Inductive sensor NJ5-30GK-S1N-15M
Technical Data
General specifications
Switching function Normally open (NO)
Output type NAMUR with safety function
Rated operating distance sn5 mm
Installation flush in mild steel
Assured operating distance sa0 ... 4.05 mm
0102
Model Number
NJ5-30GK-S1N-15M
Features
• Nonferrous targets
• 5 mm flush in ST37 / 1.0037
• Usable up to SIL 3 acc. to IEC 61
ATEX approval Ex-i and Ex
•
ne 0-2 and zone 20-22
zo
• Degree of protection IP68
Application
Danger!
In safety-related applications the
sensor must be operated with a
qualified fail safe interface from
Pepperl+Fuchs, such as KFD2-SH-EX1.
Consider the "exida Functional Safety Assessment" document which is available on
www.pepperl-fuchs.com as an integral part
of this product’s documentation.
508
-nA/tc for
Reduction factor r
Reduction factor rCu 1
Reduction factor r
Safety Integrity Level (SIL) up to SIL3 acc. to IEC 61508 Danger! In safety-related applications
Output type 2-wire
Nominal ratings
Nominal voltage Uo8.2 V
Switching frequency f 0 ... 150 Hz
Current consumption
Measuring plate not detected
Measuring plate detected
Functional safety related parameters
Safety Integrity Level (SIL) SIL 3
MTTFd 11850 a
Mission Time (T
Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection type cable silicone , 15 m
Core cross-section 0.75 mm
Housing material Crastin (PBTB), black
Sensing face Crastin (PBTB), black
Degree of protection IP68
Ca
ble
Bending radius
Note only for non-ferrous metal
General information
Use in the hazardous area see instruction manuals
Compliance with standards and
directives
Standard conformity
ards
Stand
Approvals and certificates
EAC conformity TR CU 012/2011
UL approval cULus Listed, General Purpose
CCC approval CCC approval / marking not required for products rated ≤36 V
Dimensions
1
Al
0
304
) 20 a
M
the sensor must be operated with a qualified fail safe interface from
Pepperl+Fuchs, such as KFD2-SH-EX1.
Consider the "exida Functional Safety Assessment" document
which is available on www.pepperl-fuchs.com as an integral part of
this product's documentation.
≤ 1 mA
≥ 3 mA
2
> 10 x cable diameter
EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
Accessories
BF 30
Mounting flange, 30 mm
Electrical Connection
55
36
BN
BU
BK
M30 x 1.5
L+
n.c.
L-
1
34.5
40
Release date: 2018-04-19 08:23 Date of issue: 2018-04-19 250950_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
1

Inductive sensor NJ5-30GK-S1N-15M
Data for application in connection with hazardous
areas
Equipment protection level Ga , Gb , Gc (nA) , Da , Dc , Mb
Equipment protection level Ga
Type of protection intrinsic safety
CE marking 0102
Certificates
A
ppropriate type
ATEX certificate
ATEX marking
Standards
IECEx certificate
IECEx marking
Standards
Effective internal inductivity C
Effective internal inductance L
i
i
Maximum permissible ambient temperature T
for ATEX
for IECEx
NJ 5-30GK-S1N...
PTB 00 ATEX 2049 X
¬ II 1G Ex ia IIC T6...T1 Ga
EN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx PTB 11.0092X
Ex ia IIC T6...T1 Ga
IEC 60079-0:2011 , IEC 60079-11:2011
≤ 100 nF
A cable length of 10 m is considered.
≤ 200 µH
A cable length of 10 m is considered.
Also observe the maximum permissible ambient temperature stated in the general technical data.
amb
Keep to the lower of the two values.
= 16 V , Ii = 25 mA , Pi = 34 mW ,
at U
i
T6 : 57 °C (134.6 °F)
T5 : 69 °C (156.2 °F)
T4 : 97 °C (206.6 °F)
T3 : 97 °C (206.6 °F)
T2 : 97 °C (206.6 °F)
T1 : 97 °C (206.6 °F)
at U
= 16 V , Ii = 25 mA , Pi = 64 mW ,
i
T6 : 52 °C (125.6 °F)
T5 : 64 °C (147.2 °F)
T4 : 92 °C (197.6 °F)
T3 : 92 °C (197.6 °F)
T2 : 92 °C (197.6 °F)
T1 : 92 °C (197.6 °F)
at U
= 16 V , Ii = 52 mA , Pi = 169 mW ,
i
T6 : 34 °C (93.2 °F)
T5 : 46 °C (114.8 °F)
T4 : 74 °C (165.2 °F)
T3 : 74 °C (165.2 °F)
T2 : 74 °C (165.2 °F)
T1 : 74 °C (165.2 °F)
at U
= 16 V , Ii = 76 mA , Pi = 242 mW ,
i
T6 : 22 °C (71.6 °F)
T5 : 34 °C (93.2 °F)
T4 : 61 °C (141.8 °F)
T3 : 61 °C (141.8 °F)
T2 : 61 °C (141.8 °F)
T1 : 61 °C (141.8 °F)
at Ui = 16 V , Ii = 25 mA , Pi = 34 mW ,
T6 : 73 °C (163.4 °F)
T5 : 88 °C (190.4 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at U
= 16 V , Ii = 25 mA , Pi = 64 mW ,
i
T6 : 69 °C (156.2 °F)
T5 : 84 °C (183.2 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at U
= 16 V , Ii = 52 mA , Pi = 169 mW ,
i
T6 : 51 °C (123.8 °F)
T5 : 66 °C (150.8 °F)
T4 : 80 °C (176 °F)
T3 : 80 °C (176 °F)
T2 : 80 °C (176 °F)
T1 : 80 °C (176 °F)
at U
= 16 V , Ii = 76 mA , Pi = 242 mW ,
i
T6 : 39 °C (102.2 °F)
T5 : 54 °C (129.2 °F)
T4 : 61 °C (141.8 °F)
T3 : 61 °C (141.8 °F)
T2 : 61 °C (141.8 °F)
T1 : 61 °C (141.8 °F)
Release date: 2018-04-19 08:23 Date of issue: 2018-04-19 250950_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2