Inductive sensor NJ0,2-10GM-N
Technical Data
General specifications
Switching function Normally closed (NC)
Output type NAMUR
Rated operating distance sn0.2 mm
Installation flush
Assured operating distance sa0 ... 0.2 mm
Model Number
NJ0,2-10GM-N
Features
• Sensor with dead stop
•0.2 mm flush
Reduction factor r
Reduction factor rCu 0.3
Reduction factor r
Nominal ratings
Nominal voltage Uo8 V
Operating voltage UB5 ... 25 V
Switching frequency f 0 ... 100 Hz
Hysteresis H typ. %
Current consumption
Measuring plate not detected
Measuring plate detected
Functional safety related parameters
MTTFd 11770 a
Mission Time (TM) 20 a
Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Axial load, max. F 0 ... 1200 N
Connection type cable PVC , 2 m
Core cross-section 0.34 mm
Housing material Special steel
Degree of protection IP67
Compliance with standards and directives
Stan dard conf ormit y
NAMUR
Sta ndar ds
Approvals and certificates
UL approval cULus Listed, General Purpose
CSA approval cCSAus Listed, General Purpose
CCC approval CCC approval / marking not required for products rated ≤36 V
0.4
Al
0.85
304
≥ 3 mA
≤ 1 mA
2
EN 60947-5-6:2000
IEC 60947-5-6:1999
EN 60947-5-2:2007
IEC 60947-5-2:2007
Dimensions
Electrical Connection
BN
L+
Release date: 2016-11-08 17:26 Date of issue: 2016-11-08 009805_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
BU
L-
1