Ultrasonic sensor UB4000-30GM-H3-4DT04
Technical data
General specifications
Sensing range 200 ... 4000 mm
Model Number
UB4000-30GM-H3-4DT04
Single head system
Features
• Separate evaluation
• Direct detection mode
Diagrams
Characteristic response curves
Distance Y [m]
3
2
1
0
-1
-2
2
1
Adjustment range 240 ... 4000 mm Dead band
0 ... 200 mm Standard target plate 100 mm x 100 mm Transducer frequency approx. 85 kHz
Electrical specifications
Operating voltage U
No-load supply current I
Input
B
0
10 ... 30 V DC , ripple 10 %
30 mA
Input type 1 pulse input for transmitter pulse (clock)
0-level (active): < 5 V (U
1-level (inactive): > 10 V ... +U
0-level (active): < 1/3 U
1-level (inactive): > 2/3 U
Pulse length
40 ... 600 µs (typ. 500 µs) Pause length 50 x pulse length Impedance 10 kOhm internal connected to +U
Output
Output type 1 pulse output for echo run time, short-circuit proof
open collector PNP with pulldown resistor = 22 kOhm
level 0 (no echo): -U
level 1 (echo detected): (+UB-2 V)
Rated operating current I Temperature influence the echo propagation time: 0.17 % / K
e
15 mA , short-circuit/overload protected
Ambient conditions
Ambient temperature -25 ... 85 °C (-13 ... 185 °F) Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Degree of protection IP67 Connection Deutsch connector, 4-pin DT-04-4P with 300 mm (1 ft) cable Material
Housing stainless steel (1.4305 / AISI 303)
PBT plastic parts
Transducer epoxy resin/hollow glass sphere mixture; polyurethane foam
Mass 210 g
General information
Supplementary information Only the sensor has UL approval.
Compliance with standards and directives
Standard conformity
Standards EN 60947-5-2:2007
IEC 60947-5-2:2007
Approvals and certificates
UL approval cULus Listed, General Purpose
CSA approval cCSAus Listed, General Purpose
1)
SS
> 15 V)
B
(UB > 15 V)
B
(10 V < UB < 15 V)
B
... +UB (10 V < UB < 15 V)
B
2)
B
B
-3
0 1 2 3 4 5 6 7 8
Curve 1: flat surface 100 mm x 100 mm Curve 2: round bar, Ø 25 mm
Release date: 2016-02-29 22:52 Date of issue: 2016-02-29 911811_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Distance X [m]
1
Ultrasonic sensor UB4000-30GM-H3-4DT04
Dimensions
ø 40
25
5
1
2
Electrical Connection
36
4
3
LED
M30 x 1.5
Standard symbol/Connection:
1
(BN)
2
U
2 = Emitter pulse input 4 = Echo propagation time output Core colors in accordance with EN 60947-5-2.
(WH)
4
(BK)
3
(BU)
+ U
Clock
Echo
- U
B
B
128
22
Pinout
Connector 4DT04
1
2
4
3
Accessories
BF 30
Mounting flange, 30 mm
BF 5-30
Universal mounting bracket for cylindrical sensors with a diameter of 5 ... 30 mm
UH3-KHD2-4E5
UH3-KHD2-4I
UH3-T1-KT
Function
The sensing range is determined in the downstream evaluation electronics such as PLC modules or other existing evaluation units. The object distance in pulse-echo mode is obtained from the echo time t. The emis­sion of an ultrasonic pulse starts simultaneously with the falling slope of the clock input signal.
Release date: 2016-02-29 22:52 Date of issue: 2016-02-29 911811_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.