Pepperl+Fuchs VBA-4E3A-G20-ZEL/M1L-P2 User Manual

Page 1
VBA-4E3A-G20­ZEL/M1L-P2
AS-Interface Motor Control Module
FACTORY AUTOMATION
MANUAL
Page 2
1 Introduction ................................................................................. 4
2 Declaration of Conformity .......................................................... 5
3 Safety ................................................................................................. 6
3.1
Symbols Relevant to Safety ................................................................. 6
3.2
Intended Use .......................................................................................... 6
3.3
General Safety Information ................................................................... 6
4 Product Description .................................................................... 7
4.1
Use and Application.............................................................................. 7
4.2
Housing .................................................................................................. 8
4.3
Indicators and Operating Controls ...................................................... 9
4.4
Interfaces and Connections ............................................................... 11
5 Installation ................................................................................. 13
5.1
Storage and Transport .............................................................................. 13
5.2
Unpacking ............................................................................................ 13
5.3
Connecting the AS-Interface and Auxiliary Power Flat Cable ........ 13
5.4
Connecting Motors and Sensors ....................................................... 16
6 Commissioning ......................................................................... 17
6.1
AS-Interface Communication ............................................................. 17
6.2
Configuration of the Start/Stop Ramps ............................................. 19
7 Troubleshooting .............................................................................22
3
VBA-4E3A-G20-ZEL/M1L-P2
Page 3
VBA-4E3A-G20-ZEL/M1L-P2
Introduction
1 Introduction
Congratulations
You have chosen a device manufactured by Pepperl+Fuchs. Pepperl+Fuchs develops, produces and distributes electronic sensors and interface modules for the market of automation technology on a worldwide scale.
Please read the operating instructions carefully before installing this device and putting it into operation. The instructions and notes contained in this document will guide you step by step through the installation and commissioning procedures to ensure trouble-free use of this product. By doing so, you:
Guarantee safe operation of thedevice
Can utilize the entire range of device functions
Avoid faulty operation and associated faults
Reduce costs associated with downtime and incidental repairs
Increase the effectiveness and operating efficiency of your plant.
Store these instructions somewhere safe in order to have them available for future work on the device.
After opening the packaging, please ensure that the device is intact and that the package is complete.
Symbols used
The following symbols are used in this manual:
Note!
This symbol draws your attention to important information.
Handling instructions
You will find handling instructions beside this symbol
4
Page 4
VBA-4E3A-G20-ZEL/M1L-P2
Declaration of Conformity
2 Declaration of Conformity
All products were developed and manufactured under observance of the applicable European standards and guidelines.
Note!
A Declaration of Conformity can be requested from the manufacturer.
The product manufacturer, Pepperl+Fuchs GmbH, 68307 Mannheim, has a certified quality assurance system that conforms to ISO 9001.
ISO9001
5
Page 5
VBA-4E3A-G20-ZEL/M1L-P2
Safety
Danger!
This symbol indicates an imminent danger. Non-observance will result in personal injury or death.
Warning!
This symbol indicates a possible fault or danger. Non-observance may cause personal injury or serious property damage.
Caution!
This symbol indicates a possible fault. Non-observance could interrupt the device and any connected systems and plants, or result in
their complete failure.
3
Safety
3.1
Symbols Relevant to Safety
3.2
Intended Use
The AS-Interface motor control module is used to control one or two DC roller Rulmeca RDR BL3 motors. The motor control module has two inputs for connecting three-wire sensors.
Read through these instructions thoroughly. Familiarize yourself with the device before installing, mounting, or operating.
Always operate the device as described in these instructions to ensure that the device and connected systems function correctly. The protection of operating personnel and plant is only guaranteed if the device is operated in accordance with its intended use.
3.3
General Safety Information
Make sure that the flat cables engage completely in the flat cable guide, to ensure a complete seal and secure contact.
During operation, make sure that connectors are not disconnected or inserted, and the flat cable guide is not opened. This could inadvertently start motors.
Only instructed specialist staff may operate the device in accordance with the operating manual.
User modification and or repair are dangerous and will void the warranty and exclude the manufacturer from any liability. If serious faults occur, stop using the device. Secure the device against inadvertent operation. In the event of repairs, return the device to your local Pepperl+Fuchs representative or salesoffice.
The connection of the device and maintenance work when live may only be carried out by a qualified electrical specialist.
The operating company bears responsibility for observing locally applicable safety regulations. Store the not used device in the original packaging. This offers the device optimal protection
against impact and moisture. Ensure that the ambient conditions comply with regulations.
Note! Disposal
Electronic waste is hazardous waste. When disposing of the equipment, observe the current statutory requirements in the respective country of use, as well as local regulations.
6
Page 6
VBA-4E3A-G20-ZEL/M1L-P2
Product Description
4
Product Description
4.1
Use and Application
The VBA-4E3A-G20-ZEL/M1L-P2 motor control module is an AS-Interface connection module for controlling one or two DC roller motors. The module is optimized for type Rulmeca RDR BL3 motors.
To record statuses in the field environment, the module has two inputs for three-wire sensors with positive-switching output (PNP) or for mechanical contacts. The input characteristic of the inputs corresponds to type 1 according to EN 61131-2.
The motors and the sensors are supplied with power via external auxiliary power. This auxiliary power is supplied to the AS-Interface flat cable of the motor control module via a second flat cable.
The permissible auxiliary power is 18 V ...... 30 V.
The sensor power supply may be loaded, in total, with 500 mA.
For each motor, a maximum current load of 5 A is permitted.
Figure 4.1 VBA-4E3A-G20-ZEL/M1L-P2 motor control module
7
Page 7
VBA-4E3A-G20-ZEL/M1L-P2
Product Description
Essential function and application characteristics of the motor control module are:
Compact housing for direct mounting in support profiles or cable ducts
Connection of the motors/sensors via cable outputs with M8 connectors
Insulation piercing technology with gold-plated contact pins for contacting the AS­Interface flat cable
Function displays for the bus, external auxiliary power, status information, inputs, and outputs
Communication monitoring
Configurable start/stop ramps for motorcontrol
Supply of the connected components from the external auxiliary power
4.2
Housing
The housing is made entirely of plastic, with the exception of the hinge pins for the hinged cable guide.
The main components are
A mounting base with electronics encapsulated in casting resin
A folding guide cage as a cable guide for the AS-Interface flat cable.
Figure 4.2 Housing dimensions
8
15
Ø 8
27.5
120
27.5
54
Page 8
VBA-4E3A-G20-ZEL/M1L-P2
Product Description
4.3
Indicators and Operating Controls
Figure 4.3 Status indications on the motor controlmodule.
The operating status of the motor control module is displayed via 12 LEDs.
Note! Additional Flashing Codes during Module Configuration
The following status information relates only to the normal mode of the motor control module. If you set the motor control module to configuration mode for parameterization, this is indicated by multiple LEDs flashing. Details can be found in the "Commissioning" chapter.
Status Indication for Start/Stop Ramps
Once the AUX external auxiliary power has been switched on, the motor control module first shows the number of the stored start/stop ramp. For ramps 1 to 7, the ERR2, IN1, and IN2 LEDs indicate a numerical value in binary code by short flashing. ERR2 LED is the highest value bit. The LEDs flash five times for 50 ms each time.
If no start/stop ramp is stored, the six MOT1 ... IN2 LEDs flash. For more information on the start/stop ramps, see "Configuration of Start/Stop Ramps" in the
"Commissioning" chapter.
Start/Stop Ramp Display
Ramp no.
LED MOT1
LED MOT2
LED ERR1
LED ERR2
IN1 LED
IN2 LED
0 Flashes
Flashes
Flashes
Flashes
Flashes
Flashes
1 Off
Off
Off
Off
Off
Flashes
2 Off
Off
Off
Off
Flashes
Off
3 Off
Off
Off
Off
Flashes
Flashes
4 Off
Off
Off
Flashes
Off
Off 5
Off
Off
Off
Flashes
Off
Flashes
6 Off
Off
Off
Flashes
Flashes
Off
7 Off
Off
Off
Flashes
Flashes
Flashes
9
MOT2
MOT1
IN2
IN1
AUX BLACK ASI YELLOW
PWR
FAULT
AUX
FUSE1
FUSE2
DIR
MOT1
MOT2
ERR1
ERR2
IN1
IN2
Page 9
VBA-4E3A-G20-ZEL/M1L-P2
Product Description
Status Indications for AS-Interface and Power Supply
The PWR LED and the FAULT LED show the AS-Interface operating status. Various error statuses are displayed as a collective error message "Peripheral fault."
Display of the AS-Interface Operating Statuses
LED PWR Green
LED FAULT Red Status
On
Off
AS-Interface power supply is OK
Flashes
On
Address = 0
On
On
AS-Interface communication error
Flashes
Flashes
Peripheral fault, collective error message for:
AUX external auxiliary power is missing or is inverted
Overload of the sensor supply (IN+, IN-)
Overload of the speed signal SPEED
Off
Off
AS-Interface voltage missing
The AUX LED shows the status of the AUX external auxiliary power.
Display of the AUX External Auxiliary Power
AUX LED Red/green
Status
Green on
AUX external auxiliary power is OK
Red on
AUX external auxiliary power is inverted
Off
AUX external auxiliary power voltage is missing
Status Indications for Motor Fuses
The FUSE1 LED for motor 1 and the FUSE2 LED for motor 2 show the status of the power supplied to the motors.
Motor Fuse Indicator
LED FUSE1 LED FUSE2 Green
Status
On
Power supply for motor is OK
Off
Power supply for motor is missing:
Fuse is faulty or
AUX external auxiliary power is not connected
Note! Motor Fuses Are Safety Fuses
Fuses with a 5 A rated current act as protection against short circuits. Each motor is safeguarded with a fuse. The fuses are not interchangeable. If a fuse is faulty, the module must be replaced.
10
Page 10
VBA-4E3A-G20-ZEL/M1L-P2
Product Description
Status Indications for Motors MOT1, MOT2
The MOT1, MOT2, ERR 1, ERR2, and DIR LEDs display information about the operating statuses of the respective motor.
Motor Activity Indicators
LED MOT1 LED MOT2 Yellow
Status
On
Motor is in operation
Off
Motor is off
Motor Fault Indicators
LED ERR1 LED ERR2 Yellow
Status
On
Motor fault is present:
Fault output of the motor is active or
No motor is connected or
Fuse is faulty
Off
No motor fault
Motor Direction of Rotation Indicator
LED DIR Yellow
Status
On
Direction of rotation to the right (in accordance with RDR BL3,)
Off
Direction of rotation to the left (in accordance with RDR BL3,)
Status Indications for IN1, IN2 Sensors
The IN1 LED for input 1 and IN2 LED for input 2 show the switching statuses of the inputs.
Display of the Inputs
IN1 LED IN2 LED Yellow
Status
On
Input is set (high)
Off
Input is not set (low)
4.4
Interfaces and Connections
Flat Cable Specification
The AS-Interface motor control module is compatible with the AS-Interface standard cable in accordance with IEC 62026-2.
11
Page 11
VBA-4E3A-G20-ZEL/M1L-P2
Product Description
The following AS-Interface cable types are available with UL Recognized approval:
AS-Interface Cable Types with UL Approval
Pepperl+Fuchs Designation
Color
Sheathing material/ wire insulation
Cross-section
UL "Cable Style"
Approval
VAZ-FK-R-YE
Yellow
TPE/TPE
2x 1.5 mm
2103
VAZ-FK-R-BK
Black
TPE/TPE
2x 1.5 mm
2103
VAZ-FK-PUR-YE
Yellow
PUR(TMPU)/TPM
2x 1.5 mm
20549
VAZ-FK-PUR-BK
Black
PUR(TMPU)/TPM
2x 1.5 mm
20549
Input/Output Connections
The sensors and motors are connected to the motor control module via cables with round M8 connectors:
Sensors: socket, four-pin
Motors: socket, five-pin
The cable length is 1m.
Motor Supply from Auxiliary Power
The motors are supplied with power directly from the AUX external auxiliary power and this cannot be switched. The voltage is always on contacts 1 and 3 of the five-pin M8 connector.
Connector Assignment
Connection for
Connectors
Plug type/plug assignment
Sensor
4
2
Input: LF004-GS1-A in accordance with IEC/EN 61076-2-104 M8, 4-pin, socket, cap nut, coding A
Matching female connector: LM004-Gx1-A or similar
1: IN+ sensor supply 2: Not used 3: IN- sensor supply 4: IN input
3 1
Motor
4
2
Motor: NF005-SS1-B in accordance with
IEC/EN 61076-2-104
M8, 5-pin, socket, snap lock, coding B Matching female connector: NM005-Sx1-B
or similar 1: MOT+ motor supply
2: DIR direction of rotation 3: MOT- (=AUX-) motor supply 4: ERROR motor fault 5: SPEED velocity signal
3 1
5
12
Page 12
VBA-4E3A-G20-ZEL/M1L-P2
Installation
5
Installation
5.1
Storage and Transport
For storage and transport purposes, package the unit using shockproof packaging material and protect it against moisture. The best method of protection is to package the unit using the original packaging. Furthermore, ensure that the ambient conditions are within allowable range.
5.2
Unpacking
Check the product for damage while unpacking. In the event of damage to the product, inform the post office or parcel service and notify the supplier.
Retain the original packaging in case the device must be stored or shipped again at a later date.
Should you have any questions, please direct them to Pepperl+Fuchs.
5.3
Connecting the AS-Interface and Auxiliary Power Flat Cable
The motor control module is connected to the AS-Interface network and the AUX auxiliary power via the AS-Interface flat cable. The yellow flat cable is for communication and the black flat cable is for the AUX auxiliary power. The permissible auxiliary power is 18 V ... 30 V.
Contact between the motor control module and flat cables is established via two metal mandrels and using insulation piercing technology. The flat cables are routed through a hinged cable guide. When closed, the cable guide is locked using a locking bracket and can be opened again without the needsfor tools.
The profiled flat cables have a narrow upper side (with a visibly offset profile edge) and a wide under side (profile edge not visible). The cable guide allows the flat cables to be inserted on both sides, for flexible connection of flat cables already laid in cable ducts. However, you must make sure that the profile edge always points to the motor control module. Mechanical reverse polarity protection prevents complete closure of the cable guide if the flat cable is inserted incorrectly.
13
Caution!
If one is inserted incorrectly, the motor control module will not work. If the flat cable is inserted in the cable guide in the wrong direction, the voltage is inverted. The
motor control module will not work. However, internal electrical reverse polarity protection protects it against breakage.
Page 13
VBA-4E3A-G20-ZEL/M1L-P2
Installation
4 3 5 2
AUX
YELLOW
BLACK
1
Connecting Flat Cables on the Narrow Side
The profile edge is visible from above.
1.
Open the cable guide. To do this, push the locking bracket (1) slightly to one side.
2.
Insert the black AUX flat cable with the profile edge (4) to the motor control module into the lower guide (see the module tag "Black AUX").
3.
Insert the yellow AS-Interface flat cable with the profile edge (3) to the motor control module into the upper guide (see the module tag "YELLOW").
4.
Make sure that the profile edges of both flat cables are under the respective reverse polarity protection (2, 5).
5.
Close the cable guide. It must engage securely in the locking bracket (1).
The metal mandrels contact the strands in the flat cables.
Figure 5.1 Connecting Flat Cables on the Narrow Side
14
Page 14
VBA-4E3A-G20-ZEL/M1L-P2
Installation
Connecting Flat Cables on the Wide Side
The profile edge is not visible from above. For orientation purposes in the figure below, the edge is shown as a hidden edge drawn with a dotted line.
1.
Open the cable guide. To do this, push the locking bracket (1) slightly to one side.
2.
Insert the black AUX flat cable with the profile edge (3) to the motor control module into the lower guide (see the module tag "Black AUX").
3.
Insert the yellow AS-Interface flat cable with the profile edge (2) to the motor control module into the upper guide (see the module tag "YELLOW").
4.
Close the cable guide. It must engage securely in the locking bracket (1).
The profile edges (2, 3) of both flat cables are above the two reverse polarity protections.
The metal mandrels contact the strands in the flat cables.
Figure 5.2 Connecting flat cables on the wide side (profile edge as dotted line)
15
2 3
AUX
YELLOW
BLACK
1
Page 15
VBA-4E3A-G20-ZEL/M1L-P2
Installation
Flat Cable Inserted Incorrectly
The figure below shows an incorrectly inserted flat cable. The profile edge (2) does not point to the motor control module; the flat cable is therefore inserted with reverse polarity. The flat cable is located on the reverse polarity protection (1) with a curvature, which means that the cable guide cannot be closed completely (mechanical reverse polarity protection).
Figure 5.3 Flat cable inserted incorrectly (profile edge as dotted line)
5.4
Connecting Motors and Sensors
Figure 5.4 Connection wiring diagram for motors and sensors
16
1
2
AUX+
AUX-
AUX
5
MOT
1 3
M
4 2
MOT1 & MOT2
MOT+ DIR ERROR SPEED MOT-
1 2 4 5 3 ERR
FAULT
FUSE
DIR
PWR
IN
IN-
(n.c.)
3
2
AS-Interface -
2 1
4 3
IN1 & IN2
1
IN+
4
IN
AS-Interface +
Page 16
VBA-4E3A-G20-ZEL/M1L-P2
Commissioning
6
Commissioning
6.1
AS-Interface Communication
Assigning the AS-Interface Data Bits
Four data bits are available for communication to take place between the motor control module and the master. Three data bits are available for controlling the motors.
The following designations apply below:
DI0...DI3 for AS-Interface input data (motor control module to master)
DO0...DO2 for AS-Interface output data (master to motor control module)
DI0...DI03 Motor Control Module to Master
AS-Interface data bit
Input DI
DI0
Fault at output MOT1
DI1
Fault at output MOT2
DI2
Switching status input IN1
DI3
Switching status input IN2
DO0...DO2 Master to Motor Control Module
AS-Interface data bit
Output DO
DO0
Start/stop motor 1
DO1
Start/stop motor 2
DO2
Direction of rotation of motor 1 and motor 2
AS-Interface Communication Monitoring
The motor control module has a watchdog function. If there has been no communication with the master for more than 40 ms, the motor control module sets the output data DO0...DO2 to logical 0.
Starting/Stopping Motors (D00, D01)
You can start or stop the motors separately via the DO0 and DO1 bits. To start motors, you must set the corresponding data bit to logical 1. Via the joint SPEED control signal, the motor control module actuates the respective motor switched on with an analog voltage value. The SPEED control signal is released only when DO0 or DO1 data bit is set for the relevant output. The analog voltage value corresponds to the set speed.
DO0, DO1 Data Bits
Data bit
Status
Function
LED MOT1/2
DO0 1 Start motor 1 (SPEED > 1.5 V)
MOT1: on
0 Stop motor 1 (SPEED < 1.5 V)
MOT1: off
DO1 1 Start motor 2 (SPEED > 1.5 V)
MOT2: on
0 Stop motor 2 (SPEED < 1.5 V)
MOT2: off
Switching the Motor Direction of Rotation (DO2)
You can switch the direction of rotation of the motors using the DIR control signal. The direction of rotation signal is valid for both motors together. For control purposes, you must parameterize the DO2 data bit accordingly.
Logical 0, according to RDR BL3, corresponds to direction of rotation to the left. The motor control module switches the DIR control signal to high impedance.
17
Page 17
VBA-4E3A-G20-ZEL/M1L-P2
Commissioning
Logical 1, according to RDR BL3, corresponds to direction of rotation to the right. The motor control module switches the DIR control signal to AUX level.
DO2 Data Bit
Data bit
Status
Function
DIR direction of rotation signal
LED DIR
DO2
0 Direction of rotation left
High impedance, approx. 0 V
Off
1 Direction of rotation right
(U
AUX
- 1) V
At idle speed, Ri=5.6 k
On
Adjusting the Motor Speed (P0...P2)
You can adjust the speed for both motors simultaneously only via the P0...P2 parameter bits. To do this, you must parameterize one of eight predefined speed values. The speed values correspond to analog voltagevalues.
If the master does not change the parameter bits when the AS-Interface network is switched on, the eighth speed value (7.26 V) is set per default on the motor control module.
The motor control module issues the set control voltage to the motors via the SPEED control signal as soon as the motors are switched on via DO0 and DO1 data bits (logical 1). The control voltage is readjusted by the motor control module and is therefore independent of the load within certain limits. If the control limits are exceeded due to an excessive load, the motor control module issues a peripheral fault.
Parameter Bits P0...P2
P2 P1 P0
DO0 (MOT1) or DO1 (MOT2)
Speed signal SPEED (Tolerance range)
LED MOT1 or MOT2
x x x 0 < 1.5 V
Off
0 0 0 1 3.96 V (3.92 V .... 4.00 V)
On
0 0 1 1 4.78 V (4.73 V .... 4.83 V)
On
0 1 0 1 5.61 V (5.55 V .... 5.67 V)
On
0 1 1 1 6.44 V (6.38 V .... 6.50 V)
On
1 0 0 1 8.50 V (8.42 V .... 8.59 V)
On 1 0 1 1
9.63 V (9.53 V .... 9.73 V)
On 1 1 0 1
10.00 V (9.90 V .... 10.10 V)
On
1 1 1 1
7.26 V (7.19 V .... 7.33 V)
Basic setting
On
Reporting a Motor Fault (DI0, DI1)
The motor control module records a motor fault via the ERROR status signal. The motor control module reports faults to the master using DI0 (motor 1) and DI1 (motor 2) data bits. In the event of a motor fault, the motor control module sets the respective DI0 or DI1 data bit to logical "1." This status is set if no motor is connected or the motor is not supplied with power if a fuse in the motor control module is defective.
18
Page 18
VBA-4E3A-G20-ZEL/M1L-P2
Commissioning
DI0, DI1 Data Bits
Data bit
Status
Motor error status
Motor error signal ERROR
LED ERR1/2
DI0 0
No fault in motor 1
U
ERROR
1.2 V, I
ERROR
40 A
ERR1: off
1
Fault in motor 1
Or motor 1 is not connected
Or fuse is defective
High impedance
ERR1: on
DI1 0
No fault in motor 2
U
ERROR
1.2 V, I
ERROR
40 A
ERR2: off
1
Fault in motor 2
Or motor 2 is not connected
Or fuse is defective
High impedance
ERR2: on
Status of the Sensor Inputs (DI2, DI3)
The motor control module transfers the switching statuses of the IN1 and IN2 inputs to the master using the DI2 (IN1) and DI3 (IN3) data bits.
There is a filter downstream of the inputs that suppresses pulses 2 ms.
DI2, DI3 Data Bits
Data bit
Status
Input switching status
LED IN1/2
DI2 0
Unattenuated, I
IN
0.5 mA
IN1: off
1
Attenuated, I
IN
2.0 mA
IN1: on
DI3 0
Unattenuated, I
IN
0.5 mA
IN2: off
1
Attenuated, I
IN
2.0 mA
IN2: on
6.2
Configuration of the Start/Stop Ramps
Overview
To control the acceleration and to stop the motors, you can set one of eight defined start/stop ramps for the speed signal SPEED. These ramps always apply to both motors simultaneously. The ramp duration corresponds to the time from stopping to reaching the maximum speed or from the maximum speed up to stopping. The inclines of the ramps are constant for each of the eight ramps and independent of the set speed. The reference value for all ramps is the speed signal SPEED = 10 V. For a lower parameterized speed, the ramp duration is proportionally shorter.
Predefined Start/Stop Ramps
Ramp no.
Ramp duration
0 No ramp (default setting)
1 50 ms
2 100 ms
3 200 ms
4 300 ms
5 500 ms
6 1000 ms
7 1500 ms
19
Page 19
VBA-4E3A-G20-ZEL/M1L-P2
Commissioning
The ramp is not effective if the direction of rotation signal is switched when the motor is active. In this case, the direction of rotation is reversed immediately.
Note! Default Setting on Delivery
On delivery, ramp no. 0 (no ramp) is the default setting.
Configuring Start/Stop Ramps
To adjust a start/stop ramp, you must change the motor control module to configuration mode. The motor control module stores a new ramp set in the internal nonvolatile memory. This ramp is activated automatically every time the motor is switched on. You can reconfigure a ramp as often as required.
A prerequisite for configuration is that the flat cables for the AS-Interface and AUX are connected. Communication must already be taking place between the master and motor control module.
Note! Configuration Mode Display via LEDs
If the motor control module is in configuration mode, the MOT1, MOT2, ERR1, ERR2, IN1, IN2 LEDs flash simultaneously with a frequency of approx. 2 Hz.
The configuration sequence consists of nine steps. Defined data and parameter values are transmitted between the master and the motor control module via the DO0...DO2, DI0 ... DI3 data bits andthe P0 .. P2 parameter bits. The master must keep the data and parameter bits constant for at least 10 ms for each step. Longer intervals are possible as long as a period of 10 s is not exceeded for steps one to six.
The configuration of a new start/stop ramp runs in the following phases:
In steps one to six, the master sends parameter values to the motor control module to activate configuration mode (max. 10 s). DO0.. DO2 must have the value "4" in each step.
If the parameter sequence was correct, the motor control module responds to the master via DI0.. DI2 on the last parameter value with "C
hex
." This response indicates that
configuration mode is activated. The six MOT1 ..IN1 LEDs flash.
In step seven, the master sends the selected ramp no. to the motor control module via DO0 ..DO2.
In step eight, the master sends the parameter value "4" to the motor control module via P0 .. P2. The motor control module stores the ramp number in the nonvolatile memory. It responds to the master with "A
Hex
" via DI0 ..DI2.
In step nine, the master exits configuration mode. The master sends data value "4" via DO0...DO2 and data value "7" via P0.. P2. The motor control module switches to normal mode. The six MOT1 ..IN1 LEDs stop flashing.
Note! Sequence for Command Transmission
For each step, you generally send the data value via DO0.. D02 first and then the parameter value P0.. P2. The following table shows the contexts of communication between the master and motor control module. The value "x" represents any of the values in the table.
20
Page 20
VBA-4E3A-G20-ZEL/M1L-P2
Commissioning
Sequence for Configuring a Start/Stop Ramp
Send the following data values and parameter values to the motor control module:
1.
In accordance with steps one to six, for each step send the data value "4" via DO0...DO2 and then via P0...P2, a value of the parameter string 3,1,6,3,1,6 one after the other.
2.
If configuration mode is active, send the required ramp number via DO0...DO2 and the parameter value "6" via P0...P2 as step seven.
3.
As step eight, send the ramp number again via DO0...DO2 and parameter value "4" via P0...P2.
4.
As step nine, send data value "0" via DO0...DO2 and parameter value "7" via P0...P2.
The motor control module has stored the new start/stop ramp and switched back to
normal mode.
Contexts of Module Communication
Step
DO0...DO2
P0...P2
DI0 .. DI3
Comment
4
x x Motor control module in normal mode
1 4 3 x Start activation sequence for configuration mode
2 4 1 x
3 4 6 x
4 4 3 x
5 4 1 x
6 4 6
C
hex
End activation sequence for configuration mode. Motor control module responds with C
hex
if
configuration mode is OK.
7 Ramp no.
6
C
hex
Transfer of the ramp number to the motor control module
8 Ramp no.
4
A
hex
The ramp is stored
9 0 7 x Motor control module switches back to normal mode
Troubleshooting during Configuration
The following table describes the behavior of the motor control module if a fault occurs during the nine-step configuration process.
Fault Scenarios
Step
Possible fault
Motor control module reaction
1 to 6
Incorrect data or parameter values or
steps 1 to 6 take longer than 10 s
Motor control module remains in normal mode
7 or 8
Incorrect data or parameter values
Motor control module responds with "E
hex
" via DI0 ... DI3 and remains in configuration mode.
The motor control module switches to normal mode only when the master sends "0" via DO0 ... DO2 and "7" via P0 ... P2.
If "0" or "7" has already been set by the master in one of these steps, the motor control module switches to normal mode immediately without sending a response. The stored ramp is not changed.
21
Page 21
VBA-4E3A-G20-ZEL/M1L-P2
Troubleshooting
7
Troubleshooting
Fault Information and Remedy
Fault
LED display
Possible cause
Remedy
No data communication withAS-Interface master
PWR off
AS-Interface voltage is missing or has reverse polarity
Check AS-Interface wiring
PWR flashes and FAULT on
Module address is 0
Program module address PWR on and
AS-Interface Master is not switched on (offline) or
There is duplicate addressing
Switch on the AS-Interface master
FAULT on
or Check the addresses of all modules
on the AS-Interface segment
Motors will not start
AUX off
AUX external power supply is missing
Check AUX voltage and AUX flat cable
AUX red on
AUX external power supply is inverted
Correct the polarity of the AUX flat cable in the cable guide
AUX green on and FUSE1 (motor 1) and/or FUSE2 (motor 2) off
Motor fuse is faulty due to overloading of the motor supply
Replace the motor control module (cannot be repaired) and remove the cause of the overload before starting the motor again
Note: Fault information via AS­Interface via DI0 (motor 1) data bit and/or DI1 (motor 2) data bit and ERR1 LED on and/or ERR2 LED on
PWR and FAULT flash alternately
Peripheral fault "Overload speed signal SPEED": Motor or motor cable or motor control module is faulty
Replace motor or motor control module
FUSE1 (motor 1) on and/or FUSE2 (motor 2) on and ERR1 (motor 1) on and/or ERR2 (motor 2) on
Motor fault: motor is blocked or faulty
Remove the motor blockage or replace the motor
Note: Fault information via AS­Interface via DI0 (motor 1) data bit and/or DI1 (motor 2) data bit
Sensors or IN1, IN2 inputs not working
AUX off
AUX external power supply is missing
Check AUX voltage and AUX flat cable
AUX red on
AUX external power supply is inverted
Correct the polarity of the AUX flat cable in the cable guide
PWR and FAULT flash alternately
Periphery fault: overload on sensor supply
Check the sensors and eliminate the overload
22
Page 22
FACTORY AUTOMATION – SENSING YOUR NEEDS
Loading...