Inductive positioning system PMI810-F110-IU-V1
Technical data
General specifications
Switching element function analog, current or voltage output
Object distance max. 6 mm
Measurement range 0 ... 810 mm
Nominal ratings
Model Number
PMI810-F110-IU-V1
Features
• Analog output 0 V ... 10 V/4 mA ...
20 mA
• Measuring range 0 ... 810 mm
Operating voltage U
Reverse polarity protection reverse polarity protected
Linearity error ± 0.8 mm
Repeat accuracy R ± 0.4 mm
Resolution 950 µm
Temperature drift ± 1 mm (-25 °C ... 70 °C)
No-load supply current I
Operating voltage indicator LED green
Functional safety related parameters
MTTFd 120 a
Mission Time (TM) 20 a
Diagnostic Coverage (DC) 0 %
Analog output
Output type 1 current output: 4 ... 20 mA
Load resistor current output: ≤ 400 Ω
Short-circuit protection voltage output: pulsing
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Connection type 4-pin, M12 x 1 connector
Housing length L 850 mm
Degree of protection IP65
Material
Housing PA 6 / AL
Target mild steel, e. g. 1.0037, SR235JR (formerly St37-2)
Note The data relating to accuracy only apply to a distance to the
Compliance with standards and
directives
Standard conformity
Standards EN 60947-5-2:2007
Approvals and certificates
UL approval cULus Listed, General Purpose, Class 2 Power Source
CCC approval CCC approval / marking not required for products rated ≤36 V
B
0
18 ... 30 V DC
≤ 70 mA
1 voltage output: 0 ... 10 V
voltage output: ≥ 1000 Ω
object to be detected of 1 ... 6 mm.
The path measurement system must be secured at 20 cm
intervals to prevent mechanical load.
IEC 60947-5-2:2007
Dimensions
0V/4mA
L17
10V/20mA
41 ± 0.15
30.5
8 ± 0.15
Release date: 2012-05-14 13:37 Date of issue: 2016-05-03 197524_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
1

Inductive positioning system PMI810-F110-IU-V1
Electrical Connection
IU
1
Pinout
(BN)
4
(BK)
I
I
Core colours in accordance with
EN 60947-5-2.
2
(WH)
U
3
(BU)
+ UB
4 - 20 mA
0 - 10 V
- UB
1
2
Wire colors in accordance with EN 60947-5-2
1 BN
2 WH
3 BU
4 BK
(brown)
(white)
(blue)
(black)
4
3
Accessories
BT-F110-G
Damping element for F110 housing sensors; front screw holes
BT-F110-W
Damping element for F110 housing sensors; lateral screw holes
V1-G-2M-PVC
Female cordset, M12, 4-pin, PVC cable
MH-F110
Mounting bracket for mounting F110 series sensors
Instruction manual
• Security advice
Warn ing
• Sensor Properties
The inductive positioning system F110 provides both, a current and voltage signal at the outputs, which is
proportional to the position of the attenuating element.
Output signals: 4 mA ... 20 mA and 0 V ... 10 V
• Attenuating element
The inductive position encoding system F110 is optimally
adjusted to the geometry of the attenuating elements we offer
(see accessories, below).
Note
• Installation and operation
This product must not be used in applications, where safety of persons
depend on the correct device function.
This product is not a safety device according to EC machinery directive.
≥ 41
When using your own attenuating elements, you
must ensure that the active surface of the attenuating element has a width of exactly 13 mm and
overlaps the entire sensor width (41 mm).
A different width has a direct impact on the achievable resolution and accuracy of the system.
Spacing between sensor and attenuating element is from 0 ... 6 mm.
Sensing accuracy is guaranteed between 1 ... 6 mm..
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
13
≥ 4
2