS-i Slaves (LCS)

The LCS contains the information from the Delta list. In addition to the list of con­figured slaves (LPS), the list of detected slaves (LDS), and the list of activated slaves (LAS), the AS-i master creates a fourth list, the list of corrupted slaves (LCS) containing advanced diagnostics data used to diagnose the causes for in­termittently occurring configuration errors on AS-i. This list contains entries for all AS-i slaves that were responsible for at least one intermittent configuration error since the list was last read or since the AS-i master was turned on. Furthermore, intermittent AS-i power failures are listed in the LCS at the position of AS-i slave with address 0.
Information!
Whenever the LCS is read it is deleted from memory.
Information!
The last intermittent configuration error can also be displayed on the AS-i master:
Pressing the "Set" button on the AS-i master initiates the display of the AS-i slave responsible for the last intermittent configuration error. If a intermittent AS-i power fail­ure occurred, the display shows 39 after pressing the "Set" button.
This function is only available if the device is in normal operating mode of the protected mode (display empty) or in the off-line phase (Display: "40").

12.2 Protocol analysis: Counters for corrupted data telegrams

The AS-i master with advanced diagnostics provides a counter for telegram repe­titions for each AS-i slave. The counter counts up every time a corrupted data tel­egram has been found, making it possible to determine the quality of the trans­mission if only a few telegrams are corrupt and the AS-i slave never caused a configuration error.
Information!
The counter values are read via the host interface and will be deleted after they were read.
The highest possible counter value is 254. 255 indicates a counter overflow.
Displaying the protocol analysis is possible through the AS-i Control Tools soft­ware by using the command "Master | AS-i Diagnostics".
76
27.9.2013
Page 77
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Advanced Diagnostics for AS-i Masters

12.3 Offline Phase for Configuration Errors

The AS-i masters with advanced diagnostics offer the possibility to set them­selves into the offline phase when a configuration error occurs and thus are able to transition the AS-i network into a safe operational state. This ensures a quick reaction to a configuration error and the host can be relieved from this task. If any problems occur on the AS-i network, the AS-i masters can independently switch the AS-interface into a safe state.
There are two different ways to parameterize the AS-i master for this feature:
Any configuration error occurring on AS-i switches the master from regular operation in protected mode into the offline phase.
o . A list with the addresses of slaves that can potential initiate the off-line phase is defined (list of offline slaves LOS).
The user can decide how the system should react to a configuration error on AS-i. Thus, the AS-i master can be set to the offline phase for critical AS-i slaves, whereas for less critical slaves only the error message is sent to the host, but AS­i is still running.
Like the advanced diagnostics, the parameterization "offline phase on configura­tion error" is also supported by "AS-i-Control-Tools" (Command | Characteristics | Offline because of configuration error).
There are two options to reset the error message "OFFLINE BY LOS:
1. Deleting the complete LOS list on the affected AS-i network ("CLEAR ALL").
2. Power reset on the affected AS-i network.
Attention!
If a power reset occurs on the AS-i network 1 the complete double gateway will be shut down.

12.4 Functions of the AS-i Fault Detector

12.4.1 Duplicate address detection

If two slaves on an AS-i network have the same address, a duplicate address ex­ists. Since the master cannot communicate individually with these slaves any longer, this is considered an error. Because the two slave replies interfere, it is im­possible for the master to recognize the slave responses. This results in extreme­ly unstable network behavior.
The duplicate address detection function is used to safely recognize a duplicate address and to display it on the screen and in AS-i Control Tools.
A duplicate address causes a configuration error and is displayed on the screen.
Information!
Duplicate addresses can be recognized only on an AS-i segment directly connected to the master.
27.9.2013
77
Page 78
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Advanced Diagnostics for AS-i Masters

12.4.2 Earth/Ground Fault Detector

An Earth/Ground Fault exists when the voltage
=0,5 U
U
GND
10% U
AS-i
AS-i
This error substantially limits the noise immunity of the AS-i communication. Ground faults are indicated on the master´s display as well as in AS-i Control
Tools.
Information!
To recognize ground faults the master must be grounded with its machine ground con­nection.
Information!
A ground fault in one of the two networks of a double master in a version 1 power sup­ply for two AS-i networks causes a ground fault in the other network as well because of the the existing galvanic connection.

12.4.3 Noise Detector

The noise detector detects AC voltages on AS-i, that are not initiated by an AS-i master or AS-i slaves. These interference voltages can cause telegram distur­bances.
A frequent cause are insufficiently shielded frequency inverters or improperly routed cables.
Noises is indicated on the master´s display as well as in AS-i Control Tools.
.) is outside of the following range:
U
90% U
GND
AS-i
U
GND
(Nominal value of

12.4.4 Over-voltage Detector

Over-voltages are present if the conductors of an AS-i network that normally are routed electrically symmetrical with respect to machine ground, are strongly elec­trically raised. A cause can for example be startup procedures of large consum­ers.
However, over-voltages do generally not interfere with the AS-i communication, but can under certain circumstances cause incorrect sensor signals.
Over-voltages are indicated on the master´s display as well as in the AS-i Control Tools.
78
27.9.2013
Page 79
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Advanced Diagnostics for AS-i Masters

12.5 Functions of the new generation of AS-i Gateways

The new generation scores with further optimized diagnostics, several additional functions and even greater operating convenience.
Information!
A listing of the individual devices and their features can be found in section
Generation of AS-i Gateways with ethernet diagnostics interface>.

12.5.1 C-programmable Gateways

Main menu || SETUP || AS-I CONTROL || CONTROL FLAGS ||
The devices programmed in C are able themselves to take over a great number of control tasks. In smaller systems the user will even be able to do without a PLC altogether: if desired the C program can function as a full mini-PLC. In more com­plex applications the C-programmable Gateways make the work of the PLC easi­er - for example by pre-processing special functions.
Control Info Control Run Control Flags
Control Flags 0:00 00 00 00 4:00 00 00 00 8:00 00 00 00
<New

12.5.2 Interchangeable memory card

Main menu || SETUP || CHIPCARD || AS-I CHIPCARD ||
Interchangeable memory card: redundant memory for C program and device con­figuration.
Chipcard AS-i Chipcard Format Chipcard

12.5.3 Earth fault monitor

Main menu || DIAGNOSE || ASI WATCHDOG ||
The new earth fault monitor allows the service technician to detect whether an earth fault has occurred directly on AS-i
1. Earth fault
27.9.2013
79
Page 80
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Advanced Diagnostics for AS-i Masters
or on a sensor line.
1. Earth fault sen.
The menu EFLT Ratio shows the asymmetry of the AS-i network, referenced to ground (see sketch).
100%
0%
100%
%
%
AS-i +
AS-i -
EFLT Ratio: AS-i+ 2% AS-i DC Voltage: 1 31,3V $
EFLT Ratio: AS-i+ 100% AS-i DC Voltage: 2 31,5V

12.5.4 Current can be read directly on the unit

Now the devices display both the maximum current and the current actually present in the respective AS-i circuit. Heavy consumers or a strong overload in an AS-i circuit are then easy to detect. Plus you can set the maximum current in the AS-i circuit on these devices. This ensures line protection even when using large 24V power supplies.
AS-i power Reset Maximal: 2 1,3A
80
27.9.2013
Page 81
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Advanced Diagnostics for AS-i Masters
Maximal: 1,3A current: 2 0,3A
Current: 0,3A Current limiting 2 3,2A

12.5.5 Self-resetting fuses

Main menu || SETUP || CURRENT LIMIT ||
Thanks to self-resetting fuses in the "1 Gateway, 1 power supply for 2 AS-i cir­cuits" Gateway version, when there is a short circuit in one of the two AS-i circuits the other circuit and the Gateway remain operational - the host controller keeps receiving diagnostic information from AS-i, which also provides meaningful assist­ance towards rapid troubleshooting.
The fuse resets itself periodically to check if the error is solved. The measured current value is available as diagnostic information at the field on the display and at the control level.

12.5.6 AS-i Power24V capable

Main menu || SETUP || ASI POWER ||
Gateways for AS-i Power24V have been developed especially for use in small systems. They don‘t need any special AS-i power supply. With a standard 24V power supply a 50 m line lenght and with an AS-i power supply min. 100 m line lenght can be realised.
27.9.2013
Current limiting 3,2A 2
AS-i Power 24V geerdet change
81
Page 82
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Advanced Diagnostics for AS-i Masters
AS-i Power AS-i PWR Supply change

12.5.7 Ethernet diagnostics interface with web server

These devices allow diagnostics for both the Gateway and the AS-i networks (in­cluding Safety technology) over Ethernet without additional software. AS-i net­work can be thus a part of a remote maintenance concept. Morover the configura­tion file are stored on the web server and so they are always within reach.

12.5.8 Transitionless operating mode changes

Main menu || SETUP || MODE CHANGE ||
These devices are able to change the operating mode from projecting mode to the protected operating mode without having to first go to the "offline phase".
This means the Slave outputs are not cleared and the safe Slaves not turned off. Activation and deactivation is set using the PROFINET start parameterization. This function must be explicitly activated; the default setting is “Deactivated.” The setting for activated and deactivated is saved, which means that it remains
set after a "power cycle".
Mode Change
82
Offline Phase yes change
27.9.2013
Page 83
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways

13. Configuration of AS-i/PROFINET Gateways

This section includes information for the configuration of the AS-i 3.0 PROFINET Gateway in a PROFINET network.

13.1 Projecting PROFINET network

The configuration tool needs information about the bus participants for the pro­jecting of a PROFINET network. These information is provided from the manufac­turers of bus participants as "equipment master data" in GSDML files.
During the configuration, the GSDML file must be imported into the PROFINET configuration tool.
The AS-i/PROFINET Gateway appears then in the hardware catalog as:
"PROFINET IO/Other field devices/Gateway/Pepperl+Fuchs AS-interface".
Information!
The device name of the AS-i 3.0 PROFINET-Gateway is: "". Any PROFINET partici­pant will be identified over this name. That means that every PROFINET participant has to become a precise name with the help of AS-i Control Tools.
The name of the gateways is "" per default. This must be changed to the requested name during the projecting!

13.2 Logical slots

13.2.1 Options

The GSD file offers several combinations (several lengths) for transmitting I/O da­ta, the command interface , as well as AS-i 16 bit data. This allows them to be transmitted directly as part of the process data channel.
Up to 30 modules can be configured Possible options:
Length description
16 byte I digital input (slave 0 - 31)
20 byte I digital input (slave 0 - 7b)
32 byte I digital input (slave 0 - 31B)
Information!
Up to four command interfaces can be integrated.
Tab. 13-11.
27.9.2013
83
Page 84
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways
Length description
12 byte I/O command interface
32 byte I/O
34 byte I/O
36 byte I/O
Length description
2 byte … 128 byte I analog input data, dynamic
2 byte … 128 byte O analog output data, dynamic
Length description
2 byte I flags and AS-i detector
Spezific PROFIsafe "special-IDs"
PROFIsafe V2
Allocation PROFIsafe in input and output area of control
Byte n+0 0-7 0-6 0-5 0-4 0-3 0-2 0-1 0-0 (reserviert)
Byte n+1 1-7 1-6 1-5 1-4 1-3 1-2 1-1 1-0
Byte n+2 2-7 2-6 2-5 2-4 2-3 2-2 2-1 2-0
Byte n+3 3-7 3-6 3-5 3-4 3-3 3-2 3-1 3-0
Byte n+4 4-7 4-6 4-5 4-4 4-3 4-2 4-1 4-0
Byte n+5 5-7 5-6 5-5 5-4 5-3 5-2 5-1 5-0
Byte n+6 6-7 6-6 6-5 6-4 6-3 6-2 6-1 6-0
Byte n+7 7-7 7-6 7-5 7-4 7-3 7-2 7-1 7-0
Byte n+8 PROFIsafe internal (status byte / control byte)
Byte n+9 PROFIsafe internal (CRC2)
Byte n+10 PROFIsafe internal (CRC2)
Byte n+11 PROFIsafe internal (CRC2)
Information!
Allocation of input and output signals depends on the configarion in the ASIMON soft­ware.
Tab. 13-12.
Tab. 13-13.
Tab. 13-14.
Tab. 13-15.
84
Information!
Handlng of diagnostic alarms and restarting of Profisafe communication requires use of certain organization modules in the PLC. Please refer in this regard to the user's man­ual for your PLC or the "Quick Start – Simatic Manager Standard Diagnosis" from Pep­perl+Fuchs GmbH.
27.9.2013
Page 85
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways
Information!
Available only with AS-i PROFIsafe Gateways.
EC-flags (16-bit)
EC-flags (16-bit)
7
2
byte 0
byte 1
DA NSE OV EF Pok
OR APF NA CA AAv AAs S0 Cok
DA: Double address
NSE Noise
OV: Overvoltage
EF: Earth falut
Pok: Periphery_Ok
OR: Offline_Ready
APF: APF
NA: Normal_Operation_Active
CA: Configuration_Active AAv: Auto_Address_Available AAs: Auto_Address_Assign
S0: LDS.0
Cok: Config_Ok
6
2
5
2
4
2
3
2
2
2
1
2
0
2
Tab. 13-16.
byte 0
DA 0 = OK
1 = Double address
NSE 0 = OK
1= Noise
OV 0 = OK
1= Overvoltage
EF 0 = OK
1 = Earth falut
Pok 0 = OK
1 = Periphery fault
byte 1
Cok 0 = OK
1 = ’Config Error’
S0 1 = Address ’0’ present
0 = Adresse ’0’ not present
AAs 1 = ’Auto_Address_Assign’ not active
0 = ’Auto_Address_Assign’ active
27.9.2013
85
Page 86
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways
AAv 1 = ’Auto_Address_Available’ active
0 = ’Auto_Address_Available’ not active
CA 0 = ’Configuration_Active’ not active
1 = ’Configuration_Active’ active
NA 0 = ’Normal_Operation_Active’ OK
1 = ’Normal_Operation_Active’ not OK
APF 0 = no APF
1= APF
OR 0 = online
1 = offline

13.2.2 32 bytes digital AS-i I/O data (A and B slaves)

Modul: 32 byte digitale I/O (A+B)
Module ident number 0x80000001
Name 32 byte digitale I/O (A+B)
Details 32 bytes digital AS-i I/O data (A and B slaves)
Category digital I/O data
Submodule:
Submodule ident number 0x00000001
Cycl. Input data
Name data type display as bits length (bytes)
Sensor data OctetString yes 32
Cycl. output data
Name data type display as bits length (bytes)
Actuator data OctetString yes 32
Tab. 13-17.
86
Input and Output Data Image
Byte
0 flags slave 1/1A
1 slave 2/2A slave 3/3A
2 slave 4/4A slave 5/5A
3 slave 6/6A slave 7/7A
4 slave 8/8A slave 9/9A
5 slave 10/10A slave 11/11A
6 slave 12/12A slave 13/13A
7 slave 14/14A slave 15/15A
8 slave 16/16A slave 17/17A
9 slave 18/18A slave 19/19A
7
2
F3 F2 F1 F0
6
2
5
2
4
2
3
2
2
2
1
2
0
2
Tab. 13-18.
27.9.2013
Page 87
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways
Input and Output Data Image
Byte
10 slave 20/20A slave 21/21A
11 slave 22/22A slave 23/23A
12 slave 24/24A slave 25/25A
13 slave 26/26A slave 27/27A
14 slave 28/28A slave 29/29A
15 slave 30/30A slave 31/31A
16 reserved slave 1B
17 slave 2B slave 3B
18 slave 4B slave 5B
19 slave 6B slave 7B
20 slave 8B slave 9B
21 slave 10B slave 11B
22 slave 12B slave 13B
23 slave 14B slave 15B
24 slave 16B slave 17B
25 slave 18B slave 19B
26 slave 20B slave 21B
27 slave 22B slave 23B
28 slave 24B slave 25B
29 slave 26B slave 27B
30 slave 28B slave 29B
31 slave 30B slave 31B
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
2
Tab. 13-18.
Flags
Input data Output data
F0 ConfigError Off-line
F1 APF LOS-master-bit
F2 PeripheryFault ConfigurationMode
F3 ConfigurationActive ProtectedMode
Tab. 13-19.
ConfigError: 0=ConfigOK 1=ConfigError APF: 0=AS-i-Power OK 1=AS-i-Power Fail PeripheryFault: 0=PeripheryOK 1=PeripheryFault ConfigurationActive: 0=ProtectedOperationMode 1=ProjectingMode Off-Line: 0=On-Line 1=Off-Line LOS-master-bit 0=Off-Line by ConfigError
deactivated
27.9.2013
1=Off-Line by ConfigError activated.
87
Page 88
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways

13.2.3 16 bytes digital AS-i I/O data (A slaves only)

Modul: 16 byte digitale I/O (A)
Module ident number 0x80000001
Name 16 byte digitale I/O (A)
Details 16 bytes digital AS-i I/O data (A slaves only)
Category digital I/O data
Submodule:
Submodule ident number 0x00000001
Cycl. Input data
Name data type display as bits length (bytes)
Sensor data OctetString yes 16
Cycl. output data
Name data type display as bits length (bytes)
Actuator data OctetString yes 16
Information!
For information about I/O data image, refer to the table <Input and Output Data Image>.
Tab. 13-20.

13.2.4 16 bytes digital AS-i I/O data (B slaves only)

Modul: 16 byte digital I/O (B)
Module ident number 0x80000001
Name 16 byte digital I/O (B)
Details 16 bytes digital AS-i I/O data (B slaves only)
Category digital I/O data
Submodule:
Submodule ident number 0x00000001
Cycl. Input data
Name data type display as bits length (bytes)
Sensor data OctetString yes 16
Cycl. output data
Name data type display as bits length (bytes)
Actuator data OctetString yes 16
88
Tab. 13-21.
27.9.2013
Page 89
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways
Information!
For information about I/O data image, refer to the table <Input and Output Data Image>.

13.2.5 4 words analog AS-i input data

Modul: 4 words analog E
Module Ident Number
Name 4 words analog in
Details 4 words analog AS-i input data
Category analog inputs
Submodule:
Submodule ident number
Cycl. input data
Name data type display
Analog inputs unsigned16
Analog inputs unsigned16
Analog inputs unsigned16
Analog inputs unsigned16
general parameter (Index: 1 -- length: 1 byte)
Name of parameter data type byte
First analog slave unsigned8 0 1 1 ... 30
0x80000005
0x00000001
as bits
offset
length (bytes)
bit offset
bit length
default value
value range
Tab. 13-22.
27.9.2013
89
Page 90
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways
16-bit value
16-bit value
2152142132122112102928272625242322212
D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0 word 1 channel 1 word 2 channel 2 word 3 channel 3 word 4 channel 4
16-bit data
Information!
A-slaves map the data on channels 1 and 2.
B-slaves map the data on channels 3 and 4.
In addition to the access via the command interfaces, the 16-bit data for or by the slaves with 16-bit value can by exchanged cyclically (profile 7.3., S-7.4, S-6.0, S-
7.5, S-7.A.8, S-7.A.9, S-7.A.A). Competing writing access attemps on 16-bit out­put data will not be blocked by every other. If 16-bit output data for a particular sla­ve are being transmitted both cyclically and acyclically with the command inter­face, the acyclically transmitted values will be overwritten by the cyclically transmitted values.
AS-i 16-bit data can be transmitted in a reserved data area. Therefore accessing 16-bit data is as easy as accessing digital data.
0
90
27.9.2013
Page 91
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways

13.2.6 4 Words analog AS-i output data

Modul: 4 words analog Out
Module ident number
Name 4 words analog out
Details 4 words analog AS-i output data
Category analog outputs
Submodule:
Submodule ident number
Cycl. output data
Name datentyp display
Analog outputs unsigned16
Analog outputs unsigned16
Analog outputs unsigned16
Analog outputs unsigned16
general parameter (Index: 1 -- length: 1 byte)
Name of parameter data type byte
First analog slave unsigned8 0 1 1 ... 30
0x80000006
0x00000001
as bits
offset
length (bytes)
bit offset
bit length
default value
value range
Tab. 13-23.
27.9.2013
91
Page 92
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways

13.2.7 36 bytes command interface

Modul: 36 bytes Cmd If
Module ident number 0x80000002
Name 36 bytes Cmd If
Details 36 bytes command interface
Category command interface
Submodule:
Submodule ident number 0x00000001
Cycl. input data
Name data type display as bits length (bytes)
Command echo unsigned8
Execution status unsigned8
Response data OctetString 34
Cycl. output data
Name data type display as bits length (bytes)
Command echo unsigned8
AS-i circuit unsigned8
Request data OctetString 34
Information!
For information about the structure and the description of the command interface, refer to the manual "AS-i 3.0 Command Interface".
Tab. 13-24.
92
27.9.2013
Page 93
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways

13.2.8 34 bytes command interface

Modul: 34 bytes Cmd If
Module ident number 0x80000002
Name 34 bytes Cmd If
Details 34 bytes command interface
Category command interface
Submodule:
Submodule ident number 0x00000001
Cycl. Input data
Name data type display as bits length (bytes)
Command echo unsigned8
Execution status unsigned8
Response data OctetString 32
Cycl. output data
Name data type display as bits length (bytes)
Command unsigned8
AS-i circuit unsigned8
Request data OctetString 32
Information!
For information about the structure and the description of the command interface, refer to the manual "AS-i 3.0 Command Interface".
Tab. 13-25.
27.9.2013
93
Page 94
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways

13.2.9 12 byte command interface

Modul: 12 bytes Cmd If
Module ident number 0x80000002
Name 12 bytes Cmd If
Details 12 bytes command interface
Category command interface
Submodule:
Submodule ident number 0x00000001
Cycl input data
Name data type display as bits length (bytes)
Command echo unsigned8
Execution status unsigned8
Response data OctetString 10
Cycl. output data
Name data type display as bits length (bytes)
Command unsigned8
AS-i circuit unsigned8
Request data OctetString 10
Information!
For information about the structure and the description of the command interface, refer to the manual "AS-i 3.0 Command Interface".
Tab. 13-26.

13.3 Executing of command interface commands

The command interface cann be accessed via the slot 0, subslot 1, data set 7FFF with "date set read/write". The command interface command is executed when the data set is written. The result can be read in the same data set. This com­mand interface has the same structure as those in the process data.
94
27.9.2013
Page 95
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways

13.4 PROFINET diagnostics

Description of the diagnostic data which are sent via the PROFINET diagnostics channel.

13.4.1 Channel error codes

Slot chan-
nel
0AS-i
Master
AS-i Master
0: circuit 1 1: circuit 2
error
error text help text
type
16 configuration error the actual configuration found on AS-i
17 slave 0 detected there is an AS-i slave with zero
18 no auto address
assignment
19 auto address
assignment availa­ble
20 configuration mode the AS-i master is in configuration
21 no normal operation the AS-i master is performing startup
22 AS-i power fail the AS-i power supply is insufficient
23 off-line the AS-i master doesn't send tele-
24 peripheral fault at least one AS-i slave reports a
25 earth fault the AS-i is short-circuited to ground
26 overvoltage the AS-i is short-circuited to an higher
27 noise the AS-i signals are noisy
28 duplicate address at least two AS-i slaves answers on
does not match the projected configu­ration, or the AS-i master performs startup operations.
address
automatic address assignment would not be possible
as soon as an appropriate slave is connected, its address will be auto­matically assigned
mode
operations
grams on AS-i
peripheral fault, or the AS-i master performs startup operations
potential
the same address
Tab. 13-27.
27.9.2013
95
Page 96
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways
Slot channel code message
1
0 64 incorrect target address
PS
65 invalid target address
66 invalid source address
67 invalid watchdog time
68 submitted SIL-class is too high
69 invalid CRC2-lenght
70 invalid PROFIsafe-version
71 CRC1 error
72 parameter setting inconsistent
75 iParCRC
1. PS: Slot of the PROFIsafe module
Information!
Available only with AS-i/PROFIsafe Gateways.

13.4.2 Manufacturer specific diagnostic

Tab. 13-28.
96
AS-i flags
structure 0xA0: circuit 1 structure 0xA1: circuit 2
Byte bit message
0 0 config error
0 1 slave 0 detected
0 2 automatic addressing not possible
0 3 automatic addressing possible
0 4 configuration mode
0 5 no normal operation
0 6 AS-i power fail
0 7 off-line
1 0 peripheral fault
11 —
12 —
13 —
Tab. 13-29.
27.9.2013
Page 97
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways
Byte bit message
1 4 earth fault
1 5 overvoltage
16 noise
1 7 double addressing
List of configuration errors
structure 0xA2: circuit 1
structure 0xA3: circuit 2
Byte bit message
0 0 slave 0: config error
0 1 slave 1/1A: config error
0 2 slave 2/2A: config error
…… …
3 7 slave 31/31A: config error
40 —
4 1 slave 1B: config error
…… …
7 7 slave 31B: config error
List of peripheral faults
structure 0xA4: circuit 1
structure 0xA5: circuit 2
Byte bit message
00 —
0 1 slave 1/1A: peripheral fault
0 2 slave 2/2A: peripheral fault
…… …
3 7 slave 31/31A: peripheral fault
40 —
4 1 slave 1B: peripheral fault
…… …
7 7 slave 31B: peripheral fault
27.9.2013
Tab. 13-29.
Tab. 13-30.
Tab. 13-31.
97
Page 98
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways
Safety status (single- und A-slaves)
structure 0xA8: circuit 1
structure 0xA9: circuit 2
Byte bit message
0 0 SaW configuration operation
0 1 slave 1/1A: yellow flashing
0 2 slave 2/2A: yellow flashing
…… …
3 7 slave 31/31A: yellow flashing
4 0 SaW monitor error
4 1 slave 1/1A: red flashing
4 2 slave 2/2A: red flashing
…… …
7 7 slave 31/31A: red flashing
Safety status (B-slaves)
structure 0xAA: circuit 1
structure 0xAB: circuit 2
Byte bit message
00 —
0 1 slave 1B: yellow flashing
0 2 slave 2B: yellow flashing
…… …
3 7 slave 31B: yellow flashing
40 —
4 1 slave 1B: red flashing
4 2 slave 2B: red flashing
…… …
7 7 slave 31B: red flashing
Tab. 13-32.
Tab. 13-33.
98
27.9.2013
Page 99
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways

13.4.3 Safety Control/Status

In the fieldbus configuration the designator Safety Control/Status can be added as cyclical data. This is possible both for the integrated Safety Monitor and for 2nd generation Monitors.
Information!
Generation III external Monitors allow a maximum of eight OSSDs to be sent.
The state of the outputs and the message outputs is then inserted as a cyclical in­put datum.
Inputs
byte description 1 Status OSSD 1, color-coded as defined in the table <Coding of status bytes>).
2 Status OSSD 2, color-coded as defined in the table <Coding of status bytes>).
……
n Status OSSD n, color-coded as defined in the table <Coding of status bytes>).
Coding of status bytes
Bit [0 ... 3] state or. color description
00
16
01
16
02
16
03
16
04
16
05
16
06
16
07
16
Bit [6] status or color
0 no device flashing yellow
1 at least one device flash-
Bit [7] status or color
green permanent lighting output on
green flashing delay time is running at stop category 1
yellow permanent lighting start-up/restart-disable active
yellow flashing external test necessary / acknowledge-
ment / start delay active
red permanent lighting output off
red flashing error
grey or off output not projected
reserved
ing yellow
Tab. 13-34.
Tab. 13-35.
27.9.2013
99
Page 100
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways
Coding of status bytes
0 no device flashing red
1 at least one device flash-
ing red
The cyclical output identifier contains the 4 Safety Monitor bits 1.Y1, 1.Y2, 2.Y1 and 2.Y2. The monitoring element “Monitor input” and the start elements “Monitor Start-Monitor Input” and “Activation using Monitor Input” access these data. In contrast, the “Feedback circuit” element always accesses the EDM input.
Outputs
byte description
1 byte from the fieldbus
bit 0: 1.Y1 bit 1: 1.Y2 bit 2: 2.Y1 bit 3: 2.Y2
bit 4 ... 7: reserved
2 reserved
The bits of the output bytes are ORed with the real and the homonymous hard­ware inputs of the device.
Tab. 13-35.
Tab. 13-36.
100
Safety Control Status
Length description
2byteI 1byteO
4byteI 1byteO
6byteI 2byteO
8byteI 2byteO
10 byte I 3byteO
12 byte I 3byteO
14 byte I 4byteO
16 byte I 4byteO
Safety Ctrl/Status (2 OSSD)
Safety Ctrl/Status (4 OSSD)
Safety Ctrl/Status (6 OSSD)
Safety Ctrl/Status (8 OSSD)
Safety Ctrl/Status (10 OSSD)
Safety Ctrl/Status (12 OSSD)
Safety Ctrl/Status (14 OSSD)
Safety Ctrl/Status (16 OSSD)
Tab. 13-37.
27.9.2013
Loading...