Ultrasonic sensor UC500-F65-UE2R2-V15
Technical data
General specifications
Sensing range 60 ... 500 mm
Adjustment range 60 ... 500 mm
Dead band 0 ... 60 mm
Standard target plate 10 mm x 10 mm
Transducer frequency approx. 300 kHz
Nominal ratings
Model Number
UC500-F65-UE2R2-V15
Features
• Level indication
• 1 analog output, 0-10 V voltage
source
•1 switch output
• Programmable by means of Interface (see accessories) and SONPROG
• Synchronization options
• Temperature compensation
Diagrams
Characteristic response curve
Distance Y [mm]
150
125
100
75
50
25
0
-25
-50
-75
-100
-125
-150
0 100 200 300 400 500 600 700 800
Y
Curve 1: flat surface 100 mm x 100 mm
Curve 2: round bar, Ø 25 mm
2
X
1
Distance X [mm]
Time delay before availability t
Limit data
v
Permissible cable length max. 300 m
Indicators/operating means
LED green Power on
LED yellow solid: switching state switch output
Electrical specifications
Rated operating voltage U
Operating voltage U
e
B
Ripple ≤ 10 %
No-load supply current I
Input
0
Input type 1 Function input
Input voltage ≤ Operating voltage
Level low level : 0 ... 3 V
Switching output
Output type 1 switch output PNP, NO
Default setting 60 ... 500 mm
Operating current I
Voltage drop ≤ 3 V
L
Analog output
Output type 1 voltage output 0 ... 10 V , rising ramp
Default setting 60 ... 500 mm
Linearity error ≤ 1.5 %
Load resistor ≤ 2 kΩ
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Shock resistance 30 g , 11 ms period
Vibration resistance 10 ... 55 Hz , Amplitude ± 1 mm
Mechanical specifications
Connection type Connector M12 x 1 , 5-pin
Degree of protection IP65
Material
Housing PBT
Transducer epoxy resin/hollow glass sphere mixture; polyurethane foam
Installation position any position
Mass 500 g
Compliance with standards and
directives
Standard conformity
Standards EN 60947-5-2:2007 + A1:2012
Approvals and certificates
UL approval cULus Listed, General Purpose
CSA approval cCSAus Listed, General Purpose
CCC approval CCC approval / marking not required for products rated
250 ms
flashing: misadjustment
24 V DC
15 ... 30 V (including ripple)
In supply voltage interval 15 ... 20 V sensitivity reduced to
20% ... 0%
≤ 60 mA
high level : ≥ 15 V
≤ 300 mA , short-circuit/overload protected
IEC 60947-5-2:2007 + A1:2012
EN 60947-5-7:2003
IEC 60947-5-7:2003
≤36 V
Release date: 2016-02-16 08:26 Date of issue: 2016-02-16 235147_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
1

Ultrasonic sensor UC500-F65-UE2R2-V15
Dimensions
Additional Information
Function of the outputs
2 x ø8.8
6
30
17
10
2 x ø5.5
ø30
54
64.4
4612
125
Sensor
Sensor
Sensor
Switching
output
1
0
Analog-
output
S
min
A
E
S
max
max.
min.
Electrical Connection
Pinout
Wire colors in accordance with EN 60947-5-2
1 BN
2 WH
3 BU
4 BK
5 GY
1
2
4
5
3
2
+U
B
XI
Switch output
Analog output
-U
B
1
3
(brown)
(white)
(blue)
(black)
(gray)
5
4
Release date: 2016-02-16 08:26 Date of issue: 2016-02-16 235147_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2

Ultrasonic sensor UC500-F65-UE2R2-V15
Accessories
V15-G-2M-PUR
Female cordset, M12, 5-pin, PUR cable
V15-G-2M-PVC
Female cordset, M12, 5-pin, PVC cable
V15-W-2M-PVC
Female cordset, M12, 5-pin, PVC cable
3RX4000-PF
PC interface
Application ranges
The design and function of this ultrasonic sensor make it ideal for filling level applications in small containers. The device has a switch output and an analogue output. With
the switch output, a specific filling level in a tank can be signalled directly. The analogue output represents the current level as an analogue output variable.
Assembly and connection
All components are contained in an encapsulated housing. The ultrasonic converter is in a slightly recessed position in the housing. The integrated circumferential seal allows
the sensor to be used directly as a closure with integrated filling level measurement. The tank opening must have a diameter of 26 mm. It can be mounted on the tank using
2 M5 screws. The electrical connection is based on a 5-pin device connector, M12 x 1. The connections are protected against reverse polarity, short circuits and overloads.
Shielded cables are recommended if there is electrical interference.
Setting
As delivered, the switch-on and switch-off point, the measuring range limits and the averaging are fixed (see Technical data). They can subsequently be adapted to the application via SONPROG using the interface (see Accessories).
SONPROG
The following parameters can be changed via SONPROG:
• Measuring range limits S
• Switch-on and switch-off points (A, E)
• Blind zone
• Averaging
Special programming options are available on request.
Operation
The filling level of a container is detected within the detection range. When the filling level reaches the switch-on or switch-off point (E or A), the switch output reacts according
to its setting. The switching statuses of the switch output are signalled by the yellow LEDs. If the level is between the switching points A and E, the output is active.
Filling levels between the measuring range limits (S
minimum value at filling level S
Objects in the blind zone cause cause false signals. Install in such a way that the filling level cannot enter the blind zone.
Function input XI
The sensor is placed in standby mode by connecting a low level at the function input XI (blocked release). The sensors then performs no measurements. The outputs retain
the most recent status. As soon as function input XI is disconnected from the low level or a high level is connected (release), the sensor resumes its normal function.
The function input XI can be used during operation for the synchronisation of multiple sensors. This can be done by connecting external signals, e.g. from a controller (external
synchronisation) or by simply connecting the function inputs of all sensors to be synchronised (internal synchronisation).
and S
min
max
, S
) are displayed in the form of an analogue output signal at the analogue output. The analogue output delivers its
min
and its maximum value at filling level S
min
max
. The characteristic between the two measuring range limits is linear.
max
Release date: 2016-02-16 08:26 Date of issue: 2016-02-16 235147_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
3