Inductive sensor NJ10-30GK-N-5M
Technical Data
General specifications
Switching function Normally closed (NC)
Output type NAMUR
Rated operating distance sn10 mm
Installation flush
Assured operating distance sa0 ... 8.1 mm
0102
Model Number
NJ10-30GK-N-5M
Features
• 10 mm flush
• Usable up to SIL 2 acc. to IEC 61508
Accessories
BF 30
Mounting flange, 30 mm
Reduction factor r
Reduction factor rCu 0.3
Reduction factor r
Output type 2-wire
Nominal ratings
Nominal voltage Uo8 V
Switching frequency f 0 ... 300 Hz
Current consumption
Measuring plate not detected
Measuring plate detected
Ambient conditions
Ambient temperature -25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection type cable PVC , 5 m
Core cross-section 0.75 mm
Housing material PBT
Sensing face PBT
Degree of protection IP66 / IP68
Cable
Bending radius
General information
Use in the hazardous area see instruction manuals
Category
Compliance with standards and
directives
Standard conformity
NAMUR
Standards
Approvals and certificates
EAC conformity TR CU 012/2011
FM approval
Control drawing
UL approval cULus Listed, General Purpose
CSA approval cCSAus Listed, General Purpose
CCC approval CCC approval / marking not required for products rated ≤36 V
Dimensions
0.4
Al
0.85
304
≥ 3 mA
≤ 1 mA
2
> 10 x cable diameter
2G; 1D
EN 60947-5-6:2000
IEC 60947-5-6:1999
EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
116-0165
Electrical Connection
55
36
BN
BU
M30 x 1.5
L+
L-
1
34.5
40
Release date: 2018-04-19 08:18 Date of issue: 2018-04-19 106478_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
1

Inductive sensor NJ10-30GK-N-5M
Equipment protection level Gb
CE marking 0102
ATEX marking ¬ II 2G Ex ia IIC T6…T1 Gb The Ex-related marking can also be printed on the enclosed label.
Standards EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety"
Appropriate type NJ 10-30GK...-N...
Effective internal inductivity C
Effective internal inductance L
Maximum permissible ambient temperature T
Equipment protection level Da
CE marking 0102
ATEX marking ¬ II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label.
Standards EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety"
Appropriate type NJ 10-30GK...-N...
Effective internal inductivity C
Effective internal inductance L
Maximum permissible ambient temperature T
i
i
i
i
Use is restricted to the following stated conditions
≤ 140 nF ; a cable length of 10 m is considered.
≤ 100 µH ; a cable length of 10 m is considered.
Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
amb
temperature class, and the effective internal reactance values can be found on the EC-type examination certificate.
Use is restricted to the following stated conditions
≤ 140 nF ; a cable length of 10 m is considered.
≤ 100 µH ; a cable length of 10 m is considered.
Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
amb
surface temperature, and the effective internal reactance values can be found on the EC-type-examination
certificate.
The maximum permissible ambient temperature of the data sheet must be noted, in addition, the lower of
the two values must be maintained.
Release date: 2018-04-19 08:18 Date of issue: 2018-04-19 106478_eng.xml