Pepperl Fuchs NJ8-18GK-N-150 Data Sheet

Inductive sensor NJ8-18GK-N-150
Technical Data
General specifications
Switching function Normally closed (NC) Output type NAMUR Rated operating distance sn8 mm Installation non-flush Assured operating distance sa0 ... 6.48 mm
0102
Model Number
NJ8-18GK-N-150
Features
• Temperature range
-40 ... 150 °C (-40 ... 302 °F)
Reduction factor r Reduction factor rCu 0.3 Reduction factor r Output type 2-wire
Nominal ratings
Nominal voltage Uo8.2 V (Ri approx. 1 kΩ) Switching frequency f 0 ... 200 Hz Current consumption
Measuring plate not detected Measuring plate detected
Ambient conditions
Ambient temperature -40 ... 150 °C (-40 ... 302 °F)
Mechanical specifications
Connection type cable SIHF , 2 m Core cross-section 0.34 mm Housing material PPS Sensing face PPS Degree of protection IP65 Cable
Bending radius
General information
Use in the hazardous area see instruction manuals
Category
Compliance with standards and directives
Standard conformity
NAMUR
Standards
Approvals and certificates
EAC conformity TR CU 012/2011 UL approval cULus Listed, General Purpose CSA approval cCSAus Listed, General Purpose CCC approval CCC approval / marking not required for products rated 36 V
Dimensions
0.4
Al
0.85
304
3 mA 1 mA
2
> 10 x cable diameter
1G; 2G
EN 60947-5-6:2000 IEC 60947-5-6:1999 EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
Electrical Connection
BN
BU
M18x1
4
24
1
34,5
40
7
L+
L-
Release date: 2018-04-19 08:23 Date of issue: 2018-04-19 106466_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
1
Inductive sensor NJ8-18GK-N-150
Equipment protection level Ga
CE marking 0102
ATEX marking ¬ II 1G Ex ia IIC T6T1 Ga
Standards EN 60079-0:2012+A11:2013, EN 60079-11:2012
Appropriate type NJ8-18GK-N-150...
Effective internal inductivity C
Effective internal inductance L
Highest permissible ambient temperature Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
Special conditions
Equipment protection level Gb
CE marking 0102
ATEX marking ¬ II 1G Ex ia IIC T6T1 Ga
Standards EN 60079-0:2012+A11:2013, EN 60079-11:2012
Appropriate type NJ8-18GK-N-150...
Effective internal inductivity C
Effective internal inductance L
Maximum permissible ambient temperature T
Special conditions
Equipment protection level Da
CE marking 0102
ATEX marking ¬ II 1D Ex ia IIIC T135°C Da
Standards EN 60079-0:2012+A11:2013, EN 60079-11:2012
Appropriate type NJ8-18GK-N-150...
Effective internal inductivity C
Effective internal inductance L
Special conditions
i
i
i
i
i
i
The Ex-related marking can also be printed on the enclosed label.
Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions
70 nF ; a cable length of 10 m is considered.
50 µH ; a cable length of 10 m is considered.
temperature class, and the effective internal reactance values can be found on the EU-type examination certificate.
Note:
Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already
been applied to the temperature table for category 1.
The Ex-related marking can also be printed on the enclosed label.
Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions
70 nF ; a cable length of 10 m is considered.
50 µH ; a cable length of 10 m is considered.
Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
amb
temperature class, and the effective internal reactance values can be found on the EU-type examination certificate.
The Ex-related marking can also be printed on the enclosed label.
Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions
70 µF A cable length of 10 m is considered.
50 µH A cable length of 10 m is considered.
Release date: 2018-04-19 08:23 Date of issue: 2018-04-19 106466_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2