Pepperl Fuchs UB500-F54-I-V15 Data Sheet

Ultrasonic sensor UB500-F54-I-V15
Technical data
General specifications
Sensing range 30 ... 500 mm Adjustment range 50 ... 500 mm Dead band 0 ... 30 mm Standard target plate 100 mm x 100 mm Transducer frequency approx. 380 kHz Response delay 50 ms
Indicators/operating means
Model Number
UB500-F54-I-V15
Single head system
Features
•Analog output 4mA...20mA
• Measuring window adjustable
•Program input
• Synchronization options
• Deactivation option
• Temperature compensation
Diagrams
Characteristic response curve
Distance Y [m]
0.20
0.15
0.10
0.05
0.00
-0.05
-0.10
-0.15
-0.20
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Y
Curve 1: flat surface 100 mm x 100 mm Curve 2: round bar, Ø 25 mm
2
X
1
Distance X [m]
LED green solid green: monitoring system
LED yellow solid yellow: object in the evaluation range
LED red flashing:
Electrical specifications
Operating voltage U No-load supply current I
Input/Output
B
0
Synchronization 1 synchronous input
Synchronization frequency
Common mode operation 100 Hz Multiplex operation 100 / n Hz, n = number of sensors
Input
Input type 1 program input
Output
Output type 1 analog output 4 ... 20 mA Default setting evaluation limit A1: 50 mm evaluation limit A2: 500 mm Resolution 0.13 mm Deviation of the characteristic curve ± 1 % of full-scale value Repeat accuracy ± 0.1 % of full-scale value Load impedance 0 ... 300 Ohm Temperature influence ± 1.5 % of full-scale value
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F) Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Connection type Connector M12 x 1 , 5-pin Degree of protection IP65 Material
Housing ABS Transducer epoxy resin/hollow glass sphere mixture; polyurethane foam
Mass 100 g
Compliance with standards and directives
Standard conformity
Standards EN 60947-5-2:2007 + A1:2012
Approvals and certificates
UL approval cULus Listed, General Purpose CSA approval cCSAus Listed, General Purpose CCC approval CCC approval / marking not required for products rated 36 V
green flashing: program function
yellow, flashing: program function, object detected
normal mode: error Program function: no object detected permanently: Program mode, object uncertain
10 ... 30 V DC , ripple 10 % 55 mA
0 level: U 1 level: +4 V...+U input impedance: > 12 KOhm
...+1 V
B
SS
B
synchronization pulse: 0.1 ... 8 ms
lower evaluation limit A1: -U A2: +4 V ... +U input impedance: > 4.7 k, pulse duration: 1 s
IEC 60947-5-2:2007 + A1:2012 EN 60947-5-7:2003
B
... +1 V, upper evaluation limit
B
IEC 60947-5-7:2003
Release date: 2016-04-13 11:24 Date of issue: 2016-04-13 105512_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
1
Ultrasonic sensor UB500-F54-I-V15
Dimensions
Bore hole and countersinking for screws/hexagon M4
120
105
94
21
3.5 3.5
Additional Information
Programming the analog output mode
Rising ramp A1 < A2:
A1
Falling ramp A2 < A1:
32
25
A2
object range
A2
A1
Electrical Connection
Standard symbol/Connections:
(version I)
U
Core colours in accordance with EN 60947-5-2.
Pinout
Wire colors in accordance with EN 60947-5-2
1 BN 2 WH 3 BU 4 BK 5 GY
(BN)
1
(WH)
2
(GY)
5
(BK)
4
(BU)
3
2
+ U
B
Teaching input
Synchronous
Analog output
- U
B
1
5
4
3
(brown) (white) (blue) (black) (gray)
Accessories
UB-PROG2
Programming unit
V15-G-2M-PVC
Female cordset, M12, 5-pin, PVC cable
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2
Release date: 2016-04-13 11:24 Date of issue: 2016-04-13 105512_eng.xml
Loading...
+ 1 hidden pages