Pepperl Fuchs NJ1.5-18GM-N-D10M Data Sheet

Inductive sensor NJ1,5-18GM-N-D-10M
Technical Data
General specifications
Switching function Normally closed (NC) Output type NAMUR Rated operating distance sn1.5 mm Installation flush Assured operating distance sa0 ... 1.22 mm
0102
Model Number
NJ1,5-18GM-N-D-10M
Features
• Compression proof up to 350 bar, dynamic on active surface
• Usable up to SIL 2 acc. to IEC 61508
Application
Note
Please refer to the technical information about this product at www.pepperl­fuchs.com. This information describes the necessary geometry of the installation space!
Reduction factor r Reduction factor rCu 0 Reduction factor r Output type 2-wire
Nominal ratings
Nominal voltage Uo8 V Switching frequency f 0 ... 400 Hz Hysteresis H typ. % Current consumption
Measuring plate not detected Measuring plate detected
Limit data
Operating pressure 350 bar (5076.4 psi)
Ambient conditions
Ambient temperature -25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Connection type cable PVC , 10 m Core cross-section 0.34 mm Housing material Stainless steel 1.4305 / AISI 303 Sensing face Ceramic Degree of protection IP68 Cable
Bending radius
General information
Use in the hazardous area see instruction manuals
Category
Compliance with standards and directives
Standard conformity
NAMUR
Standards
Approvals and certificates
EAC conformity TR CU 012/2011 UL approval cULus Listed, General Purpose CSA approval cCSAus Listed, General Purpose
Dimensions
0
Al
0.55
304
3 mA 1 mA
2
> 10 x cable diameter
2G; 1D
EN 60947-5-6:2000 IEC 60947-5-6:1999 EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
Electrical Connection
M18 x 1
ø 15 f9
4
24
14
BN
BU
L+
L-
0.1 A
8
15
35
50
Release date: 2018-06-21 08:35 Date of issue: 2018-06-21 106343_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
1
Inductive sensor NJ1,5-18GM-N-D-10M
Equipment protection level Gb
CE marking 0102
ATEX marking ¬ II 2G Ex ia IIC T6T1 Gb The Ex-related marking can also be printed on the enclosed label.
Standards EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety"
Appropriate type NJ1,5-18GM-N-D..
Effective internal inductivity C
Effective internal inductance L
Maximum permissible ambient temperature T
Equipment protection level Da
CE marking 0102
ATEX marking ¬ II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label.
Standards EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety"
Appropriate type NJ1,5-18GM-N-D..
Effective internal inductivity C
Effective internal inductance L
Maximum permissible ambient temperature T
i
i
i
i
Use is restricted to the following stated conditions
50 nF ; a cable length of 10 m is considered.
60 µH ; a cable length of 10 m is considered.
Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
amb
temperature class, and the effective internal reactance values can be found on the EC-type examination certificate.
Use is restricted to the following stated conditions
50 nF ; a cable length of 10 m is considered.
60 µH ; a cable length of 10 m is considered.
Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
amb
surface temperature, and the effective internal reactance values can be found on the EC-type-examination certificate.
The maximum permissible ambient temperature of the data sheet must be noted, in addition, the lower of the two values must be maintained.
Release date: 2018-06-21 08:35 Date of issue: 2018-06-21 106343_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2