Technical Data
General specifications
Switching function Normally closed (NC)
Output type NAMUR, bistable
Inside diameter 10 mm
0102
Model Number
RC10-14-N3
Features
• 10 mm inside diameter
•Bistable
• Direction detection
Measuring cylinder
Diameter
Length
Measuring cone
Material
Output type 2-wire
Nominal ratings
Nominal voltage Uo8.2 V (Ri approx. 1 kΩ)
Hysteresis H typ. 1 %
Reverse polarity protection reverse polarity protected
Design data
Current consumption
Traverse B
Traverse A
Time delay before availability t
Functional safety related parameters
MTTFd 2144 a
Mission Time (TM) 20 a
Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -20 ... 100 °C (-4 ... 212 °F)
Mechanical specifications
Connection type cable PVC , 2 m
Core cross-section 0.14 mm
Housing material PBT
Degree of protection IP67
Cable
Bending radius
General information
Use in the hazardous area see instruction manuals
Category
Compliance with standards and
directives
Standard conformity
NAMUR
Standards
Approvals and certificates
FM approval
Control drawing
UL approval cULus Listed, General Purpose
CSA approval cCSAus Listed, General Purpose
Dimensions
2.5 mm
3 mm
9S20K
3 mA
1 mA
≤ 5 ms
v
> 10 x cable diameter
2G
EN 60947-5-6:2000
IEC 60947-5-6:1999
EN 60947-5-2:2007
IEC 60947-5-2:2007
116-0165F
2
B
20
6
A
3,1
14
12,5
18
25
10
32,5
20
Release date: 2017-07-27 13:48 Date of issue: 2018-02-16 051666_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
1

Inductive ring sensor RC10-14-N3
Electrical Connection
BN
BU
Equipment protection level Gb
CE marking 0102
ATEX marking ¬ II 2G Ex ia IIC T6…T1 Gb
Standards EN 60079-0:2012+A11:2013, EN 60079-11:2012
Appropriate type RC10-...-N3...
Effective internal inductivity C
Effective internal inductance L
Maximum permissible ambient temperature T
Special conditions
i
i
L+
L-
The Ex-related marking can also be printed on the enclosed label.
Ignition protection "Intrinsic safety"
Use is restricted to the following stated conditions
≤ 90 nF ; a cable length of 10 m is considered.
≤ 120 µH ; a cable length of 10 m is considered.
Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
amb
temperature class, and the effective internal reactance values can be found on the EU-type examination certificate.
Release date: 2017-07-27 13:48 Date of issue: 2018-02-16 051666_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.