Inductive sensor NJ1,5-8GM-N-V1
Technical Data
General specifications
Switching function Normally closed (NC)
Output type NAMUR
Rated operating distance sn1.5 mm
Installation flush
Assured operating distance sa0 ... 1.215 mm
0102
Model Number
NJ1,5-8GM-N-V1
Features
•1.5 mm flush
• Usable up to SIL 2 acc. to IEC 61508
Accessories
V1-G
Female connector, M12, 4-pin, field attachable
V1-W
Female connector, M12, 4-pin, field attachable
V1-G-N-2M-PUR
Female cordset, M12, 2-pin, NAMUR, PUR cable
V1-W-N-2M-PUR
Female cordset, M12, 2-pin, NAMUR, PUR cable
BF 8
Mounting flange, 8 mm
Actual operating distance s
Reduction factor rAl 0.4
Reduction factor r
Reduction factor r
Output type 2-wire
Nominal ratings
Nominal voltage Uo8.2 V (Ri approx. 1 kΩ)
Switching frequency f 0 ... 5000 Hz
Hysteresis H 1 ... 10 typ. 5 %
Suitable for 2:1 technology yes , Reverse polarity protection diode not required
Current consumption
Measuring plate not detected
Measuring plate detected
Ambient conditions
Ambient temperature -25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection type Connector plug M12 x 1 , 4-pin
Housing material Stainless steel 1.4305 / AISI 303
Sensing face PBT
Degree of protection IP67
General information
Use in the hazardous area see instruction manuals
Category
Compliance with standards and
directives
Standard conformity
NAMUR
Standards
Approvals and certificates
EAC conformity TR CU 012/2011
FM approval
Control drawing
UL approval cULus Listed, General Purpose
CSA approval cCSAus Listed, General Purpose
CCC approval CCC approval / marking not required for products rated ≤36 V
0.3
Cu
0.85
304
Dimensions
1.35 ... 1.65 mm typ.
r
≥ 3 mA
≤ 1 mA
2G
EN 60947-5-6:2000
IEC 60947-5-6:1999
EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
116-0165
Release date: 2018-04-19 08:17 Date of issue: 2018-04-19 106364_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Electrical Connection
M8x1
4
13
M12x1
1
2
20
42
6
L+
L-
1

Inductive sensor NJ1,5-8GM-N-V1
Pinout
1
2
4
3
Wire colors in accordance with EN 60947-5-6
1 BN
2 BU
Equipment protection level Gb
CE marking 0102
ATEX marking ¬ II 2G Ex ia IIC T6…T1 Gb
Standards EN 60079-0:2012+A11:2013, EN 60079-11:2012
Appropriate type NJ1,5-8GM-N...
Effective internal inductivity C
Effective internal inductance L
Maximum permissible ambient temperature T
Special conditions
Equipment protection level Da
CE marking 0102
i
i
(brown)
(blue)
The Ex-related marking can also be printed on the enclosed label.
Ignition protection "Intrinsic safety"
Use is restricted to the following stated conditions
≤ 30 nF ; a cable length of 10 m is considered.
≤ 50 µH ; a cable length of 10 m is considered.
Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
amb
temperature class, and the effective internal reactance values can be found on the EU-type examination certificate.
ATEX marking ¬ II 1D Ex ia IIIC T135°C Da
Standards EN 60079-0:2012+A11:2013, EN 60079-11:2012
Appropriate type NJ1,5-8GM-N...
Effective internal inductivity C
Effective internal inductance L
Special conditions
i
i
The Ex-related marking can also be printed on the enclosed label.
Ignition protection "Intrinsic safety"
Use is restricted to the following stated conditions
≤ 30 µF
A cable length of 10 m is considered.
≤ 50 µH
A cable length of 10 m is considered.
Release date: 2018-04-19 08:17 Date of issue: 2018-04-19 106364_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2