Inductive ring sensor RJ15-N
Technical Data
General specifications
Switching function Normally closed (NC)
Output type NAMUR
Inside diameter 15 mm
0102
Model Number
RJ15-N
Features
• 15 mm inside diameter
Measuring cylinder
Diameter
Length
Output type 2-wire
Nominal ratings
Nominal voltage Uo8.2 V (Ri approx. 1 kΩ)
Operating voltage U
Switching frequency f 0 ... 1500 Hz
Current consumption
Measuring plate not detected
Measuring plate detected
Functional safety related parameters
MTTFd 9340 a
Mission Time (TM) 20 a
Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Connection type cable PVC , 2 m
Core cross-section 0.14 mm
Housing material PBT
Degree of protection IP67
Cable
Bending radius
General information
Use in the hazardous area see instruction manuals
Category
Compliance with standards and
directives
Standard conformity
NAMUR
Standards
Approvals and certificates
FM approval
Control drawing
UL approval cULus Listed, General Purpose
CSA approval cCSAus Listed, General Purpose
Dimensions
3 mm
4 mm
5 ... 25 V
B
≥ 3 mA
≤ 1 mA
> 10 x cable diameter
2G
EN 60947-5-6:2000
IEC 60947-5-6:1999
EN 60947-5-2:2007
IEC 60947-5-2:2007
116-0165
2
M3 x 6
Electrical Connection
15
45
15
13
25
BN
BU
29
L+
L-
30.5
ø 6.4
Release date: 2017-07-25 10:20 Date of issue: 2018-02-16 106556_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
1

Inductive ring sensor RJ15-N
Equipment protection level Gb
CE marking 0102
ATEX marking ¬ II 2G Ex ia IIC T6…T1 Gb
Standards EN 60079-0:2012+A11:2013, EN 60079-11:2012
Appropriate type RJ15-N...
Effective internal inductivity C
Effective internal inductance L
Maximum permissible ambient temperature T
Special conditions
i
i
The Ex-related marking can also be printed on the enclosed label.
Ignition protection "Intrinsic safety"
Use is restricted to the following stated conditions
≤ 130 nF ; a cable length of 10 m is considered.
≤ 20 µH ; a cable length of 10 m is considered.
Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
amb
temperature class, and the effective internal reactance values can be found on the EU-type examination certificate.
Release date: 2017-07-25 10:20 Date of issue: 2018-02-16 106556_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2