Inductive ring sensor RC10-14-N0
Technical Data
General specifications
Switching function Normally closed (NC)
Output type NAMUR
Inside diameter 10 mm
0102
Model Number
RC10-14-N0
Features
• 10 mm inside diameter
Measuring cylinder 9S20K
Diameter
Length
Output type 2-wire
Nominal ratings
Nominal voltage Uo8.2 V (Ri approx. 1 kΩ)
Operating voltage U
Switching frequency f 0 ... 2000 Hz
Suitable for 2:1 technology yes , Reverse polarity protection diode not required
Current consumption
Measuring plate not detected
Measuring plate detected
Functional safety related parameters
MTTFd 6150 a
Mission Time (T
Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -20 ... 65 °C (-4 ... 149 °F)
Mechanical specifications
Connection type cable PVC , 2 m
Core cross-section 0.14 mm
Housing material PBT
Degree of protection IP67
Cable
Bending radius
Mass 36 g
General information
Use in the hazardous area see instruction manuals
Category
Compliance with standards and
directives
Standard conformity
NAMUR
Electromagnetic compatibility
Standards
Approvals and certificates
FM approval
Control drawing
UL approval cULus Listed, General Purpose
CSA approval cCSAus Listed, General Purpose
) 20 a
M
Dimensions
2.5 mm
4 mm
5 ... 25 V
B
≥ 3 mA
at maximum permissible ambient temperature, the current
consumption can drop to 1.6 mA
≤ 1 mA
2
> 10 x cable diameter
2G
EN 60947-5-6:2000
IEC 60947-5-6:1999
NE 21:2007
EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
116-0165F
Release date: 2018-02-02 11:02 Date of issue: 2018-02-16 095912_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
20
6
10
32.5
3.1
14
12.5
18
25
20
M5
1

Inductive ring sensor RC10-14-N0
Electrical Connection
BN
BU
Equipment protection level Gb
CE marking 0102
ATEX marking ¬ II 2G Ex ia IIC T6…T1 Gb
Standards EN 60079-0:2012+A11:2013, EN 60079-11:2012
Appropriate type RC10-...-N0...
Effective internal inductivity C
Effective internal inductance L
Maximum permissible ambient temperature T
i
i
L+
L-
The Ex-related marking can also be printed on the enclosed label.
Ignition protection "Intrinsic safety"
Use is restricted to the following stated conditions
≤ 150 nF ; a cable length of 10 m is considered.
≤ 100 µH ; a cable length of 10 m is considered.
Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
amb
temperature class, and the effective internal reactance values can be found on the EU-type examination certificate.
Release date: 2018-02-02 11:02 Date of issue: 2018-02-16 095912_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2