Pepperl Fuchs SK-IDM-Z1-160-BD-1D-J1-DC-S-N0, SK-IDM-Z1-160-BD-1D-J1-DC-U-N0, SK-IDM-Z1-160-BD-1D-J1-AC-S-N0, SK-IDM-Z1-160-BD-1D-J1-AC-U-N0, SK-IDM-Z1-260-D-2D-J1-DC-S-N0 Instruction Manual

...
Pepperl Fuchs SK-IDM-Z1-160-BD-1D-J1-DC-S-N0, SK-IDM-Z1-160-BD-1D-J1-DC-U-N0, SK-IDM-Z1-160-BD-1D-J1-AC-S-N0, SK-IDM-Z1-160-BD-1D-J1-AC-U-N0, SK-IDM-Z1-260-D-2D-J1-DC-S-N0 Instruction Manual

Instruction Manual

1. Marking

Power Supply Unit

SK-IDM-Z1-160-BD-1D-J1-DC-S-N0,

SK-IDM-Z1-160-BD-1D-J1-DC-U-N0,

SK-IDM-Z1-160-BD-1D-J1-AC-S-N0,

SK-IDM-Z1-160-BD-1D-J1-AC-U-N0,

SK-IDM-Z1-260-D-2D-J1-DC-S-N0,

SK-IDM-Z1-260-D-2D-J1-AC-S-N0

SK-IDM-Z1-260-D-2D-J1-DC-U-N,

SK-IDM-Z1-260-D-2D-J1-AC-U-N

Equipment protection level Gb

ATEX certificate: IBExU 18 ATEX 1051

ATEX marking: 1 II 2G Ex eb q [ib IIC/IIB] IIC T4 Gb

IECEx certificate: IECEx IBE 18.0010

IECEx marking: Ex eb q [ib IIC/IIB] IIC T4 Gb

Equipment protection level Db

ATEX certificate0: IBExU 18 ATEX 1051

ATEX marking: 1 II 2D Ex tb [ib] IIIC T135°C Db

IECEx certificate: IECEx IBE 18.0010

IECEx marking: Ex tb [ib] IIIC T135°C Db

Pepperl+Fuchs Group

Lilienthalstraße 200, 68307 Mannheim, Germany

Internet: www.pepperl-fuchs.com

2. Validity

Specific processes and instructions in this instruction manual require special provisions to guarantee the safety of the operating personnel.

3. Target Group, Personnel

Responsibility for planning, assembly, commissioning, operation, maintenance, and dismounting lies with the plant operator.

The personnel must be appropriately trained and qualified in order to carry out mounting, installation, commissioning, operation, maintenance, and dismounting of the device. The trained and qualified personnel must have read and understood the instruction manual.

4. Reference to Further Documentation

Observe laws, standards, and directives applicable to the intended use and the operating location. Observe Directive 1999/92/EC in relation to hazardous areas.

Observe laws, standards, and directives applicable to the intended use and the operating location.

Refer to the relevant EU-type examination certificate to see the relationship between the connected circuit type, the maximum permitted ambient temperature, the surface temperature, and the effective inner reactances.

The corresponding datasheets, manuals, declarations of conformity, EUtype examination certificates, certificates, and control drawings if applicable (see datasheet) are an integral part of this document. You can find this information under www.pepperl-fuchs.com.

Due to constant revisions, documentation is subject to permanent change.

Please refer only to the most up-to-date version, which can be found under www.pepperl-fuchs.com.

6. Improper Use

Protection of the personnel and the plant is not ensured if the device is not used according to its intended use.

7. Mounting and Installation

Prior to using the product make yourself familiar with it. Read the instruction manual carefully.

Only use accessories specified by the manufacturer.

Adjust the sealing element of the cable gland to the diameter of the cables and connection lines used.

Ensure that all cable glands are in good condition and are securely tightened.

Requirements for Cables and Connection Lines

Only cables and connection lines that meet the requirements of the respective hazardous area certificate of the device may be connected to the intrinsically safe connection.

Only use cables and connection lines with a temperature range appropriate to the application.

Observe the permissible cable type and cable length given in the respective hazardous area certificate.

Regarding the verification of intrinsic safety, observe the maximum permissible external capacitance of this device and the other devices in the circuit.

Install the cables and connection lines in such a way that they are protected from ultraviolet radiation.

Install cables and cable glands in a way that they are not exposed to mechanical hazards.

Protect cables and cable glands from tensile load and torsional stress or use certified cable glands.

The dielectric strength of the insulation must be at least 500 V according to IEC/EN 60079-14.

Observe the permissible core cross section of the conductor.

When installing the conductors the insulation must reach up to the terminal.

When using stranded conductors, crimp wire end ferrules on the conductor ends.

Do not use aluminum wire for connection of the device.

Protect plastic cable glands against mechanical hazard.

Never pull the cable. A wire could become loose from the terminal and protection against electric shock can no longer be ensured. Always pull the terminal.

Observe the minimum bending radius of the conductors.

Unused cables and connection lines must be connected to earth or be adequately insulated by means of terminals suitable for the type of protection.

Observe the grounding requirements for type of protection Ex i according to IEC/EN 60079 14.

8. Operation, Maintenance, Repair

Prior to using the product make yourself familiar with it. Read the instruction manual carefully.

Observe the warning markings.

The device must not be repaired, changed, or manipulated. In case of failure, always replace the device with an original device.

Do not use a damaged or polluted device.

Do not connect or disconnect the electrical connection when energized.

If cleaning is necessary while the device is located in a hazardous area, in order to avoid electrostatic charging only use a clean damp cloth.

Observe IEC/EN 60079-17 for maintenance and inspection. Only operate the device with a closed Ex e terminal compartment.

Remove the dust before opening the terminal compartment.

5. Intended Use

The device is only approved for appropriate and intended use. Ignoring these instructions will void any warranty and absolve the manufacturer from any liability.

The power supply unit supplies the following devices:

Handheld readers IDM-Z1-160-D-1D-J1-SU-N-N0, IDM-Z1-160-D-1D-J1-SU-P-N0, IDM-Z1-260-D-2D-J1-S1-N-N0

Bluetooth handheld readers IDM-Z1-161-M-1D-J1-BT-N-N0, IDM-Z1-161-M-1D-J1-BT-P-N0, IDM-Z1-261-M-2D-J1-BT-N-N0

Base station IDM-Z1-X61-B-1D-J1-BT-N0

The device is available with RS-232, RS-485, or with USB interface. The device is available in 3 supply versions.

The device is an electrical apparatus for hazardous areas.

The device may be installed in Zones 1 and 21.

Take the intended use of the connected devices from the corresponding documentation.

DOCT-6131A / 2019-12

1 / 1

9. Delivery, Transport, Disposal

Check the packaging and contents for damage.

Check if you have received every item and if the items received are the ones you ordered.

Always store and transport the device in the original packaging.

Store the device in a clean and dry environment. The permitted ambient conditions must be considered, see datasheet.

The device, built-in components, packaging, and any batteries contained within must be disposed in compliance with the applicable laws and guidelines of the respective country.