With regard to the supply of products, the current issue of the following document is applicable: The
General Terms of Delivery for Products and Services of the Electrical Industry, published by the Central
Association of the Electrical Industry (Zentralverband Elektrotechnik und Elektroindustrie (ZVEI) e.V.)
in its most recent version as well as the supplementary clause: "Expanded reservation of proprietorship"
4.2UL Control Drawing ..................................................................................... 55
2020-04
3
VisuNet GXP
Introduction
1Introduction
1.1Content of this Document
This document contains information that you need in order to use your product throughout the
applicable stages of the product life cycle. These can include the following:
•Product identification
•Delivery, transport, and storage
•Mounting and installation
•Commissioning and operation
•Maintenance and repair
•Troubleshooting
•Dismounting
•Disposal
Note
This document does not substitute the instruction manual.
Note
For full information on the product, refer to the instruction manual and further documentation on
the Internet at www.pepperl-fuchs.com.
The documentation consists of the following parts:
•Present document
•Instruction manual
•Datasheet
Additionally, the following parts may belong to the documentation, if applicable:
•EU-type examination certificate
•EU declaration of conformity
•Attestation of conformity
•Certificates
•Control drawings
•Additional documents
1.2Target Group, Personnel
Responsibility for planning, assembly, commissioning, operation, maintenance, and dismounting lies with the plant operator.
Only appropriately trained and qualified personnel may carry out mounting, installation, commissioning, operation, maintenance, and dismounting of the product. The personnel must have
read and understood the instruction manual and the further documentation.
Prior to using the product make yourself familiar with it. Read the document carefully.
4
2020-04
VisuNet GXP
Introduction
1.3Symbols Used
This document contains symbols for the identification of warning messages and of informative
messages.
Warning Messages
You will find warning messages, whenever dangers may arise from your actions. It is mandatory
that you observe these warning messages for your personal safety and in order to avoid property damage.
Depending on the risk level, the warning messages are displayed in descending order as follows:
Danger!
This symbol indicates an imminent danger.
Non-observance will result in personal injury or death.
Warning!
This symbol indicates a possible fault or danger.
Non-observance may cause personal injury or serious property damage.
Caution!
This symbol indicates a possible fault.
Non-observance could interrupt the device and any connected systems and plants, or result in
their complete failure.
Informative Symbols
Note
This symbol brings important information to your attention.
Action
This symbol indicates a paragraph with instructions. You are prompted to perform an action or
a sequence of actions.
2020-04
5
VisuNet GXP
Product Description
2Product Description
2.1Overview
The Pepperl+Fuchs VisuNet Remote Monitors GXP RM-GXP1100-19S*/RM-GXP1200-19S*
and PC-GXP-1100-19S*/PC-GXP-1200-19S* are ATEX/IECEx certified, UL listed devices
intended for use in potentially explosive atmospheres, such as Zones 1/21, 2/22 and Class I
Div. 2, Class II Div. 2, and Class III.
The VisuNet GXP serves as a thin client- or PC-based operator workstation that uses standard
Ethernet technology to transmit process information from a process control or manufacturing
execution system into hazardous areas.
The assembly consists of several core devices that can be exchanged by the customer:
•The display units DPU1100-* and DPU1200-* are display panels with optional 10-finger
multi-touch sensors. The displays and touch-sensors are optically bonded with the hardened front glass.
•The thin client units TCU1100-* and TCU1200-* are computing units running the latest
Pepperl+Fuchs RM Shell 5.x or RM Shell 4.x firmware. They allow connectivity to various
host systems in the safe area using standard Ethernet technology. The computing units
PCU1100-* and PCU1200-* run an open Microsoft® Windows® operating system, allowing installation of any software, such as SCADA packages.
•The power supply units PSU1100-* and PSU1200-* provide the above-listed devices with
24 V DC power. They are available as DC and AC versions.
As the standard mounting option, a bezel is available that allows the panel to be mounted into a
system housing or cabinet that needs to be ordered separately. The panel can also be flushmounted into a cabinet from behind.
2020-04
6
VisuNet GXP
1
2
3
4
Product Description
VisuNet GXP Panel Components
Figure 2.1VisuNet GXP panel components
1Bezel for housing and panel mounting
2Computing unit (TCU or PCU): processor, SSD and memory, Ex circuits,
interface modules
3Power supply unit: DC or AC option, backpacked (panel-mount) or stand-
alone (in system enclosure)
4Display unit: display, touch screen, hardened front glass
2020-04
7
VisuNet GXP
Product Description
VisuNet GXP Pedestal Mounted with Keyboard/Mouse
Figure 2.2VisuNet GXP system mounted in AG1 Housing with Pedestal5 -1458-* and EXTA2
keyboard/mouse (ordered separately)
Note
For a description of the product model nomenclature, see the VisuNet GXP PC or VisuNet GXP
RM product datasheets at www.pepperl-fuchs.com.
For more mounting options and information, see the datasheet "Mounting Options
'StandardLine' and 'BasicLine'".
2020-04
8
VisuNet GXP
Product Description
2.2Technical Specifications
Technical Data RM-GXP*
Hardware
ProcessorIntel® Atom™ Bay Trail E3827 1.75 GHz
RAM2048 MB DDR3L
Mass storage32 GByte industrial grade MLC SSD
Software
Operating systemVisuNet RM Shell 5.x (based on Microsoft®
Interface type1 x Ethernet 100/1000BASE-TX (Ex e) or
1 x fiber optic 1000BASE-SX (Multimode) or
1 x fiber optic 1000BASE-LX (Singlemode)
1 x USB 2.0 (Ex e)
2 x USB 1.1 (Ex i; intended for Pepperl+Fuchs
keyboard and mouse)
1 x DC or AC power in (via power supply unit)
Optional:
1 x barcode reader interface Pepperl+Fuchs
Pscan-D/B (Ex i)
"interface 3": 1 x barcode reader interface for
wired 1-D scanners IDM-160-D*, IDM-Z1160-D-* and base station IDMx61-B-* and
IDM-Z1-x61-B-*
"interface 4": 1 x barcode reader interface for
wired 2-D Scanner IDM-Z1-260-D-* (Ex i)
"interface 5": 1 x RS-232 interface with Power
Supply for miscellaneous devices and peripherals (Ex i)
1 x RS-232 (Ex e)
1 x RS-485 (Ex e)
1 x Ethernet 100/1000Base-TX (Ex e)
Bluetooth v4.0, communication distance up to
30 m in open terrain, transmission power +8
dBm, transmission frequency 2.402 ... 2.48
GHz
panel with AC: 524 mm x 453 mm x 137 mm
panel with AG1 housing: 582 mm x 490 mm x
224 mm
•Thin Client Units TCU1100-J1-* and TCU1200-J2-*
•Computing Units PCU1100-J1-* and PCU1200-J2-*
Marking
ATEX
RM-GXP1100-J1-*
RM-GXP1200-J2-*
IECEx
RM-GXP1100-J1-*Ex eb q ib [ib] IIC T4 IP66 Gb
RM-GXP1200-J2-*Ex ec [ib] q IIC T4 IP66 Gc
II 2G Ex eb q ib [ib] IIC T4 IP66 Gb
II 2D Ex tb [ib] IIIC T85°C IP66 Db
II 3G Ex ec [ib] q IIC T4 IP66 Gc
II 3D Ex tc [ib] IIIC T85 °C IP66 Dc
Ex tb [ib] IIIC T85°C IP66 Db
Ex tc [ib] IIIC T85 °C IP66 Dc
UL Marking
2020-04
11
VisuNet GXP
582
490
1702
228
475
1100
Product Description
2.3Dimensions
Dimensions with AG1 Housing and Pedestal
Figure 2.3Dimensions with StandardLine Pedestal5-1458-Fix and EXTA2 keyboard/mouse—sample
configuration
Note
Keyboard/mouse and pedestal are ordered separately.
12
2020-04
VisuNet GXP
524
137
453
499
480
167
419
400
270
Ø 6.5
± 0.5 (14 x)
Product Description
Panel Dimensions with Bezel
Panel Cut-Out Dimensions
Cut-out dimensions: 480 x 400 mm. For more information, see chapter 3.5.
2020-04
13
VisuNet GXP
490
582
583
62
532
285
686
413
Product Description
Wall Mount Dimensions
Figure 2.4Wall mount dimensions with additional wall brackets (#198768)
2.4Disposal
Follow all local and any other requirements for disposing of electronic equipment. When disposing of any system component, mark VOID across all certification labels.
2020-04
14
VisuNet GXP
Mechanical Installation
3Mechanical Installation
3.1General Installation Requirements
Observe the following requirements when installing the system components.
•The equipment must be installed by competent personnel in accordance with the instruc-
tions. National laws and regulations must be observed.
•The building installation must provide a 20 A overcurrent protection.
•The installer must make a readily accessible disconnect device available.
•The safety of any system incorporating the power supply unit is the responsibility of the
assembler of the system.
3.2Installation Tools
•4-mm and 5-mm torque Allen keys
•Open-ended wrench for cable glands
•Screws for floor or wall mounting. Choose the appropriate screws based on the mounting
conditions.
•Small cable ties
•Side cutters
•Strong adhesive tape, such as duct tape or packing tape
•At least 1 piece of thin, 2.5-m-long wire for pulling cables through the pedestal
Warning!
Risk of injury
Lifting the device on your own may lead to injury.
Do not attempt to lift the device on your own. Use a crane or have another person help you.
2020-04
15
VisuNet GXP
Mechanical Installation
3.3System Installation
3.3.1Preparation for System Installation
Warning!
Proper installation on the floor
It is the installer's responsibility to select a suitable location with sufficient strength to hold the
equipment. It is the installer's responsibility to select the proper screws based on the installation conditions.
Warning!
Distance between housing and wall
Provide at least 350 mm of space between the housing/pedestal assembly and the left wall.
This is required in order to properly open the housing and connect the GXP components.
16
Figure 3.1Distance required between housing/pedestal assembly and wall
2020-04
VisuNet GXP
400
180180
300
250
140
130
130
20
40
Ø 100
Ø 10
071
031
130
170
90
45°
1
0
5°
5°
184
Mechanical Installation
StandardLine Pedestal Floor-Mount Hole Pattern
BasicLine Pedestal Floor-Mount Hole Pattern
3.3.2Preparing the GXP Panel/Housing
The VisuNet GXP comes pre-assembled and consists of the core components display unit,
power supply unit, and thin client unit / power supply unit. If the AG1 housing option is chosen,
the panel is pre-mounted in the housing.
Required Components
•1 x pre-assembled VisuNet RM-GXP or PC-GXP panel (option: panel-mounted into AG1
housing)
2020-04
•2 x protective tubes
•Screws for housing
•EXTA2 keyboard and PEDESTAL5-xxxx-* (ordered separately)
Warning!
Risk of injury
Handling the devices with bare hands may cut fingers, hands, or wrists.
Wear gloves at all times during the installation process.
17
VisuNet GXP
Mechanical Installation
Warning!
Risk of injury
Lifting the GXP housing on your own may cause injury.
Do not attempt to lift the device on your own. Use a crane or have another person help you.
Warning!
Danger resulting from scratched display unit screen
Scratches on a display unit front screen weaken the glass structure and may result in broken
glass. Explosion protection is no longer ensured if a display unit with a scratched screen is
used.
NEVER use a display unit with a scratched front screen in a hazardous area. If the surface is
damaged in any way, return the display unit to Pepperl+Fuchs at once and replace it with a new
one.
Preparing the Housing
1.
Remove the box and leave the protective foam blocks on the housing. Save the uncollapsed
box for further mounting steps.
2.
Wrap strong adhesive tape around the foam blocks to hold them onto the housing and protect
the components during mounting.
18
3.
Place the housing face down on a flat surface.
2020-04
VisuNet GXP
Mechanical Installation
4.
Remove and discard the screws from the bottom of the housing.
2020-04
19
VisuNet GXP
1
2
3
Mechanical Installation
3.3.3Preparing the StandardLine Pedestal
A variety of pedestals are available for floor mounting. For a complete list of available mounting
options, see the mounting options datasheet. Pedestals are shipped with an attached protective earth (PE) wire and screws for mounting the VisuNet GXP AG1 housing to the pedestal: 6 x
M8 countersunk screws and 2 x M6 countersunk screws.
StandardLine Pedestal
1Pre-installed PE wire
2Top cable opening
3Cable glands
2020-04
20
VisuNet GXP
1
2
3
4
Mechanical Installation
Bottom of Pedestal
1PE stud
2M25 opening
3M20 opening
4M20 plug
Warning!
Connection to the PE stud
Connection to the PE stud is mandatory.
Opening SizeWrench SizeCable DiameterTorque
M2024 mm7 ... 13 mm12 Nm
M2529 mm9 ... 17 mm
Preparing the Pedestal for Connection to the GXP Housing
1.
Remove the cable glands at the bottom of the pedestal.
2.
Feed the pull wire (thin, 2.5-m-long wire for pulling cables through pedestal) through the top of
the pedestal and out the appropriate cable entry.
3.
Put the gland nut and ferrule of the cable gland on the cable and slide them a few meters down
the length of the cable away from the pedestal. Keep the nut and ferrule on the cable in order to
tighten them in a later installation step.
2020-04
21
VisuNet GXP
Mechanical Installation
4.
Attach the cable to the pull wire.
22
2020-04
VisuNet GXP
Mechanical Installation
5.
Pull the cable through the cable entry and out the top of the pedestal.
6.
Pull the cable through the pedestal so that 50 cm of cable is hanging out of the top of the
pedestal.
7.
Repeat the preceding steps for each cable that must be routed through the pedestal.
2020-04
23
VisuNet GXP
Mechanical Installation
3.3.4Attaching the Pedestal to the Housing
Warning!
Risk of injury
Lifting the GXP housing on your own may cause injury.
Do not attempt to lift the device on your own. Use a crane or have another person help you.
Mounting the Pedestal
1.
Rest the pedestal on the box that the GXP housing was shipped in. Position the pedestal and
box behind the housing.
2.
Slide the cable ends from the top of the pedestal through the openings in the bottom of the
housing.
24
Warning!
Damage to cables
The cables may become damaged if they are pinched between the pedestal
and the housing.
Ensure that the cables do not get caught between the pedestal and housing
during the mounting process.
3.
Align the mounting holes on the top of the pedestal with the mounting holes on the back of the
housing.
2020-04
VisuNet GXP
Mechanical Installation
4.
Tighten the 6 x M8 screws in a criss-cross pattern to 20 Nm.
5.
Tighten the 2 x M6 screws to 12 Nm.
2020-04
25
VisuNet GXP
Mechanical Installation
Positioning and Floor-Mounting the GXP
1.
Remove the box from under the pedestal and carefully position the system upright on the floor
with a crane or the help of another person.
26
2.
Mount the pedestal onto the floor using suitable screws.
Warning!
Proper floor mounting
It is the installer's responsibility to select a suitable location with sufficient
strength to hold the equipment. It is the installer's responsibility to select the
proper screws based on the installation conditions.
3.
Remove the protective foam blocks.
4.
Remove the protective plastic film from the screen. This should not be present in a hazardous
location.
Note
For more information on floor mounting, including hole patterns, see see chapter 3.3.1.
Note
The StandardLine pedestal is depicted above. Follow the same steps to mount the VisuNet
GXP with the BasicLine pedestal.
2020-04
VisuNet GXP
Mechanical Installation
3.3.5Opening the Housing
The GXP housing is hinged and opens to the left.
Opening the GXP
Warning!
Risk of Damage and Injury
Opening the GXP housing before the pedestal is mounted onto the floor may
cause the housing and pedestal to tip over.
Mount the pedestal to the floor before opening the GXP housing.
1.
Loosen the 4 screws on the back of the housing.
2.
Gently pull the front side of the housing toward you.
2020-04
27
VisuNet GXP
Mechanical Installation
3.
Pull the right side of the housing front away from the back part of the housing.
28
2020-04
VisuNet GXP
Mechanical Installation
3.3.6Grounding the Housing to the Pedestal
Warning!
Customer responsibility to verify grounding path
Check the grounding path after completing system installation.
The AG1 housing comes with a pre-installed PE wire that is connected from the inside-top of
the housing to the inside-back of the housing. The pedestal comes with a pre-installed PE wire
that you must route from the pedestal into the housing (see see chapter 3.3.3).
Connecting the PE Wires
1.
Remove the nuts and washers from the PE stud on the inside-back of the AG1 housing.
2.
Connect the pre-installed PE wires from the the housing and pedestal to the PE stud.
2020-04
29
VisuNet GXP
Mechanical Installation
3.
Replace the nuts and washers. Fasten the nuts and washers with a torque of 7.5 Nm.
30
Figure 3.2Grounding Concept
1Housing
2PE stud (hexagon socket)
3Contact washer
4Nut
5Cable lug
6Flat washer
7Spring washer
8Nut
2020-04
VisuNet GXP
Mechanical Installation
3.3.7Mounting the Keyboard
1.
Remove the plug and screws from the bottom of the housing
2.
To remove the plug, open the housing (see see chapter 3.3.5). Hold the the inside nut while
removing the plug from the outside with a flat-head screwdriver.
2020-04
31
VisuNet GXP
Mechanical Installation
3.
Pull the keyboard wire through the plug and tighten the screws to 4.5 Nm.
Note
The keyboard is an intrinsically safe device. Refer to the control drawings and relevant
installation requirements.
For proper electrical termination of the keyboard, refer to the TCU/PCU and EXTA2 keyboard
manuals.
32
2020-04
VisuNet GXP
Mechanical Installation
3.3.8Mounting the Scanner Holder to the AG1 Housing
Required Installation Tools
•Size 3 hex wrench
•Safety gloves
All tools should be torque controlled if a torque is specified.
Figure 3.3#548268 scanner holder compatible with AG1 housing
2020-04
33
VisuNet GXP
Mechanical Installation
Mounting the Scanner Holder
1.
Open the AG1 housing. See chapter 3.3.5
2.
Remove the screws on the right side of the AG1 housing.
34
3.
Affix the barcode reader using the screw included in delivery with the barcode reader holder.
4.
Use a hex key to put the first screw (with lock washer and sealing washer) through the drilled
hole on the right side of the AG1 housing.
5.
Press the scanner holder against the housing from the outside. Fasten the screw using a torque
of 6 Nm.
6.
Use the hex key to put the second screw (with lock washer and sealing washer) through the
drilled hole on the right side of the AG1 housing. Fasten the screw using a torque of 6 Nm.
The scanner holder is now attached to the housing.
2020-04
VisuNet GXP
Mechanical Installation
Follow the same steps to mount the holder bracket-AG1-IDMx61-B-N0 for the IDM base station
(#548395) to the AG1 housing.
2020-04
35
VisuNet GXP
Mechanical Installation
36
Figure 3.4Technical drawing - dimensions with scanner holder.
2020-04
VisuNet GXP
Mechanical Installation
Figure 3.5Dimension drawing with holder bracket
3.3.9Installing the Handheld 1-D/2-D Code Reader
Required Components
•S3 or S4 Interface (thin client / PC-unit)
•DATL-IDM-DB-S-XX00-N0
•CBL-IDMx60-D-J1-S-S18-N0 or CBL-IDMx60-D-J1-S-C38-N0
•IDM-Z1-160-D-1D-J1-*, IDM-160-D-1D-J1-*, IDM-Z1-260-D-2D-J1-S1-N-N0, or IDM-Z1-
x61-*, IDM-x61-* in combination with required Bluetooth handheld barcode reader
•Optional: SCANNER-HOLDERU1-AG1-N0 or HOLDER-BRACKET-AG1-IDMx61-B-N0
2020-04
37
VisuNet GXP
Mechanical Installation
Required Installation Tools
•Flat head screwdriver
•19 mm socket wrench for counter nut and connector
•Size 2.5 hex wrench for cable tie screws
•Safety gloves
All tools should be torque controlled if a torque is specified.
and 2-D scanner IDM-Z1-260-D-2D-J1-S* (S4-interface required) 4-wire with
ferrules—IDM scanner connection via M12 connector.
Note
Supports only RS-232 scanner / base station
2020-04
VisuNet GXP
Mechanical Installation
Installing the cable DATL-IDM-DB-S-XX00-N0
1.
Open the AG1 housing. See chapter 3.3.5
2.
Remove the plug at the bottom-right side of the housing by holding the screw steady from
below with a screwdriver while loosening the screw from above with a wrench.
2020-04
39
VisuNet GXP
Mechanical Installation
3.
Guide the open wire end of the cable DATL-IDM-DB-S-XX00-N0 through the hole.
40
4.
Place the M16 counter nut over the end of the cable.
2020-04
VisuNet GXP
Mechanical Installation
5.
Pull the socket into the housing and tighten it with the M16 counter nut. Tighten the nut with a
torque of 5 Nm.
6.
Protect the cable from mechanical damage by fastening it with a cable tie.
2020-04
41
VisuNet GXP
Mechanical Installation
7.
Route the cable through the cable gland on the TCU/PCU. Install the wire ends per the tables
below.
Wiring Guide
DATL-IDM-DB-S-XX00-N0 to IDM-Z1-160* and Base Station IDM-Z1-x61-B-N0* Ex i
TCUCable
TerminalSignal
Xx.1VccSupplyVccgreen1
Xx.2GNDSupplyGNDbrown3
Xx.3-----
Xx.4-----
Xx.5-----
Xx.6RxDITxDwhite4
Xx.7-----
Xx.8-----
NameDirectionAssignmentColor codingPin M12 con-
nector
DATL-IDM-DB-S-XX00-N0 to IDM-Z1-260*
TCUCable
TerminalSignal
NameDirectionAssignmentColor codingPin M12 con-
Xx.1UsSupplyVccgreen1
Xx.2RxDITxDwhite4
Xx.3-----
Xx.4-----
Xx.5GNDSupplyGNDbrown3
Xx.6-----
Xx.7-----
Xx.8-----
Note
For detailed information on electrical installation, refer to the TCU/PCU and IDM* barcode
reader manuals.
nector
42
2020-04
VisuNet GXP
Mechanical Installation
Connecting the IDM* Barcode Reader
Connect the plug (M12 male connector) of the barcode reader to the socket and tighten it
firmly.
Coded Plug and Socket
Figure 3.7The plug and socket are coded. Match the coding on the plug and socket before tightening.
3.4Replacing a VisuNet EX1 with the 19-Inch VisuNet GXP
General Requirements
•Deenergize the machine or plant.
•Ensure that there are no combustible gases in the installation area while the VisuNet sys-
tem is being dismantled.
Warning!
External equipotential bonding
The housing must be provided with external equipotential bonding. The equipotential bonding
conductor must have a minimum cross section of 4 mm 2 and be as short as possible. It must
remain connected until the device has been completely dismantled.
Warning!
Waiting period after disconnecting supply voltage
Wait three minutes after disconnecting the supply voltage before opening the Ex e terminal
compartments. Internal capacitors could otherwise still be charged, leading to an explosion in
the event of a short circuit. If the Ex e terminal compartment is open, the explosion protection is
no longer effective.
2020-04
43
VisuNet GXP
Mechanical Installation
3.4.1Removing VisuNet EX1 from AG1 Housing
Required Installation Tools
•3-mm wide flat head screwdriver
•Phillips head screwdriver
•Cable gland installation tool
•Ratchet strap or, preferably, a second person to help you
•Socket wrench extension with size 10 magnetic socket for EX1 nuts
•Safety gloves
•Size 5 hex wrench for housing screws
•Size 10 socket wrench for ground bolt
All tools should be torque controlled if a torque is specified.
Removing the VisuNet EX1
1.
Disconnect the supply voltage (24 V DC) for the VisuNet supply line (X1).
2.
Open the AG1 housing. See chapter 3.3.5
3.
Wait at least three minutes, then open the Ex e terminal compartment X1.
4.
Open terminals 1 and 2 in terminal compartment X1.
5.
Open the cable gland and disconnect the supply voltage cable.
6.
Loosen all other cables in terminal compartments X1 and X2, then open the cable glands and
disconnect the cables.
7.
Seal all open cable glands in terminal compartment X1 with an Ex e-compatible plug, then
tighten the glands securely.
44
8.
Close the covers of the Ex e and Ex i terminal compartments and ensure that they are tightly
sealed in accordance with regulations.
9.
Disconnect the equipotential bonding conductor between the AG1 housing and the VisuNet
EX1.
10.
To prevent the VisuNet EX1 from falling to the floor, either secure the EX1 with a ratchet strap
prior to loosening the self-locking nut, or ask a second person to help you remove the EX1.
2020-04
VisuNet GXP
Mechanical Installation
11.
Remove the VisuNet EX1 from the AG1 housing. Be sure to wear safety gloves to protect your
hands.
Warning!
Risk of damage
When setting the VisuNet EX1 down, do not rest the EX1 on the edge of the front plate.
2020-04
45
VisuNet GXP
Mechanical Installation
3.4.2Installing VisuNet GXP into AG1 Housing
Required Components
•VisuNet GXP 19-inch prepared for panel mounting (S2 option)
•AG1 housing
Required Installation Tools
•3-mm wide slot head screwdriver
•Phillips head screwdriver
•Cable gland installation tool
•Tools for preparing cables (wire stripper, crimp tool, and wire end ferrules
•Ratchet strap or, preferably, a second person to help you
•Socket wrench extension with size 10 magnetic socket for housing nuts
•Size 5 hex wrench for housing screws
•Size 8 socket wrench for ground bolt
•Methylated spirit or cold cleaner
•Safety gloves
All tools should be torque controlled if torque is specified.
46
2020-04
VisuNet GXP
Mechanical Installation
Installing the VisuNet GXP
1.
Connect the AG1 housing to an external equipotential bonding conductor.
2.
Close the AG1 housing, but do not yet insert the screws to fasten the housing closed.
3.
Insert the 19-inch VisuNet GXP into the opening of the AG1 housing. Be sure to wear safety
gloves to protect your hands.
4.
Ensure that no foreign bodies are attached either to the front plate of the VisuNet GXP or to the
connection surface of the AG1 housing. If necessary, clean the surfaces with methylated spirit
or cold cleaner before installing the VisuNet GXP.
5.
While securing the VisuNet GXP housing to prevent it from falling, swing the AG1 front housing
sideways along with the GXP.
Note
Check the surrounding seal of the front plate for damage before installing the
VisuNet GXP.
6.
Tighten the self-locking nuts onto the threaded pins on the front plate using the magnetic
wrench.
7.
Connect the equipotential bonding conductor between the AG1 housing and the VisuNet GXP.
2020-04
47
VisuNet GXP
V+
V+
GND
GND
VCC
D-
D+
GND
.1TX+/D1+
.2TX-/D1-
.3D3+
.4D3-
.5RX+/D2+
.6RX-/D2-
.7D4+
.8D4-
.1
.2
.3
.4
.5
.6
.7
.8
Power Supply
+24 VDC
USB Ex e
Ethernet Ex e
X1
VCC
D-
D+
GND
VCC
D-
D+
GND
.1
.2
.3
.4
.5
.6
.7
.8
USB Ex iUSB Ex i
X3
X2
.1
.2
.3
.4
.5
.6
.7
.8
.1
.2
.3
.4
.5
.6
.7
.8
Optional Modules
X4
X5
Terminal Compartment Ex eTerminal Compartment Ex iTerminal Compartment for optional modules
TTY, Ethernet, RS-232, or RS-485
TX
RX
Fiber
Optic
Mechanical Installation
8.
Wire the terminal compartments as described in the VisuNet TCU/PCU manual.
Figure 3.8Terminal compartments
9.
Close the covers of the terminal compartments and ensure that they are tightly sealed in
accordance with regulations
10.
Close the AG1 housing.
11.
Start up the VisuNet GXP and test all connected components.
1. Switch on the power supply.
2. Check the functions of the VisuNet RM/PC, e.g., the display, external keyboard, and
mouse.
3. Switch on the machine or plant.
4. Check the functions of the machine or plant.
48
2020-04
VisuNet GXP
Mechanical Installation
3.5Panel Mount Installation
Warning!
Proper installation
It is the installer's responsibility to select a suitable location with sufficient strength to hold the
equipment. It is the installer's responsibility to select the proper screws based on the installation conditions.
Required Components
•VisuNet GXP 19 inch bezel prepared for panel mounting or mounting into AG1 housing
(S2 option, 14 x M6 bolts included)
•No kit for panel mounting required, no panel mount bracket required
Required Installation Tools
•Safety gloves
•Loctite® Threadlocker Blue 243®
•Size 8 socket wrench for ground bolt
•Size 10 socket wrench for mounting nuts
•Appropriate tools (6.5 mm drill size) for creating the cutout
All tools should be torque controlled if a torque is specified.
If the panel mount option (S2) is chosen, no additional kit for panel mounting is required. You
will receive a pre-assembled package consisting of a display unit, a computing unit, and a
2020-04
power supply unit.
49
VisuNet GXP
499
480
167
419
400
270
Ø 6.5
± 0.5 (14 x)
Mechanical Installation
Note
If installing the device in a different housing, ensure that the operating temperature is within the
specified range or up to +50 °C.
The panel mount option is mounted from the front and placed outside the wall surface. The
monitor protrudes slightly and is exposed.
The maximum wall thickness for panel mount installation with the VisuNet GXP is 10 mm.
Use the drilling pattern below to drill holes into the surface in which the panel is to be mounted.
Use the included bolts to fasten the panel into the wall. Tighten all bolts with a torque of 4 Nm.
Drilling Pattern
Figure 3.9The cut-out dimensions for the VisuNet GXP 19-inch are 480 x 400 mm.
2020-04
50
VisuNet GXP
Mechanical Installation
Flush Mount Installation
The 19-inch VisuNet GXP can also be flush mounted. With this mounting option (-NN), no
bezel is installed, and the monitor is recessed into the installation surface. This mounting must
be done from the back of the housing, and the fitting is kept inside the surface of the wall. The
cutout dimensions and stud location must match those on the GXP exactly.
Figure 3.10VisuNet GXP flush mounted
Note
For more options and accessories, contact your local Pepperl+Fuchs sales representative.
2020-04
51
VisuNet GXP
490
582
583
62
532
285
686
413
Mechanical Installation
3.6Wall Mount Installation
Warning!
Proper installation
It is the installer's responsibility to select a suitable location with sufficient strength to hold the
equipment. It is the installer's responsibility to select the proper screws based on the installation conditions.
Required Components
•19-inch VisuNet GXP prepared for wall mounting (front opening of the AG1 housing H2
option)
•Wall bracket adapter for wall mounting installation compatible with AG1 housing
Mounting options for Zone
1/21 hazardous locations
reader for Zone 1/21
held reader for Zone 1/21
Z1-60-D-* barcode readers to
the VisuNet GXP
Length: 1.8 m
x60-D-* barcode readers to
the VisuNet GXP
Length: 3.8 m
Scanner holder compatible
with AG1 housing
Material: stainless steel AISI
316L (1.4404)
Compatible with IDM-Z1-6x,
IDM-6x, ecom Ident-Ex 01,
and PSCAN
Prepared for mounting to right
side of housing
Bracket to mount IDM-Z1-61*, IDM-x61-* base station to
AG1 housing
Material: stainless steel AISI
304 (1.4301)
Assembly: right side of AG1
housing
Includes bracket and installation materials
Note: base station and cables
not included!
54
Note
For more options and accessories, contact your local Pepperl+Fuchs sales representative.
2020-04
VisuNet GXP
This document contains safety-relevant information. It must not be altered without the authorization of a NE EX
Only valid as long as released in EDM
date: 2017-AUG-28
Control Drawing for GXP Sysytem and TCU or PCU No n-incendive Outputs
Class I, Division 2, Groups A, B, C, D; T4
Class II, Division 2, Groups F, G; T4
Class III
Class I Zone 2, Group IIC; T4
Class II Zone 22, Group IIIB; T85°C
Class III Zone 22, Group IIIA; T85°C
Hazardous Location
Class I, Division 2, Groups A, B, C, D; T4
Class II, Division 2, Groups F, G; T4
Class III
Class I Zone 2, Group IIC; T4
Class II Zone 22, Group IIIB; T85°C
Class III Zone 22, Group IIIA; T85°C
Type 1
Type 2
Type 3
Notes
1. The Entity Concept allows interconnection of non-incendive apparatus with associated apparatus not specifically
examined in combination as a system when the approved values of Voc (or Uo) and Isc (or Io) for the associated
apparatus are less than or equal to Vmax (Ui) and Imax(Ii) for the non-incendive apparatus and the approved values of
Ca(Co) and La(Lo) for the associated apparatus are greater than Ci + Ccable and Li + Lcable, respectively, for the nonincendive apparatus,
Where Ccable= 60pF/ft if unknown
Where Lcable= 0.20uH/ft if unknown
2. Simple apparatus: an electrical component or combination of components of simple construction with well-defined
electrical parameters that does not generate more than 1.5 V, 100mA, 25mW, or is a passive component that does not
disipate more than 1.3W and is compatible with the intrinsic safety of the circuit in which it is used.
3. Wiring methods must be in accordance with all applicable installation requirements of the county in use. For US, this is
NFPA 70 (NEC) article 504 with additional information in ANSI-ISA –RP12.06.01. For Canada this is CSA 22.1-12 (CEC)
section 18 and appendix F.