Inductive sensor NJ2-11-N
Technical Data
General specifications
Switching function Normally closed (NC)
Output type NAMUR
Rated operating distance sn2 mm
Installation flush
Assured operating distance sa0 ... 1.62 mm
0102
Model Number
NJ2-11-N
Features
•2 mm flush
• Usable up to SIL 2 acc. to IEC 61508
Accessories
BF 11
Mounting flange, 11 mm
Actual operating distance s
Reduction factor rAl 0.4
Reduction factor r
Reduction factor r
Output type 2-wire
Nominal ratings
Nominal voltage Uo8.2 V (Ri approx. 1 kΩ)
Switching frequency f 0 ... 3000 Hz
Hysteresis H 0.5 ... 3.5 typ. 2 %
Current consumption
Measuring plate not detected
Measuring plate detected
Functional safety related parameters
MTTFd 5887 a
Mission Time (T
Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection type cable PVC , 2 m
Core cross-section 0.34 mm
Housing material PVDF
Sensing face PVDF
Degree of protection IP68
Cable
Bending radius
General information
Use in the hazardous area see instruction manuals
Category
Compliance with standards and
directives
Standard conformity
NAMUR
Standards
Approvals and certificates
FM approval
Control drawing
UL approval cULus Listed, General Purpose
CCC approval CCC approval / marking not required for products rated ≤36 V
0.3
Cu
0.85
304
) 20 a
M
Dimensions
1.8 ... 2.2 mm
r
≥ 3 mA
≤ 1 mA
> 10 x cable diameter
1G; 2G; 3G; 1D; 3D
EN 60947-5-6:2000
IEC 60947-5-6:1999
EN 60947-5-2:2007
IEC 60947-5-2:2007
116-0165
2
Release date: 2016-11-08 17:34 Date of issue: 2018-02-16 106377_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Electrical Connection
BN
BU
ø11
30
L+
L-
1

Inductive sensor NJ2-11-N
Equipment protection level Ga
CE marking 0102
ATEX marking ¬ II 1G Ex ia IIC T6…T1 Ga The Ex-related marking can also be printed on the enclosed label.
Standards EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety"
Appropriate type NJ 2-11-N...
Effective internal inductivity C
Effective internal inductance L
i
i
Ambient temperature Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
Equipment protection level Gb
CE marking 0102
ATEX marking ¬ II 1G Ex ia IIC T6…T1 Ga The Ex-related marking can also be printed on the enclosed label.
Standards EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety"
Appropriate type NJ 2-11-N...
Effective internal inductivity C
Effective internal inductance L
i
i
Maximum permissible ambient temperature T
Equipment protection level Gc (ic)
Certificate PF 13 CERT 2895 X
CE marking
Use is restricted to the following stated conditions
≤ 45 nF ; a cable length of 10 m is considered.
≤ 50 µH ; a cable length of 10 m is considered.
temperature class, and the effective internal reactance values can be found on the EC-type examination certificate.
Note:
Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already
been applied to the temperature table for category 1.
Use is restricted to the following stated conditions
≤ 45 nF ; a cable length of 10 m is considered.
≤ 50 µH ; a cable length of 10 m is considered.
Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
amb
temperature class, and the effective internal reactance values can be found on the EC-type examination certificate.
ATEX marking ¬ II 3G Ex ic IIC T6…T1 Gc
Standards EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection category "ic" Use is restricted to the following
Effective internal inductivity C
Effective internal inductance L
i
i
The Ex-significant identification is on the enclosed adhesive label
stated conditions
≤ 45 nF ; a cable length of 10 m is considered.
≤ 50 µH ; A cable length of 10 m is considered.
Special conditions
for Pi=34 mW, Ii=25 mA, T6
for Pi=34 mW, Ii=25 mA, T5
for Pi=34 mW, Ii=25 mA, T4-T1
for Pi=64 mW, Ii=25 mA, T6
for Pi=64 mW, Ii=25 mA, T5
for Pi=64 mW, Ii=25 mA, T4-T1
for Pi=169 mW, Ii=52 mA, T6
for Pi=169 mW, Ii=52 mA, T5
for Pi=169 mW, Ii=52 mA, T4-T1
for Pi=242 mW, Ii=76 mA, T6
for Pi=242 mW, Ii=76 mA, T5
for Pi=242 mW, Ii=76 mA, T4-T1
55 °C (131 °F)
55 °C (131 °F)
55 °C (131 °F)
55 °C (131 °F)
55 °C (131 °F)
55 °C (131 °F)
35 °C (95 °F)
35 °C (95 °F)
35 °C (95 °F)
20 °C (68 °F)
20 °C (68 °F)
20 °C (68 °F)
Equipment protection level Gc (nL)
Standard conformity EN 60079-15:2005 Ignition protection category "n"
Effective internal capacitance C
≤ 45 nF ; a cable length of 10 m is considered.
i
Use is restricted to the following stated conditions
Effective internal inductance Li ≤ 50 µH ; A cable length of 10 m is considered.
General The apparatus has to be operated according to the appropriate data in the data sheet and in this instruction manual.
The data stated in the data sheet are restricted by this operating instruction!
The special conditions must be observed!
The ATEX Directive applies only to the use of apparatus under atmospheric conditions.
If you use the device outside atmospheric conditions, consider that the permissible safety parameters should be
reduced.
Special conditions
for Pi=34 mW, Ii=25 mA, T6
for Pi=34 mW, Ii=25 mA, T5
for Pi=34 mW, Ii=25 mA, T4-T1
for Pi=64 mW, Ii=25 mA, T6
for Pi=64 mW, Ii=25 mA, T5
for Pi=64 mW, Ii=25 mA, T4-T1
for Pi=169 mW, Ii=52 mA, T6
for Pi=169 mW, Ii=52 mA, T5
for Pi=169 mW, Ii=52 mA, T4-T1
for Pi=242 mW, Ii=76 mA, T6
for Pi=242 mW, Ii=76 mA, T5
for Pi=242 mW, Ii=76 mA, T4-T1
55 °C (131 °F)
55 °C (131 °F)
55 °C (131 °F)
55 °C (131 °F)
55 °C (131 °F)
55 °C (131 °F)
35 °C (95 °F)
35 °C (95 °F)
35 °C (95 °F)
20 °C (68 °F)
20 °C (68 °F)
20 °C (68 °F)
Release date: 2016-11-08 17:34 Date of issue: 2018-02-16 106377_eng.xml