Inductive sensor |
NJ6-22-N |
|
|
|
|
0102
Model Number
NJ6-22-N
Features
•6 mm flush
•Usable up to SIL 2 acc. to IEC 61508
<![if ! IE]><![endif]>Release date: 2017-05-30 13:12 Date of issue: 2018-02-16 106456_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Technical Data
General specifications |
|
Normally closed (NC) |
Switching function |
|
|
Output type |
sn |
NAMUR |
Rated operating distance |
6 mm |
|
Installation |
sa |
flush |
Assured operating distance |
0 ... 4.86 mm |
|
Reduction factor rAl |
|
0.4 |
Reduction factor rCu |
|
0.3 |
Reduction factor r304 |
|
0.85 |
Output type |
|
2-wire |
Nominal ratings |
Uo |
8.2 V (Ri approx. 1 kΩ) |
Nominal voltage |
||
Switching frequency |
f |
0 ... 2000 Hz |
Hysteresis |
H |
1 ... 7 typ. 4 % |
Current consumption |
|
≥ 3 mA |
Measuring plate not detected |
|
|
Measuring plate detected |
|
≤ 1 mA |
Functional safety related parameters |
4566 a |
|
MTTFd |
|
|
Mission Time (TM) |
|
20 a |
Diagnostic Coverage (DC) |
|
0 % |
Ambient conditions |
|
-25 ... 100 °C (-13 ... 212 °F) |
Ambient temperature |
|
|
Mechanical specifications |
|
cable PVC , 2 m |
Connection type |
|
|
Core cross-section |
|
0.75 mm2 |
Housing material |
|
PBT |
Sensing face |
|
PBT |
Degree of protection |
|
IP68 |
Cable |
|
> 10 x cable diameter |
Bending radius |
|
|
General information |
|
see instruction manuals |
Use in the hazardous area |
|
|
Category |
|
2G; 3G |
Compliance with standards and |
|
|
directives |
|
|
Standard conformity |
|
EN 60947-5-6:2000 |
NAMUR |
|
|
Standards |
|
IEC 60947-5-6:1999 |
|
EN 60947-5-2:2007 |
|
Approvals and certificates |
|
IEC 60947-5-2:2007 |
|
|
|
FM approval |
|
116-0165 |
Control drawing |
|
|
UL approval |
|
cULus Listed, General Purpose |
CSA approval |
|
cCSAus Listed, General Purpose |
CCC approval |
|
CCC approval / marking not required for products rated ≤36 V |
Dimensions
Ø 22
<![if ! IE]><![endif]>35
Electrical Connection
BN
L+
BU
L-
1
|
|
|
|
|
|
|
|
|
|
|
|
|
Inductive sensor |
|
|
|
|
|
|
NJ6-22-N |
|
|
|
|
|
|
|
|
|
|
|
|
|
Equipment protection level Gb |
|
|
|
|
|
|
|
|
|
|
CE marking |
|
|
|
|
0102 |
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
ATEX marking |
|
¬II 2G Ex ia IIC T6…T1 Gb |
|||||||
|
|
|
|
The Ex-related marking can also be printed on the enclosed label. |
||||||
|
Standards |
|
EN 60079-0:2012+A11:2013, EN 60079-11:2012 |
|
||||||
|
|
|
|
Ignition protection "Intrinsic safety" |
|
|||||
|
|
|
|
Use is restricted to the following stated conditions |
|
|||||
|
Appropriate type |
|
NJ 6-22-N... |
|
||||||
|
Effective internal inductivity |
Ci |
≤ 130 nF ; a cable length of 10 m is considered. |
|
||||||
|
Effective internal inductance |
Li |
≤ 100 |
H ; a cable length of 10 m is considered. |
|
|||||
|
Maximum permissible ambient temperature Tamb |
Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the |
|
|||||||
|
|
|
|
temperature class, and the effective internal reactance values can be found on the EU-type examination certificate. |
|
|||||
|
Special conditions |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Equipment protection level Gc (ic) |
|
|
|
|
|
|
|
|
|
|
Certificate |
|
PF 13 CERT 2895 X |
|
||||||
|
CE marking |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ATEX marking |
|
¬II 3G Ex ic IIC T6…T1 Gc |
|||||||
|
|
|
|
The Ex-related marking can also be printed on the enclosed label. |
|
|||||
|
Standards |
|
EN 60079-0:2012+A11:2013, EN 60079-11:2012 |
|
||||||
|
|
|
|
Ignition protection category "ic" |
||||||
|
|
|
|
Use is restricted to the following stated conditions |
||||||
|
Effective internal inductivity |
Ci |
≤ 130 nF ; a cable length of 10 m is considered. |
|
||||||
|
Effective internal inductance |
Li |
≤ 100 |
H ; A cable length of 10 m is considered. |
|
|||||
|
Special conditions |
|
|
|
|
|
|
|
|
|
|
|
for Pi=34 mW, Ii=25 mA, T6 |
|
70 |
°C |
(158 °F) |
|
|||
|
|
for Pi=34 mW, Ii=25 mA, T5 |
|
85 |
°C |
(185 °F) |
|
|||
|
|
for Pi=34 mW, Ii=25 mA, T4-T1 |
|
100 °C (212 °F) |
|
|||||
|
|
for Pi=64 mW, Ii=25 mA, T6 |
|
69 |
°C |
(156.2 °F) |
|
|||
|
|
for Pi=64 mW, Ii=25 mA, T5 |
|
84 |
°C |
(183.2 °F) |
|
|||
|
|
for Pi=64 mW, Ii=25 mA, T4-T1 |
|
100 °C (212 °F) |
|
|||||
|
|
for Pi=169 mW, Ii=52 mA, T6 |
|
51 |
°C |
(123.8 °F) |
|
|||
|
|
for Pi=169 mW, Ii=52 mA, T5 |
|
66 |
°C |
(150.8 °F) |
|
|||
|
|
for Pi=169 mW, Ii=52 mA, T4-T1 |
80 |
°C |
(176 °F) |
|
||||
|
|
for Pi=242 mW, Ii=76 mA, T6 |
|
39 |
°C |
(102.2 °F) |
|
|||
|
|
for Pi=242 mW, Ii=76 mA, T5 |
|
54 |
°C |
(129.2 °F) |
|
|||
|
|
for Pi=242 mW, Ii=76 mA, T4-T1 |
61 |
°C |
(141.8 °F) |
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Equipment protection level Da |
|
|
|
|
|
|
|
|
|
|
CE marking |
|
|
|
|
0102 |
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
ATEX marking |
|
¬II 1D Ex ia IIIC T135°C Da |
|||||||
|
|
|
|
The Ex-related marking can also be printed on the enclosed label. |
||||||
|
Standards |
|
EN 60079-0:2012+A11:2013, EN 60079-11:2012 |
|
||||||
|
|
|
|
Ignition protection "Intrinsic safety" |
|
|||||
|
|
|
|
Use is restricted to the following stated conditions |
|
|||||
|
Appropriate type |
|
NJ 6-22-N... |
|
||||||
|
Effective internal inductivity |
Ci |
≤ 130 |
F |
|
|||||
|
|
|
|
A cable length of 10 m is considered. |
|
|||||
|
Effective internal inductance |
Li |
≤ 100 |
H |
|
|||||
|
|
|
|
A cable length of 10 m is considered. |
Special conditions
<![if ! IE]><![endif]>Release date: 2017-05-30 13:12 Date of issue: 2018-02-16 106456_eng.xml
2Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.