Pepperl Fuchs SJ2-SN Data Sheet

Inductive slot sensor SJ2-SN
Technical Data
General specifications
Switching function Normally closed (NC) Output type NAMUR with safety function Slot width 2 mm Depth of immersion (lateral) 5 ... 7 typ. 6 mm Reference target 5 x 8 x 0.5 mm3, Al
0102
Model Number
SJ2-SN
Features
• Usable up to SIL 3 acc. to IEC 61
508
Application
Danger!
In security applications, the sen­sor must be operated on a quali-
fied safety switch amplifier from Pepperl+Fuchs (e.g., KFD2-SH-Ex1). Observe the "exida Functional Safety As­sessment" document, which belongs to this sensor and is available as part of the product documentation from www.pepperl­fuchs.com.
Attention!
NAMUR-compliant switch amplifiers can, due to a low current consumption at the re­corded measuring plate (0.2 mA ... 1 mA), in­correctly report cable breaks (required in accordance with EN 60947-5-6:2000: 0.4 mA ... 1 mA).
Safety Integrity Level (SIL) up to SIL3 acc. to IEC 61508 Danger! In safety-related applications
Output type 2-wire
Nominal ratings
Nominal voltage Uo8.2 V Switching frequency f 0 ... 5000 Hz Hysteresis H with NAMUR switch amplifier: 0.02 mm (e. g. Pepperl+Fuchs
Suitable for 2:1 technology yes , with reverse polarity protection diode Rate of current rise -11 mA / mm Current consumption
Measuring plate not detected Measuring plate detected
Functional safety related parameters
Safety Integrity Level (SIL) SIL 3 MTTFd 11800 a Mission Time (T Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -40 ... 100 °C (-40 ... 212 °F)
Mechanical specifications
Connection type flexible leads LIFYW , 500 mm Core cross-section 0.06 mm Housing material PBT Degree of protection IP67 Mass 2.5 g No
te adjustable
General information
Use in the hazardous area see instruction manuals
Compliance with standards and directives
Standard conformity
MUR
NA
Standards
Approvals and certificates
EAC conformity TR CU 012/2011 FM approval
Control drawing UL approval cULus Listed, General Purpose CCC approval CCC approval / marking not required for products rated 36 V
) 20 a
M
Dimensions
the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs, such as KFD2-SH-EX1. Consider the "exida Functional Safety Assessment" document which is available on www.pepperl-fuchs.com as an integral part of this product's documentation.
KCD2-SR-Ex1.LB) with safety switch amplifier 0.01 mm (e. g. Pepperl+Fuchs KFD2­SH-Ex1)
3 mA
0.2 ... 1 mA
2
stop
EN 60947-5-6:2000 IEC 60947-5-6:1999 EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
116-0165F
Release date: 2018-04-19 08:24 Date of issue: 2018-04-19 273025_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2
6
111
ø1.5
8
3.5
15
4.2
1
Inductive slot sensor SJ2-SN
Electrical Connection
BN
BU
L+
L-
Release date: 2018-04-19 08:24 Date of issue: 2018-04-19 273025_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2
Loading...
+ 3 hidden pages