Pepperl Fuchs NJ4-12GK-N Data Sheet

Inductive sensor NJ4-12GK-N
Technical Data
General specifications
Switching function Normally closed (NC) Output type NAMUR Rated operating distance sn4 mm Installation non-flush Assured operating distance sa0 ... 3.24 mm
0102
Model Number
NJ4-12GK-N
Features
• Usable up to SIL 2 acc. to IEC 61508
Accessories
BF 12
Mounting flange, 12 mm
Reduction factor r Reduction factor rCu 0.3 Reduction factor r Output type 2-wire
Nominal ratings
Nominal voltage Uo8.2 V (Ri approx. 1 kΩ) Switching frequency f 0 ... 1500 Hz Current consumption
Measuring plate not detected Measuring plate detected
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2 MTTF
11774 a
d
Mission Time (TM) 20 a Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection type cable PVC , 2 m Core cross-section 0.34 mm Housing material PBT Sensing face PBT Degree of protection IP66 / IP68 Cable
Bending radius
General information
Use in the hazardous area see instruction manuals
Compliance with standards and directives
Standard conformity
NAMUR
Standards
Approvals and certificates
EAC conformity TR CU 012/2011 FM approval
Control drawing UL approval cULus Listed, General Purpose CSA approval cCSAus Listed, General Purpose CCC approval CCC approval / marking not required for products rated 36 V
Dimensions
0.4
Al
0.85
304
3 mA 1 mA
2
> 10 x cable diameter
EN 60947-5-6:2000 IEC 60947-5-6:1999 EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
116-0165
Release date: 2018-04-19 08:21 Date of issue: 2018-04-19 106413_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Electrical Connection
BN
BU
44
17
M12 x 1
35
30.5
L+
L-
1
Inductive sensor NJ4-12GK-N
Data for application in connection with hazardous areas
Equipment protection level Gb , Da , Mb
Equipment protection level Gb
Type of protection intrinsic safety
CE marking 0102
Certificates
Appropriate type
ATEX certificate
ATEX marking
Standards
IECEx certificate
IECEx marking
Standards
Effective internal inductivity C
Effective internal inductance L
i
i
Maximum permissible ambient temperature T
Equipment protection level Da
Type of protection intrinsic safety
CE marking 0102
NJ4-12GK-N...
PTB 00 ATEX 2048 X ¬ II 2G Ex ia IIC T6…T1 Gb
EN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx PTB 11.0037X
Ex ia IIC T6 Ga
IEC 60079-0:2004 , IEC 60079-11:2006
45 nF A cable length of 10 m is considered.
50 µH A cable length of 10 m is considered.
Also observe the maximum permissible ambient temperature stated in the general technical data.
amb
Keep to the lower of the two values. at U
= 16 V , Ii = 25 mA , Pi = 34 mW ,
i
T6 : 73 °C (163.4 °F) T5 : 88 °C (190.4 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at U
= 16 V , Ii = 25 mA , Pi = 64 mW ,
i
T6 : 69 °C (156.2 °F) T5 : 84 °C (183.2 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at U
= 16 V , Ii = 52 mA , Pi = 169 mW ,
i
T6 : 51 °C (123.8 °F) T5 : 66 °C (150.8 °F) T4 : 80 °C (176 °F) T3 : 80 °C (176 °F) T2 : 80 °C (176 °F) T1 : 80 °C (176 °F) at U
= 16 V , Ii = 76 mA , Pi = 242 mW ,
i
T6 : 39 °C (102.2 °F) T5 : 54 °C (129.2 °F) T4 : 61 °C (141.8 °F) T3 : 61 °C (141.8 °F) T2 : 61 °C (141.8 °F) T1 : 61 °C (141.8 °F)
Certificates
Appropriate type
ATEX certificate
ATEX marking
Standards
Effective internal inductivity C
Effective internal inductance L
i
i
Maximum permissible ambient temperature T
NJ4-12GK-N...
PTB 00 ATEX 2048 X ¬ II 1D Ex ia IIIC T135°C Da
EN 60079-0:2012+A11:2013 , EN 60079-11:2012
45 nF A cable length of 10 m is considered.
50 µH A cable length of 10 m is considered.
Also observe the maximum permissible ambient temperature stated in the general technical data.
amb
Keep to the lower of the two values. at U
= 16 V , Ii = 25 mA , Pi = 34 mW : 100 °C (212 °F)
i
at U
= 16 V , Ii = 25 mA , Pi = 64 mW : 100 °C (212 °F)
i
at U
= 16 V , Ii = 52 mA , Pi = 169 mW : 80 °C (176 °F)
i
at U
= 16 V , Ii = 76 mA , Pi = 242 mW : 61 °C (141.8 °F)
i
Equipment protection level Mb
Type of protection intrinsic safety
Certificates
Appropriate type
IECEx certificate
IECEx marking
Standards
Effective internal inductivity C
Effective internal inductance L
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
i
i
NJ4-12GK-N...
IECEx PTB 11.0037X
Ex ia I
IEC 60079-0:2004 , IEC 60079-11:2006
45 nF A cable length of 10 m is considered.
50 µH A cable length of 10 m is considered.
2
Release date: 2018-04-19 08:21 Date of issue: 2018-04-19 106413_eng.xml