Inductive sensor |
NJ5-11-N-5M |
|
|
|
|
0102
Model Number
NJ5-11-N-5M
Features
•Comfort series
•5 mm non-flush
•Usable up to SIL 2 acc. to IEC 61508
Accessories
BF 11
Mounting flange, 11 mm
<![if ! IE]><![endif]>Release date: 2017-05-30 10:37 Date of issue: 2018-02-16 106435_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Technical Data
General specifications |
|
Normally closed (NC) |
Switching function |
|
|
Output type |
sn |
NAMUR |
Rated operating distance |
5 mm |
|
Installation |
sa |
non-flush |
Assured operating distance |
0 ... 4.05 mm |
|
Reduction factor rAl |
|
0.4 |
Reduction factor rCu |
|
0.3 |
Reduction factor r304 |
|
0.85 |
Output type |
|
2-wire |
Nominal ratings |
Uo |
8 V |
Nominal voltage |
||
Switching frequency |
f |
0 ... 3000 Hz |
Hysteresis |
H |
typ. % |
Suitable for 2:1 technology |
|
yes , Reverse polarity protection diode not required |
Current consumption |
|
≥ 3 mA |
Measuring plate not detected |
|
|
Measuring plate detected |
|
≤ 1 mA |
Functional safety related parameters |
11774 a |
|
MTTFd |
|
|
Mission Time (TM) |
|
20 a |
Diagnostic Coverage (DC) |
|
0 % |
Ambient conditions |
|
-25 ... 100 °C (-13 ... 212 °F) |
Ambient temperature |
|
|
Mechanical specifications |
|
cable PVC , 5 m |
Connection type |
|
|
Core cross-section |
|
0.34 mm2 |
Housing material |
|
PVDF |
Sensing face |
|
PVDF |
Degree of protection |
|
IP68 |
Cable |
|
> 10 x cable diameter |
Bending radius |
|
|
General information |
|
see instruction manuals |
Use in the hazardous area |
|
|
Category |
|
2G |
Compliance with standards and |
|
|
directives |
|
|
Standard conformity |
|
EN 60947-5-6:2000 |
NAMUR |
|
|
Standards |
|
IEC 60947-5-6:1999 |
|
EN 60947-5-2:2007 |
|
|
|
IEC 60947-5-2:2007 |
Approvals and certificates |
|
cULus Listed, General Purpose |
UL approval |
|
|
CCC approval |
|
CCC approval / marking not required for products rated ≤36 V |
Dimensions
ø11
<![if ! IE]><![endif]>30
Electrical Connection
BN
L+
BU
L-
1
|
|
|
|
|
|
|
|
|
Inductive sensor |
|
|
NJ5-11-N-5M |
|
|
|
|
|
|
|
|
|
Equipment protection level Gb |
|
|
|
|
|
|
CE marking |
|
|
0102 |
|
|
|
|
|
|
|
|
|
|
ATEX marking |
|
¬II 2G Ex ia IIC T6…T1 Gb |
|||
|
|
|
|
The Ex-related marking can also be printed on the enclosed label. |
||
|
Standards |
|
EN 60079-0:2012+A11:2013, EN 60079-11:2012 |
|
||
|
|
|
|
Ignition protection "Intrinsic safety" |
|
|
|
|
|
|
Use is restricted to the following stated conditions |
|
|
|
Appropriate type |
|
NJ 5-11-N... |
|
||
|
Effective internal inductivity |
Ci |
≤ 45 nF ; a cable length of 10 m is considered. |
|
||
|
Effective internal inductance |
Li |
≤ 50 H ; a cable length of 10 m is considered. |
|
||
|
Maximum permissible ambient temperature Tamb |
Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the |
|
|||
|
|
|
|
temperature class, and the effective internal reactance values can be found on the EU-type examination certificate. |
|
|
|
Special conditions |
|
|
|
|
|
|
|
|
|
|
|
|
|
Equipment protection level Da |
|
|
|
|
|
|
CE marking |
|
|
0102 |
|
|
|
|
|
|
|
|
|
|
ATEX marking |
|
¬II 1D Ex ia IIIC T135°C Da |
|||
|
|
|
|
The Ex-related marking can also be printed on the enclosed label. |
||
|
Standards |
|
EN 60079-0:2012+A11:2013, EN 60079-11:2012 |
|
||
|
|
|
|
Ignition protection "Intrinsic safety" |
|
|
|
|
|
|
Use is restricted to the following stated conditions |
|
|
|
Appropriate type |
|
NJ 5-11-N... |
|
||
|
Effective internal inductivity |
Ci |
≤ 45 F |
|
||
|
|
|
|
A cable length of 10 m is considered. |
|
|
|
Effective internal inductance |
Li |
≤ 50 H |
|
||
|
|
|
|
A cable length of 10 m is considered. |
Special conditions
<![if ! IE]><![endif]>Release date: 2017-05-30 10:37 Date of issue: 2018-02-16 106435_eng.xml
2Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.