Pepperl Fuchs NJ5-30GK-S1N-5M Data Sheet

Inductive sensor NJ5-30GK-S1N-5M
Technical Data
General specifications
Switching function Normally open (NO) Output type NAMUR with safety function Rated operating distance sn5 mm Installation flush in mild steel Assured operating distance sa0 ... 4.05 mm
0102
Model Number
NJ5-30GK-S1N-5M
Features
• 5 mm flush in ST37 / 1.0037
• Usable up to SIL 3 acc. to IEC 61508
• ATEX approval Ex-i and Ex-nA/tc for zone 0-2 and zone 20-22
• Degree of protection IP68
Application
Danger!
In safety-related applications the sensor must be operated with a
qualified fail safe interface from Pepperl+Fuchs, such as KFD2-SH-EX1. Consider the "exida Functional Safety As­sessment" document which is available on
as an integral part
of this product’s documentation.
Accessories
BF 30
Mounting flange, 30 mm
Reduction factor r Reduction factor rCu 1 Reduction factor r Safety Integrity Level (SIL) up to SIL3 acc. to IEC 61508 Danger! In safety-related applications
Output type 2-wire
Nominal ratings
Nominal voltage Uo8.2 V Switching frequency f 0 ... 150 Hz Suitable for 2:1 technology yes , with reverse polarity protection diode Current consumption
Measuring plate not detected Measuring plate detected
Functional safety related parameters
Safety Integrity Level (SIL) SIL 3 MTTF
11850 a
d
Mission Time (TM) 20 a Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection type cable silicone , 5 m Core cross-section 0.75 mm Housing material Crastin (PBTB), black Sensing face Crastin (PBTB), black Degree of protection IP68 Cable
Bending radius
Note only for non-ferrous metal
General information
Use in the hazardous area see instruction manuals
Compliance with standards and directives
Standard conformity
Standards
Approvals and certificates
EAC conformity TR CU 012/2011 FM approval
Control drawing UL approval cULus Listed, General Purpose CCC approval CCC approval / marking not required for products rated 36 V
Dimensions
1
Al
0
304
the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs, such as KFD2-SH-EX1. Consider the "exida F ment" document which is available on as an integral part of this product's docume
1 mA 3 mA
2
> 10 x cable diameter
EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
116-0165
Release date: 2018-04-19 08:23 Date of issue: 2018-04-19 250948_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
55
36
M30 x 1.5
1
34.5
40
1
Inductive sensor NJ5-30GK-S1N-5M
Electrical Connection
BN
BU
BK
L+
n.c.
L-
Release date: 2018-04-19 08:23 Date of issue: 2018-04-19 250948_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2
Loading...
+ 3 hidden pages