Inductive sensor NJ10-30GKK-N
Technical Data
General specifications
Switching function Normally closed (NC)
Output type NAMUR
Rated operating distance sn10 mm
Installation flush
Assured operating distance sa0 ... 8.1 mm
0102
Model Number
NJ10-30GKK-N
Features
• 10 mm flush
• Usable up to SIL 2 acc. to IEC 61508
Accessories
BF 30
Mounting flange, 30 mm
Reduction factor r
Reduction factor rCu 0.3
Reduction factor r
Output type 2-wire
Nominal ratings
Nominal voltage Uo8.2 V (Ri approx. 1 kΩ)
Switching frequency f 0 ... 300 Hz
Current consumption
Measuring plate not detected
Measuring plate detected
Functional safety related parameters
MTTFd 4560 a
Mission Time (T
Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection type terminal compartment
Core cross-section up to 2.5 mm
Housing material PBT
Sensing face PBT
Degree of protection IP66 / IP67
General information
Use in the hazardous area see instruction manuals
Category
Compliance with standards and
directives
Standard conformity
NAMUR
Standards
Approvals and certificates
UL approval cULus Listed, General Purpose
CSA approval cCSAus Listed, General Purpose
CCC approval CCC approval / marking not required for products rated ≤36 V
Dimensions
0.4
Al
0.85
304
) 20 a
M
≥ 3 mA
≤ 1 mA
2
2G
EN 60947-5-6:2000
IEC 60947-5-6:1999
EN 60947-5-2:2007
IEC 60947-5-2:2007
5
36
Electrical Connection
M30x1,5
M16x1,5
40
2
58
115
M16x1,5
M16x1,5
40
1
2
L+
L-
Release date: 2017-05-30 10:37 Date of issue: 2017-07-24 106475_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
1

Inductive sensor NJ10-30GKK-N
Equipment protection level Gb
CE marking 0102
Effective internal inductivity C
Effective internal inductance L
Maximum permissible ambient temperature T
Equipment protection level Da
CE marking 0102
Effective internal inductivity C
Effective internal inductance L
i
i
i
i
≤ 140 nF ; a cable length of 10 m is considered.
≤ 100 µH ; a cable length of 10 m is considered.
Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
amb
temperature class, and the effective internal reactance values can be found on the EU-type examination certificate.
≤ 140 µF
A cable length of 10 m is considered.
≤ 100 µH
A cable length of 10 m is considered.
Release date: 2017-05-30 10:37 Date of issue: 2017-07-24 106475_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2