Pepperl Fuchs SC3.5-N0-WH Data Sheet

Inductive slot sensor SC3,5-N0-WH
Technical Data
General specifications
Switching function Normally closed (NC) Output type NAMUR Slot width 3.5 mm Depth of immersion (lateral) 5 ... 7 typ. 6 mm Output type 2-wire
Nominal ratings
Nominal voltage Uo8.2 V (Ri approx. 1 kΩ)
0102
Model Number
SC3,5-N0-WH
Features
• 3.5 mm slot width
Operating voltage U Switching frequency f 0 ... 3000 Hz Hysteresis H 0.06 ... 0.1 mm Suitable for 2:1 technology yes , Reverse polarity protection diode not required Design data Current consumption
Measuring plate not detected Measuring plate detected
Switching state indicator LED, yellow
Ambient conditions
Ambient temperature -25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection type flexible leads LiY , 500 mm Core cross-section 0.14 mm Housing material PBT Degree of protection IP67
General information
Use in the hazardous area see instruction manuals
Category
Compliance with standards and directives
Standard conformity
NAMUR
Electromagnetic compatibility Standards
Approvals and certificates
EAC conformity TR CU 012/2011 UL approval cULus Listed, General Purpose CSA approval cCSAus Listed, General Purpose CCC approval CCC approval / marking not required for products rated 36 V
Dimensions
5 ... 25 V
B
3 mA 1 mA
2
1G; 2G; 1D
EN 60947-5-6:2000 IEC 60947-5-6:1999 NE 21:2007 EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
Electrical Connection
10
10
BN
BU
3.5
ø 1.85
19.5
1 0.5
7.25
L+
L-
5.5
LED
3
152
Release date: 2018-04-19 08:24 Date of issue: 2018-04-19 106700_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
1
Inductive slot sensor SC3,5-N0-WH
Equipment protection level Ga
CE marking 0102
ATEX marking ¬ II 1G Ex ia IIC T6T1 Ga
Standards EN 60079-0:2012+A11:2013, EN 60079-11:2012
Appropriate type SC3,5...-N0...
Effective internal inductivity C
Effective internal inductance L
Highest permissible ambient temperature Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
Equipment protection level Gb
CE marking 0102
ATEX marking ¬ II 1G Ex ia IIC T6T1 Ga
Standards EN 60079-0:2012+A11:2013, EN 60079-11:2012
Appropriate type SC3,5...-N0...
Effective internal inductivity C
Effective internal inductance L
Maximum permissible ambient temperature T
Equipment protection level Da
CE marking 0102
ATEX marking ¬ II 1D Ex ia IIIC T135°C Da
Standards EN 60079-0:2012+A11:2013, EN 60079-11:2012
Appropriate type SC3,5...-N0...
Effective internal inductivity C
Effective internal inductance L
i
i
i
i
i
i
The Ex-related marking can also be printed on the enclosed label.
Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions
150 nF ; a cable length of 10 m is considered.
150 µH ; a cable length of 10 m is considered.
temperature class, and the effective internal reactance values can be found on the EU-type examination certificate.
Note:
Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already
been applied to the temperature table for category 1.
The Ex-related marking can also be printed on the enclosed label.
Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions
150 nF ; a cable length of 10 m is considered.
150 µH ; a cable length of 10 m is considered.
Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
amb
temperature class, and the effective internal reactance values can be found on the EU-type examination certificate.
The Ex-related marking can also be printed on the enclosed label.
Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions
150 nF ; a cable length of 10 m is considered.
150 µH ; a cable length of 10 m is considered.
Release date: 2018-04-19 08:24 Date of issue: 2018-04-19 106700_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2
Loading...