Pepperl Fuchs NJ3-18GK-S1N-10M Data Sheet

Inductive sensor NJ3-18GK-S1N-10M
Technical Data
General specifications
Switching function Normally open (NO) Output type NAMUR with safety function Rated operating distance sn3 mm Installation flush in mild steel Assured operating distance sa0 ... 2.4 mm
0102
Model Number
NJ3-18GK-S1N-10M
Features
• 3 mm flush in ST37 / 1.0037
• Usable up to SIL 3 acc. to IEC 61508
• ATEX approval Ex-i and Ex-nA/tc for zone 0-2 and zone 20-22
• Degree of protection IP68
Application
Danger!
In safety-related applications the sensor must be operated with a
qualified fail safe interface from Pepperl+Fuchs, such as KFD2-SH-EX1. Consider the "exida Functional Safety As­sessment" document which is available on
as an integral part
of this product’s documentation.
Accessories
BF 18
Mounting flange, 18 mm
Actual operating distance s Reduction factor rAl 1 Reduction factor r Reduction factor r Safety Integrity Level (SIL) up to SIL3 acc. to IEC 61508 Danger! In safety-related applications
Output type 2-wire
Nominal ratings
Nominal voltage Uo8.2 V Switching frequency f 0 ... 200 Hz Current consumption
Measuring plate not detected Measuring plate detected
Functional safety related parameters
Safety Integrity Level (SIL) SIL 3 MTTF
10660 a
d
Mission Time (TM) 20 a Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection type cable silicone , 10 m Core cross-section 0.75 mm Housing material Crastin (PBTB), black Sensing face Crastin (PBTB), black Degree of protection IP68 Cable
Bending radius
Note only for non-ferrous metal
General information
Use in the hazardous area see instruction manuals
Compliance with standards and directives
Standard conformity
Standards
Approvals and certificates
EAC conformity TR CU 012/2011 UL approval cULus Listed, General Purpose CCC approval CCC approval / marking not required for products rated 36 V
1
Cu
0
304
Dimensions
2.7 ... 3.3 mm typ.
r
the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs, such as KFD2-SH-EX1. Consider the "exida F ment" document which is available on as an integral part of this product's docume
1 mA 3 mA
2
> 10 x cable diameter
EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
Release date: 2018-04-19 08:20 Date of issue: 2018-04-19 250937_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Electrical Connection
BN
BU
BK
44
24
L+
n.c.
L-
M18 x 1
1
35.5
40.5
1
Inductive sensor NJ3-18GK-S1N-10M
Data for application in connection with hazardous areas
Equipment protection level Ga , Gb , Gc (ic) , Gc (nA) , Da , Dc , Mb
Equipment protection level Ga
Type of protection intrinsic safety
CE marking 0102
Certificates
Appropriate type
ATEX certificate
ATEX marking
Standards
IECEx certificate
IECEx marking
Standards
Effective internal inductivity C
Effective internal inductance L
i
i
Maximum permissible ambient temperature T
for ATEX
for IECEx
NJ 3-18GK-S1N...
PTB 00 ATEX 2049 X ¬ II 1G Ex ia IIC T6...T1 Ga
EN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx PTB 11.0092X
Ex ia IIC T6...T1 Ga
IEC 60079-0:2011 , IEC 60079-11:2011
70 nF A cable length of 10 m is considered.
200 µH A cable length of 10 m is considered.
Also observe the maximum permissible ambient temperature stated in the general technical data.
amb
Keep to the lower of the two values.
= 16 V , Ii = 25 mA , Pi = 34 mW ,
at U
i
T6 : 57 °C (134.6 °F) T5 : 69 °C (156.2 °F) T4 : 97 °C (206.6 °F) T3 : 97 °C (206.6 °F) T2 : 97 °C (206.6 °F) T1 : 97 °C (206.6 °F) at U
= 16 V , Ii = 25 mA , Pi = 64 mW ,
i
T6 : 52 °C (125.6 °F) T5 : 64 °C (147.2 °F) T4 : 92 °C (197.6 °F) T3 : 92 °C (197.6 °F) T2 : 92 °C (197.6 °F) T1 : 92 °C (197.6 °F) at U
= 16 V , Ii = 52 mA , Pi = 169 mW ,
i
T6 : 34 °C (93.2 °F) T5 : 46 °C (114.8 °F) T4 : 74 °C (165.2 °F) T3 : 74 °C (165.2 °F) T2 : 74 °C (165.2 °F) T1 : 74 °C (165.2 °F) at U
= 16 V , Ii = 76 mA , Pi = 242 mW ,
i
T6 : 22 °C (71.6 °F) T5 : 34 °C (93.2 °F) T4 : 61 °C (141.8 °F) T3 : 61 °C (141.8 °F) T2 : 61 °C (141.8 °F) T1 : 61 °C (141.8 °F)
at Ui = 16 V , Ii = 25 mA , Pi = 34 mW , T6 : 73 °C (163.4 °F) T5 : 88 °C (190.4 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at U
= 16 V , Ii = 25 mA , Pi = 64 mW ,
i
T6 : 69 °C (156.2 °F) T5 : 84 °C (183.2 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at U
= 16 V , Ii = 52 mA , Pi = 169 mW ,
i
T6 : 51 °C (123.8 °F) T5 : 66 °C (150.8 °F) T4 : 80 °C (176 °F) T3 : 80 °C (176 °F) T2 : 80 °C (176 °F) T1 : 80 °C (176 °F) at U
= 16 V , Ii = 76 mA , Pi = 242 mW ,
i
T6 : 39 °C (102.2 °F) T5 : 54 °C (129.2 °F) T4 : 61 °C (141.8 °F) T3 : 61 °C (141.8 °F) T2 : 61 °C (141.8 °F) T1 : 61 °C (141.8 °F)
Release date: 2018-04-19 08:20 Date of issue: 2018-04-19 250937_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2
Loading...
+ 2 hidden pages