This document contains information that you must read for your own personal safety and to
avoid property damage. Depending on the hazard category, the warning signs are displayed in
descending order as follows:
Safety-relevant symbols
Danger!
This symbol indicates an imminent danger.
Non-observance will result in personal injury or death.
Warning!
This symbol indicates a possible fault or danger.
Non-observance may cause personal injury or serious property damage.
Caution!
This symbol indicates a possible fault.
Non-observance could interrupt devices and any connected facilities or systems, or result in
their complete failure.
Informative symbols
Note!
This symbol brings important information to your attention.
Action
This symbol indicates a paragraph with instructions.
2014-10
7
Pulscon LTC51
-
Important document information
1.1.2Electrical symbols
SymbolMeaning
)
*
Table 1.1
Direct current
A terminal to which DC voltage is applied or through which direct
current flows.
Alternating current
A terminal to which alternating voltage is applied or through which
alternating current flows.
Direct current and alternating current
•A terminal to which alternating voltage or DC voltage is applied.
•A terminal through which alternating current or direct current
flows.
Ground connection
A grounded terminal which, as far as the operator is concerned, is
grounded via a grounding system.
Protective ground connection
A terminal which must be connected to ground prior to establishing
any other connections.
Equipotential connection
A connection that has to be connected to the plant grounding
system: This may be a potential equalization line or a star grounding
system depending on national or company codes of practice.
1.1.3Symbols in graphics
SymbolMeaning
1, 2, 3 ...Item numbers
,…,1. 2. 3.
A, B, C, ...Views
A-A, B-B, C-C, ...Sections
.
Table 1.2
Series of steps
Hazardous area
Indicates a hazardous area.
Safe area (non-hazardous area)
Indicates a non-hazardous location.
2014-10
8
Pulscon LTC51
F
L
D
E
20 mA
100%
4mA
0%
LN
R
Function and system design
2Function and system design
2.1Measuring principle
2.1.1Basic principles
The device is a "downward-looking" measuring system that functions according to the ToF
method (ToF = Time of Flight). The distance from the reference point to the product surface is
measured. High-frequency pulses are injected to a probe and led along the probe. The pulses
are reflected by the product surface, received by the electronic evaluation unit and converted
into level information. This method is also known as TDR (Time Domain Reflectometry).
Figure 2.1Parameters for level measurement with the guided radar
LNProbe length
DDistance
LLevel
RReference point of measurement
EEmpty calibration (= zero)
FFull calibration (= span)
Note!
If, for rope probes, the DC value is less than 7, then measurement is not possible in the area of
the straining weight (0 to 250 mm from end of probe; lower blocking distance).
2.1.2Dielectric constant
The dielectric constant (DC) of the medium has a direct impact on the degree of reflection of
the high frequency pulses. In the case of large DC values, such as for water or ammonia, there
is strong pulse reflection while, with low DC values, such as for hydrocarbons, weak pulse
reflection is experienced.
2014-10
9
Pulscon LTC51
Function and system design
2.1.3Input
The reflected pulses are transmitted from the probe to the electronics. There, a
microprocessor analyzes the signals and identifies the level echo which was generated by the
reflection of the high-frequency pulses at the product surface. This clear signal detection
system benefits from over 30 years' experience with pulse time-of-flight procedures.
The distance D to the product surface is proportional to the time of flight t of the impulse:
D = c x t / 2,
where c is the speed of light.
Based on the known empty distance E, the level L is calculated:
L = E – D
Note!
The reference point R of the measurement is located at the process connection.
See chapter 10.
The device possesses functions for interference echo suppression that can be activated by the
user. They guarantee that interference echoes from e. g. internals and struts are not
interpreted as level echoes.
2.1.4Output
The device is preset at the factory to the probe length ordered so that in most cases only the
application parameters that automatically adapt the device to the measuring conditions need
to be entered. For models with a current output, the factory adjustment for zero point E and
span F is 4 mA and 20 mA, for digital outputs and the display module 0 % and 100 %. A
linearization function with max. 32 points, which is based on a table entered manually or semiautomatically, can be activated on site or via remote operation. This function allows the level to
be converted into units of volume or mass, for example.
2.2Life cycle of the product
Engineering
• Universal measuring principle
• Measurement unaffected by medium properties
• Hardware and software developed according to SIL IEC 61508
Procurement
• Pepperl+Fuchs being the world market leader in level measurement guarantees asset
protection
• Worldwide support and service
10
Installation
• Special tools are not required
• Reverse polarity protection
• Modern, detachable terminals
• Main electronics protected by a separate connection compartment
2014-10
Pulscon LTC51
Function and system design
Commissioning
• Fast, menu-guided commissioning in only 6 steps
• Plain text display in national languages reduces the risk of error or confusion
• Direct local access of all parameters
• Short instruction manual at the device
Operation
• Multi-echo tracking: Reliable measurement through self-learning echo-search algorithms
taking into account the short-term and long-term history in order to check the found echoes
for plausibility and to suppress interference echoes.
• Diagnostics in accordance with NAMUR NE 107
Maintenance
• HistoROM: Data backup for instrument settings and measured values
• Exact instrument and process diagnosis to assist fast decisions with clear details
concerning remedies
• Intuitive, menu-guided operating concept in national languages saves costs for training,
maintenance and operation
• Cover of the electronics compartment can be opened in hazardous areas
Retirement
• Order code translation for subsequent models
• RoHS-conforming (Restriction of certain Hazardous Substances), unleaded soldering of
electronic components
• Environmentally sound recycling concept
2014-10
11
Pulscon LTC51
Function and system design
2.3Measuring system
2.3.1General notes on probe selection
• Normally use rod probes for liquids. Rope probes are used in liquids for measuring ranges
> 10 m (33 ft) and with restricted ceiling clearance which does not allow the installation of
rigid probes.
• Coax probes are suited to liquids with viscosities of up to approx. 500 cst. Coax probes
can measure most liquefied gases, as of a dielectric constant of 1.4. Moreover, installation
conditions, such as nozzles, tank internal fittings etc., have no effect on the measurement
when a coax probe is used. A coax probe offers maximum EMC safety when used in
plastic tanks.
Probe selection
The various types of probe in combination with the process connections are suitable for the
following applications
1
:
Type of probeRod probeRope probeCoax probe
Feature "Probe"OptionOptionOption
18 mm (316L)24 mm (316)4... mm (316L)
51/3 in (316L)31/6 in (316)G... inch (316L)
812 mm (316L)E4 mm (316) with
H... mm (Alloy C)
center rod
91/2 in (316L)F1/6 in (316) with
K... inch (Alloy C)
center rod
612 mm (Alloy C)
71/2 in (Alloy C)
A
16 mm (316L) divisible
C
B
0.63 in (316L) divisible
D
Max. probe length 10 m (33 ft)
b
45 m (148 ft)6 m (20 ft)
For applicationLevel measurement in liquids
Table 2.1
a
a
Multiple punched for process connections G1-1/2 in or flange
b
Maximum probe length for indivisible rod probes: 4 m (13 ft)
1
If required, rod and rope probes can be replaced. They are secured with Nord-Lock washers or a thread coating.
For further information on service and spare parts please contact the Pepperl+Fuchs service.
12
2014-10
Pulscon LTC51
Input
3Input
3.1Measured variable
The measured variable is the distance between the reference point and the product surface.
Subject to the empty distance entered E the level is calculated.
Alternatively, the level can be converted into other variables (volume, mass) by means of
linearization (32 points).
3.2Measuring range
The following table describes the media groups and the possible measuring range as a
function of the media group.
Pulscon LTC51
Media
group
11.4 ... 1.6condensed gases,
21.6 ... 1.9•liquefied gas,
31.9 ... 2.5mineral oils, fuels•one-piece: 4 m (13 ft)
42.5 ... 4•benzene, styrene,
54 ... 7•chlorobenzene,
6>7•aqueous
Table 3.1
DC (r)Typical liquidsMeasuring range
bare metallic
rod probes
e. g. N2, CO
e. g. propane
•solvent
•Freon
•palm oil
toluene
•furan
•naphthalene
chloroform
•cellulose spray
•isocyanate,
aniline
solutions
•alcohols
•ammonia
2
on request6 m (20 ft)
•one-piece: 4 m (13 ft)
•divisible: 10 m (33 ft)
•divisible: 10 m (33 ft)
•one-piece: 4 m (13 ft)
•divisible: 10 m (33 ft)
•one-piece: 4 m (13 ft)
•divisible: 10 m (33 ft)
•one-piece: 4 m (13 ft)
•divisible: 10 m (33 ft)
bare metallic
rope probes
15 ... 22 m
(49 ... 72 ft)
22 ... 32 m
(72 ... 105 ft)
32 ... 42 m
(105 ... 138 ft)
42 ... 45 m
(138 ... 148 ft)
45 m (148 ft)6 m (20 ft)
coax probes
6 m (20 ft)
6 m (20 ft)
6 m (20 ft)
6 m (20 ft)
Note!
Reduction of the max. possible measuring range through buildup, above all of moist products.
Due to the high diffusion rate of ammonia it is recommended with gas-tight bushing for
measurements in this medium.
2014-10
13
Pulscon LTC51
F
UB
E
100%
0%
LN
R
SD
Input
3.3Blocking distance
The upper blocking distance (= UB) is the minimum distance from the reference point of the
measurement (mounting flange) to the maximum level.
Figure 3.1Definition of blocking distance and safety distance
RReference point of measurement
LNProbe length
UBUpper blocking distance
EEmpty calibration (= zero)
FFull calibration (= span)
SDSafety distance
Blocking distance (factory setting):
• with coax probes: 0mm(0in)
• with rod and rope probes up to 8 m (26 ft): 200 mm (8 in)
• with rod and rope probes exceeding a length of 8 m (26 ft): 0.025 x (length of probe)
Note!
The specified blocking distances are preset on delivery. Depending on the application these
settings can be changed.
For rod and rope probes and for media with DC > 7 (or generally for stilling well/bypass
applications) the blocking distance may be reduced to 100 mm (4 in).
Within the blocking distance, a reliable measurement can not be guaranteed.
Note!
A safety distance SD can be defined in addition to the blocking distance. A warning is
generated if the level rises into this safety distance.
3.4Measuring frequency spectrum
100 MHz to 1.5 GHz
14
2014-10
Pulscon LTC51
Output
4Output
4.1Output signal
HART
Signal codingFSK ±0.5 mA over currency signal
Data transmission rate1200 Baud
Galvanic isolationYes
Table 4.1
PROFIBUS PA
Signal codingManchester Bus Powered (MBP)
Data transmission rate31.25 kBit/s, voltage mode
Galvanic isolationYes
Table 4.2
Switch output
Note!
For HART devices, the switch output is available as an option. See product structure, feature
"Electrical Output", option ID. Devices with PROFIBUS PA always have a switch output.
Switching behaviorBinary (conductive or non-conductive), switches when the
programmable switch point is reached
Failure modenon-conductive
Electrical connection valuesU = 10.4 ... 35 V DC, I = 0 ... 40 mA
Internal resistanceRI < 880
The voltage drop at this internal resistance has to be taken
into account on planning the configuration. For example, the
resulting voltage at a connected relay must be sufficient to
switch the relay.
Insulation voltagefloating, Insulation voltage 1350 V DC to power supply and
Switch pointfreely programmable, separately for switch-on and switch-off
Switching delayfreely programmable from 0 to 100 s, separately for switch-
Number of switching cyclescorresponds to the measuring cycle
Signal source
device variables
Number of switching cyclesunlimited
Table 4.3
500 V AC to ground
point
on and switch-off point
•Level linearized
•Distance
•Terminal voltage
•Electronic temperature
•Relative echo amplitude
•Diagnostic values, Advanced diagnostics
2014-10
15
Pulscon LTC51
Output
4.2Signal on alarm
Depending on the interface, failure information is displayed as follows:
• Current output (for HART devices)
•Fail-safe mode selectable (in accordance with NAMUR Recommendation NE 43):
Minimum alarm: 3.6 mA
Maximum alarm (= factory setting): 22 mA
•Fail-safe mode with user-selectable value: 3.59 ... 22.5 mA
•Local display
•Status signal (in accordance with NAMUR Recommendation NE 107)
•Plain text display
• Operating tool via digital communication (HART, PROFIBUS PA) or service interface (CDI)
•Status signal (in accordance with NAMUR Recommendation NE 107)
•Plain text display
4.3Linearization
The linearization function of the device allows the conversion of the measured value into any
unit of length or volume. Linearization tables for calculating the volume in cylindrical tanks are
pre-programmed. Other tables of up to 32 value pairs can be entered manually or semiautomatically.
4.4Galvanic isolation
All circuits for the outputs are galvanically isolated from each other.
HART loadMin. 250
HART device variablesThe measured values can be freely assigned to the device
Supported functions•Burst mode
Table 4.4
Information and files under:
•www.pepperl-fuchs.com
•www.hartcomm.org
variables.
Measured values for PV (primary variable)
•Level linearized
•Distance
•Electronic temperature
•Relative echo amplitude
Measured values for SV, TV, FV (second, third and fourth
variable)
•Level linearized
•Distance
•Terminal voltage
•Electronic temperature
•Absolute echo amplitude
•Relative echo amplitude
•Calculated DC
•Additional transmitter status
Wireless HART data
Minimum start-up voltage11.4 V
Start-up current3.6 mA
Start-up time15 s
Minimum operating voltage11.4 V
Multidrop current3.6 mA
Set-up time1 s
Table 4.5
2014-10
17
Pulscon LTC51
Output
PROFIBUS PA
Manufacturer ID93 (5D HEX)
Ident number0E3B HEX
Profile version3.02
GSD fileInformation and files under:
GSD file version
Output valuesAnalog Input:
Input valuesAnalog Output:
Supported functions•Identification & Maintenance
Table 4.6
•www.pepperl-fuchs.com
•www.profibus.org
•Level linearized
•Distance
•Terminal voltage
•Electronic temperature
•Absolute echo amplitude
•Relative echo amplitude
•Calculated DC
Digital Input:
•Extended diagnostic blocks
•Status output PFS Block
•Analog value from PLC (for sensor block external
pressure and temperature)
•Analog value from PLC to be indicated on the display
Digital Output:
•Extended diagnostic block
•Level limiter
•Sensor block measurement on
•Sensor block save history on
•Status output
Simple device identification via control system and
nameplate
•Automatic Ident Number Adoption
GSD compatibility mode with respect to the previous
device
•Physical Layer Diagnostics
Installation check of the PROFIBUS segment via
terminal voltage and telegram monitoring
•PROFIBUS Up-/Download
Up to 10 times faster reading and writing of parameters
via PROFIBUS Up-/Download
•Condensed Status
Simple and self-explanatory diagnostic information due
to categorization of diagnostic messages
18
2014-10
Pulscon LTC51
+
–
4 ... 20 mA
5412
7
8
3
+
–
1
+
2
4...20mA
HART
10
mm
2- wire
leve
l
4-20
mA
4-20
mA
HA
RT
[21]
open
-
6
~
Power supply
5Power supply
5.1Terminal assignment
2-wire: 4 ... 20 mA HART
Figure 5.1Terminal assignment 2-wire; 4 ... 20 mA HART
1Active barrier with power supply (e. g. KCD2-STC-Ex1): observe terminal voltage
2HART communication resistor ( 250 ): observe maximum load
3Connection for optional field communicator
4Analog display device: observe maximum load
5Cable screen; observe cable specification
64 ... 20 mA HART (passive): terminals 1 and 2
7Terminal for potential equalization line
8Cable entry
1Active barrier with power supply (e. g. KCD2-STC-Ex1): observe terminal voltage
2HART communication resistor ( 250 ): observe maximum load
3Connection for optional field communicator
4Analog display device: observe maximum load
5Cable screen; observe cable specification
64 ... 20 mA HART (passive): terminals 1 and 2
7Switch output (open collector): terminals 3 and 4
8Terminal for potential equalization line
9Cable entry for 4 ... 20 mA HART line
10Cable entry for switch output line
20
2014-10
Pulscon LTC51
1
3
+
+
2
4
4...20mA
HART
4...20mA
10 mm
2- wire
level
4-20 mA 4-20 mA
HA
RT
[04/05]
open
-
-
10
13
12
11
+
+
-
-
1
2
3
9
586
74
4
+
–
+
–
4 ... 20 mA
4 ... 20 mA
Power supply
2-wire: 4 ... 20 mA HART, 4 ... 20 mA
Figure 5.3Terminal assignment 2-wire, 4 ... 20 mA HART, 4 ... 20 mA
1Connection current output 2
2Connection current output 1
3Supply voltage for current output 1 (e. g. KCD2-STC-Ex1); observe terminal voltage
4Cable screen; observe cable specification
5HART communication resistor ( 250 ): observe maximum load
6Connection for optional field communicator
7Analog display device; observe maximum load
8Analog display device; observe maximum load
9Supply voltage for current output 2 (e. g. KCD2-STC-Ex1); observe terminal voltage
10Current output 2: terminals 3 and 4
11Terminal for the potential equalization line
12Cable entry for current output 1
13Cable entry for current output 2
Note!
This version is also suited for single-channel operation. In this case, current output 1
(terminals 1 and 2) must be used.
1Evaluation unit, e. g. PLC
2HART communication resistor ( 250 ): observe maximum load
3Connection for optional field communicator
4Analog display device: observe maximum load
5Signal cable including screening (if required), observe cable specification
6Protective connection; do not disconnect!
7Protective earth, observe cable specification
84 ... 20 mA HART (active): terminals 3 and 4
9Supply voltage: terminals 1 and 2
10Supply voltage: Observe terminal voltage, observe cable specification
11Terminal for potential equalization
12Cable entry for signal line
13Cable entry for power supply
Warning!
To ensure electrical safety:
• Do not disconnect the protective connection (6).
• Disconnect the supply voltage before disconnecting the protective earth (7).
Note!
Connect protective earth to the internal ground terminal (7) before connecting the supply
voltage. If necessary, connect the potential matching line to the external ground terminal (11).
22
2014-10
Pulscon LTC51
Power supply
Note!
In order to ensure electromagnetic compatibility (EMC): Do not only ground the device via the
protective earth conductor of the supply cable. Instead, the functional grounding must also be
connected to the process connection (flange or threaded connection) or to the external ground
terminal.
Note!
An easily accessible power switch must be installed in the proximity of the device. The power
switch must be marked as a disconnector for the device (IEC/EN 61010).
2014-10
23
Pulscon LTC51
3
1
+
L
4
2
4...20 mA
HA
RT
90...2
53
V~
10
mm
2- wire
4-20 mA
HA
RT
[09
]
ope
n
-
N
13
12
11
910
+
-
23
4
6
7
8
5
1
4 ... 20 mA
≥ 250Ω
Power supply
4-wire: 4 ... 20 mA HART (90 ... 253 V AC)
Figure 5.5Terminal assignment 4-wire; 4 ... 20 mA HART (90 ... 253 V AC)
1Evaluation unit, e. g. PLC
2HART communication resistor ( 250 ): observe maximum load
3Connection for optional filed communicator
4Analog display device: observe maximum load
5Signal cable including screening (if required), observe cable specification
6Protective connection; do not disconnect!
7Protective earth, observe cable specification
84 ... 20 mA HART (active): terminals 3 and 4
9Supply voltage: terminals 1 and 2
10Supply voltage: observe terminal voltage, observe cable specification
11Terminal for potential equalization
12Cable entry for signal line
13Cable entry for power supply
Warning!
To ensure electrical safety:
• Do not disconnect the protective connection (6).
• Disconnect the supply voltage before disconnecting the protective earth (7).
Note!
Connect protective earth to the internal ground terminal (7) before connecting the supply
voltage. If necessary, connect the potential matching line to the external ground terminal (11).
24
2014-10
Pulscon LTC51
Power supply
Note!
In order to ensure electromagnetic compatibility (EMC): Do not only ground the device via the
protective earth conductor of the supply cable. Instead, the functional grounding must also be
connected to the process connection (flange or threaded connection) or to the external ground
terminal.
Note!
An easily accessible power switch must be installed in the proximity of the device. The power
switch must be marked as a disconnector for the device (IEC/EN 61010).
2014-10
25
Pulscon LTC51
1
1
+
+
2
2
PA
[06/07]
-
-
1
3
+
+
2
4
PA
10 mm
2- wire
level
4-20 mA PFS
[26/27]
open
-
-
4
1
2
3
5
3+
4-
Power supply
PROFIBUS PA
Figure 5.6Terminal assignment PROFIBUS PA
1Cable screen: observe cable specifications
2Switch output (open collector): terminals 3 and 4
3Connection PROFIBUS PA: terminals 1 and 2
4Terminal for potential equalization line
5Cable entries
26
2014-10
Pulscon LTC51
Power supply
Connection examples for the switch output
Note!
For HART devices, the switch output is available as an option. See product structure, feature
"Electrical Output", option ID. Devices with PROFIBUS PA always have a switch output.
3+
4-
+
1
+
-
3+
4-
2
Connection of a relay
Suitable relays (examples):
•Solid-state relay: Phoenix Contact OV-
Connection of a digital input
1 Pull-up resistor
2 Digital input
24DC/480AC/5 with mounting rail
connector UMK-1 OM-R/AMS
For optimum interference immunity we recommend to connect an external resistor (internal
resistance of the relay or Pull-up resistor) of < 1000 .
2014-10
27
Pulscon LTC51
Stromausgang1
Relais1
Stromausgang2
Stromausgang3
Relais2Relais2
versorgungversorgung
EingangEingang
1
2
3
4
5
6
7
8
9
11
12
13
14
15
19
20
21
16
17
18
22
23
24
24V DC
10
HART Loop Converter
HART
+
-
+
Current output 1
Relay 1
Current output 2
Current output 3
Relay 2
Power
supply
Input
Auxiliary energy
HART
ESC
OK
KFD2-HLCEx1.D.2W
RS232
PWR
ERR
1 2
OUT
19 21
15
9
13
7
20
14
8
2
2
24
18
12
16
10
23
17
11
1
3
24
6
5
Power supply
5.2HART Loop Converter KFD2-HLC-Ex1.D.**
The dynamic variables of the HART protocol can be converted into individual 4 to 20 mA
sections using the HART loop converter KFD2-HLC-Ex1.D.**. The variables are assigned to
the current output and the measuring ranges of the individual parameters are defined in the
KFD2-HLC-Ex1.D.**.
28
Figure 5.7Connection example KFD2-HLC-Ex1.D.**: passive 2-wire device and current outputs
The HART loop converter KFD2-HLC-Ex1.D.** can be acquired.
Note!
Additional documentation: see data sheets.
connected as power source
2014-10
Pulscon LTC51
21
3
4
2
1
4
3
Power supply
5.3Device plug connectors
Note!
For the versions with fieldbus plug connector (M12 or 7/8 in), the signal line can be connected
without opening the housing.
Various supply units can be ordered from Pepperl+Fuchs: see chapter 14.4.
2-wire, 4 ... 20 mA HART, passive
Approval
•Non-Ex
•ExnA
•CSAGP
•Exic11.5 ... 32 V
•Exia/IS11.5 ... 30 V
•Exd/XP
•Exic(ia)
•Ex tD/DIP
a
Terminal voltage U at the
device
11.5 ... 35 V
13.5 ... 30 V
1
Maximum load R, depending on the supply voltage
at the supply unit
U
0
b
c
d
e
Table 5.4
a
Feature "Approval" of the product structure
b
For ambient temperatures Ta -30 °C (-22 °F) a minimum voltage of 14 V is required for the startup of the device at the
MIN error current (3.6 mA). The startup current can be parametrized. If the device is operated with a fixed current I 4.5 mA
(HART multidrop mode), a voltage of U 11.5 V is sufficient throughout the entire range of ambient temperatures.
c
For ambient temperatures Ta -30 °C (-22 °F) a minimum voltage of 14 V is required for the startup of the device at the
MIN error current (3.6 mA). The startup current can be parametrized. If the device is operated with a fixed current I 4.5 mA
(HART multidrop mode), a voltage of U 11.5 V is sufficient throughout the entire range of ambient temperatures.
d
For ambient temperatures Ta -30 °C (-22 °F) a minimum voltage of 14 V is required for the startup of the device at the
MIN error current (3.6 mA). The startup current can be parametrized. If the device is operated with a fixed current I 4.5 mA
(HART multidrop mode), a voltage of U 11.5 V is sufficient throughout the entire range of ambient temperatures.
e
For ambient temperatures Ta -20 °C (-4 °F) a minimum voltage of 16 V is required for the startup of the device at the MIN error
current (3.6 mA).
1
Feature "Electrical Output" of the product structure, option IH
30
2014-10
Loading...
+ 82 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.