Pepperl Fuchs NJ40 U1 N Dimensions

11
56 60
55
128
30
5.5
M20 x 1.5
Germany: +49 621 776 1111Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0001 Singapore: +65 6779 9091
www.pepperl-fuchs.com fa-info@us.pepperl-fuchs.com fa-info@sg.pepperl-fuchs.com
fa-info@de.pepperl-fuchs.com

Dimensions

Inductive sensor

NJ40+U1+N

40 mm non-flush
<

Technical Data

General specifications
Switching function Normally closed (NC)
Output type NAMUR
Rated operating distance s
Installation non-flush
Assured operating distance s
Reduction factor rAl 0.4
Reduction factor rCu 0.3
Reduction factor r
Output type 2-wire
Nominal ratings
Nominal voltage U
Switching frequency f 0 ... 80 Hz
Current consumption
Measuring plate not detected ≥ 3 mA
Measuring plate detected ≤ 1 mA
Functional safety related parameters
Release date: 2020-12-15 Date of issue: 2020-12-15 Filename: 106690_eng.pdf
0.85
304
40 mm
n
0 ... 32.4 mm
a
8.2 V (Ri approx. 1 kΩ)
o
1
Inductive sensor NJ40+U1+N
Germany: +49 621 776 1111Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0001 Singapore: +65 6779 9091
www.pepperl-fuchs.com fa-info@us.pepperl-fuchs.com fa-info@sg.pepperl-fuchs.com
fa-info@de.pepperl-fuchs.com

Technical Data

MTTF
d
2588 a
Mission Time (TM) 20 a
Diagnostic Coverage (DC) 0 %
Compliance with standards and directives
Standard conformity
NAMUR EN 60947-5-6:2000
IEC 60947-5-6:1999
Standards EN 60947-5-2:2007
EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
Approvals and certificates
IECEx approval
Equipment protection level Ga IECEx PTB 11.0021X
Equipment protection level Gb IECEx PTB 11.0021X
Equipment protection level Da IECEx PTB 11.0021X
Equipment protection level Mb IECEx PTB 11.0021X
ATEX approval
Equipment protection level Ga PTB 00 ATEX 2032 X
Equipment protection level Gb PTB 00 ATEX 2032 X
Equipment protection level Da PTB 00 ATEX 2032 X
EAC conformity TR CU 012/2011
FM approval
Control drawing 116-0165
UL approval cULus Listed, General Purpose
Ordinary Location E87056
Hazardous Location E501628
Control drawing 116-0451
CSA approval cCSAus Listed, General Purpose
CCC approval
Hazardous Location 2020322315002302
NEPSI approval
NEPSI certificate GYJ16.1394X
Ambient conditions
Ambient temperature -25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection type screw terminals
Information for connection A maximum of two conductors with the same core cross section may be mounted on
one terminal connection! tightening torque 1.2 Nm + 10 %
Core cross-section up to 2.5 mm2 , stripped insulation length: 7 mm
Minimum core cross-section without wire end ferrule 0.5 mm2 , with connector sleeves 0.34 mm
Maximum core cross-section without wire end ferrule 2.5 mm2 , with connector sleeves 1.5 mm
2
2
Connection (system side) screw terminals , M20 x 1.5 cable gland , usable thread length 9.1 mm , screw-in depth
max. 9.1 mm
Housing material PBT
Sensing face PBT
Degree of protection IP68
Note Tightening torque: 1.8 Nm (housing)
General information
Use in the hazardous area see instruction manuals
Release date: 2020-12-15 Date of issue: 2020-12-15 Filename: 106690_eng.pdf
2
Loading...