Pepperl Fuchs P-LB-1.E.23 DATASHEET

Surge Protection Barrier

P-LB-1.E.23

(2)
(3)
2
3
Zone 2Zone 0, 1, 2
Germany: +49 621 776 2222Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0002 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com
P-LB-1.E.23
1-channel
<
Plugs directly in to field side of KF modules
<
Analog or digital signal inputs
<
Surge protection up to 10 kA
<
Protects leads 2 and 3 of KF modules
<
<

Function

This Surge Protection Barrier is designed for use with K-System (KF modules). By simply snapping the barriers into a standard KF module, the modules are safely protected against voltage surges of different origin (e. g. lightning stroke, switching impulse, etc.). This is achieved by diverting the transient current to ground and limiting the signal line voltage to a safe level for the duration of the surge. The end digits of the model designation correspond to the protected terminals of the respective KF module. For additional information, refer to the manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must always be connected to a solid and effective ground and be at the same equipotential level as the instrument it is protecting. The ground system must comply with all applicable regulations.

Connection

Technical Data

General specifications
Number of protected signal lines 2
Signal lines
Connection terminals 2, 3
Rated voltage U
Rated current I
Leakage current max. 5 µA
On-state voltage max. 45 V
Ground insulation max. 500 V breakdown voltage
Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 103645_eng.pdf
B
B
max. 30 V
max. 250 mA
1
Surge Protection Barrier P-LB-1.E.23
Germany: +49 621 776 2222Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0002 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com

Technical Data

Conformity
Degree of protection IEC 60529:2001
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection IP20
Mass approx. 70 g
Dimensions 20 x 62 x 115 mm (0.8 x 2.4 x 4.5 inch)
Mounting on the KF module
Data for application in connection with hazardous areas
EU-Type Examination Certificate PTB 02 ATEX 2044
Marking 1 II (1)G [Ex ia Ga] IIC
Voltage U
Current I
Internal capacitance C
Internal inductance Li 200 µH
Maximum leakage current 10 kA (8/20 µs) per conductor
Nominal response time
Symmetrical 1 ns
Asymmetric 100 ns
Series resistor ≤ 0.5 Ω per wire
Bandwidth ≥ 40 kHz
Certificate PF 16 CERT 3908 X
Marking 1 II 3G Ex nA IIC T4 Gc
Directive conformity
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
IECEx approval
IECEx certificate IECEx BAS 12.0123
IECEx marking [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Standards IEC 60079-0:2011 , IEC 60079-11:2011
General information
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals
30 V
i
250 mA
i
negligible
i
where applicable. For information see www.pepperl-fuchs.com.
Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 103645_eng.pdf