Inductive sensor NJ2-12GM-N-5M
Technical Data
General specifications
Switching function Normally closed (NC)
Output type NAMUR
Rated operating distance sn2 mm
Installation flush
Assured operating distance sa0 ... 1.62 mm
0102
Model Number
NJ2-12GM-N-5M
Features
• Comfort series
•2 mm flush
• Usable up to SIL 2 acc. to IEC 61508
Accessories
EXG-12
Quick mounting bracket with dead stop
BF 12
Mounting flange, 12 mm
Reduction factor r
Reduction factor rCu 0.3
Reduction factor r
Output type 2-wire
Nominal ratings
Nominal voltage Uo8 V
Switching frequency f 0 ... 2000 Hz
Suitable for 2:1 technology yes , Reverse polarity protection diode not required
Current consumption
Measuring plate not detected
Measuring plate detected
Functional safety related parameters
MTTFd 5887 a
Mission Time (TM) 20 a
Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection type cable PVC , 5 m
Core cross-section 0.34 mm
Housing material Stainless steel 1.4305 / AISI 303
Sensing face PBT
Degree of protection IP67
Cable
Bending radius
General information
Scope of delivery 2 self locking nuts in scope of delivery
Use in the hazardous area see instruction manuals
Category
Compliance with standards and
directives
Standard conformity
NAMUR
Standards
Approvals and certificates
EAC conformity TR CU 012/2011
UL approval cULus Listed, General Purpose
CSA approval cCSAus Listed, General Purpose
CCC approval CCC approval / marking not required for products rated ≤36 V
Dimensions
0.4
Al
0.85
304
≥ 3 mA
≤ 1 mA
2
> 10 x cable diameter
1G; 2G; 1D
EN 60947-5-6:2000
IEC 60947-5-6:1999
EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
Electrical Connection
M12 x 1
4
35
17
BN
BU
L+
L-
Release date: 2018-04-19 08:20 Date of issue: 2018-04-19 106636_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
1

Inductive sensor NJ2-12GM-N-5M
Equipment protection level Ga
CE marking 0102
ATEX marking ¬ II 1G Ex ia IIC T6…T1 Ga The Ex-related marking can also be printed on the enclosed label.
Standards EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety"
Appropriate type NJ 2-12GM-N...
Effective internal inductivity C
Effective internal inductance L
i
i
Ambient temperature Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
Equipment protection level Gb
CE marking 0102
ATEX marking ¬ II 1G Ex ia IIC T6…T1 Ga The Ex-related marking can also be printed on the enclosed label.
Standards EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety"
Appropriate type NJ 2-12GM-N...
Effective internal inductivity C
Effective internal inductance L
i
i
Maximum permissible ambient temperature T
Equipment protection level Da
CE marking 0102
Use is restricted to the following stated conditions
≤ 30 nF ; a cable length of 10 m is considered.
≤ 50 µH ; a cable length of 10 m is considered.
temperature class, and the effective internal reactance values can be found on the EC-type examination certificate.
Note:
Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already
been applied to the temperature table for category 1.
Use is restricted to the following stated conditions
≤ 30 nF ; a cable length of 10 m is considered.
≤ 50 µH ; a cable length of 10 m is considered.
Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
amb
temperature class, and the effective internal reactance values can be found on the EC-type examination certificate.
ATEX marking ¬ II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label.
Standards EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety"
Use is restricted to the following stated conditions
Appropriate type NJ 2-12GM-N...
Effective internal inductivity C
Effective internal inductance L
i
i
Maximum permissible ambient temperature T
≤ 30 nF ; a cable length of 10 m is considered.
≤ 50 µH ; a cable length of 10 m is considered.
Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
amb
surface temperature, and the effective internal reactance values can be found on the EC-type-examination
certificate.
The maximum permissible ambient temperature of the data sheet must be noted, in addition, the lower of
the two values must be maintained.