Ultrasonic sensor UC500-L2-U-V15
Technical data
General specifications
Sensing range 35 ... 500 mm
Adjustment range 50 ... 500 mm
Dead band 0 ... 35 mm
Standard target plate 100 mm x 100 mm
Transducer frequency approx. 380 kHz
Model Number
UC500-L2-U-V15
Single head system
Features
• Sensor head bidirectional and rotatable
• Function indicators visible from all
directions
• Quick mounting bracket
• Selectable sound lobe width
• Programmable
Diagrams
Characteristic response curve
Distance Y [mm]
250
flat surface 100 mm x 100 mm
200
150
100
50
0
-50
-100
-150
-200
0 200 400 600 800 1000 1200
Y
X
round bar, Ø 25 mm
Distance X [mm]
wide sound lobe
narrow sound lobe
Response delay minimum : 20 ms
Indicators/operating means
LED green Operating display
LED yellow object in evaluation range
LED red error
Electrical specifications
Operating voltage U
No-load supply current I
Interface
B
0
Interface type Serial interface (programming adapter required)
Input/Output
Input/output type 1 synchronization connection, bidirectional
0 Level 0 ... 1 V
1 Level 4 V ... U
Input impedance > 12 kΩ
Output rated operating current < 12 mA
Pulse length 0.5 ... 300 ms (level 1)
Pulse interval ≥ 14 ms (level 0)
Synchronization frequency
Common mode operation ≤ 70 Hz
Multiplex operation ≤ 90 Hz / n , n = number of sensors , n ≤ 10
Input
Input type 1 program input
Level (evaluation limit 1) 0 ... 1 V
Level (evaluation limit 2) 4 V ... U
Input impedance > 12 kΩ
Pulse length 2 ... 10 s
Output
Output type 1 analog output 0 ... 10 V
Resolution evaluation range [mm]/4000, but ≥ 0.05 mm
Deviation of the characteristic curve ≤ 0.2 % of full-scale value
Repeat accuracy ≤ 0.1 % of full-scale value
Load impedance ≥ 500 Ohm
Temperature influence ≤ 1.5 % of full-scale value
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Connection type Connector M12 x 1 , 5-pin
Degree of protection IP67
Material
Housing PA-GF35
Transducer epoxy resin/hollow glass sphere mixture; polyurethane foam
Mass 115 g
Factory settings
Output evaluation limit A1: 50 mm
Beam width wide
Evaluation procedure low-pass behavior
General information
Supplementary information Switch settings of the external programming adapter:
Compliance with standards and
directives
Standard conformity
Standards EN 60947-5-2:2007 + A1:2012
Ex works settings: 145 ms
12 ... 30 V DC , ripple 10 %
SS
≤ 50 mA
9600 BPS, no parity, 8 data bits, 1 stop bit
B
(factory setting: n = 5 )
B
evaluation limit A2: 500 mm
output function: rising ramp
"output load": pull-down
"output logic": noninv
IEC 60947-5-2:2007 + A1:2012
EN 60947-5-7:2003
IEC 60947-5-7:2003
Release date: 2016-02-12 15:24 Date of issue: 2016-02-12 277754_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Approvals and certificates
UL approval cULus Listed, General Purpose
CSA approval cCSAus Listed, General Purpose
CCC approval CCC approval / marking not required for products rated
≤36 V
1

Ultrasonic sensor UC500-L2-U-V15
Dimensions
LED yeLED gnLED ye
40
3
LED gn
28
7
67
40
M12 x 1
Electrical Connection
Pinout
40
T
out pwr
5.5
60
1
5
2
4
3
2
+U
B
Synchronization
Program input
Analog output
-U
B
1
5
4
20
30
ø 5.546
3
Wire colors in accordance with EN 60947-5-2
1 BN
2 WH
3 BU
4 BK
5 GY
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
(brown)
(white)
(blue)
(black)
(gray)
Release date: 2016-02-12 15:24 Date of issue: 2016-02-12 277754_eng.xml
2