Inductive sensor NCN4-12GM35-N0-V1
Technical Data
General specifications
Switching function Normally closed (NC) Output type NAMUR Rated operating distance sn4 mm Installation non-flush Assured operating distance sa0 ... 3.24 mm
0102
Model Number
NCN4-12GM35-N0-V1
Features
• Usable up to SIL 2 acc. to IEC 61508
Actual operating distance s Reduction factor rAl 0.37 Reduction factor r Reduction factor r Output type 2-wire
Nominal ratings
Nominal voltage Uo8.2 V (Ri approx. 1 kΩ) Switching frequency f 0 ... 800 Hz Hysteresis H 1 ... 10 typ. 5 % Reverse polarity protection reverse polarity protected Short-circuit protection yes Current consumption
Measuring plate not detected Measuring plate detected
Switching state indicator Multihole-LED, yellow
Functional safety related parameters
MTTFd 2520 a Mission Time (TM) 20 a Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 100 °C (-13 ... 212 °F) Storage temperature -40 ... 100 °C (-40 ... 212 °F)
Mechanical specifications
Connection type Connector plug M12 x 1 , 4-pin Housing material Stainless steel 1.4305 / AISI 303 Sensing face PBT Degree of protection IP67
General information
Scope of delivery 2 self locking nuts in scope of delivery Use in the hazardous area see instruction manuals
Category
Compliance with standards and directives
Standard conformity
NAMUR
Electromagnetic compatibility Standards
Approvals and certificates
EAC conformity TR CU 012/2011 FM approval
Control drawing UL approval cULus Listed, General Purpose CSA approval cCSAus Listed, General Purpose CCC approval CCC approval / marking not required for products rated 36 V
0.36
Cu
0.74
304
Dimensions
3.6 ... 4.4 mm typ.
r
3 mA 1 mA
1G; 2G; 3G; 1D
EN 60947-5-6:2000 IEC 60947-5-6:1999 NE 21:2007 EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
116-0165
Release date: 2018-04-19 08:16 Date of issue: 2018-04-19 181103_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
17
LED
M12x1
M12x1
4
5
34
40
50
6
1
Inductive sensor NCN4-12GM35-N0-V1
Electrical Connection
1
2
L+
L-
Wire colors in accordance with EN 60947-5-6
1 BN 2 BU
Equipment protection level Ga
CE marking 0102
ATEX marking ¬ II 1G Ex ia IIC T6T1 Ga The Ex-related marking can also be printed on the enclosed label.
Standards EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety"
Appropriate type NCN4-12GM...-N0...
Effective internal inductivity C
Effective internal inductance L
Ambient temperature Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
Equipment protection level Gb
CE marking 0102
i
i
(brown) (blue)
Use is restricted to the following stated conditions
95 nF ; a cable length of 10 m is considered.
100 µH ; a cable length of 10 m is considered.
temperature class, and the effective internal reactance values can be found on the EC-type examination certificate.
Note:
Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already
been applied to the temperature table for category 1.
ATEX marking ¬ II 1G Ex ia IIC T6T1 Ga
Standards EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety"
Appropriate type NCN4-12GM...-N0...
Effective internal inductivity C
Effective internal inductance L
Maximum permissible ambient temperature T
Equipment protection level Gc (ic)
Certificate PF 13 CERT 2895 X
CE marking
ATEX marking ¬ II 3G Ex ic IIC T6T1 Gc
Standards EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection category "ic" Use is restricted to the following
Effective internal inductivity C
Effective internal inductance L
Special conditions
for Pi=34 mW, Ii=25 mA, T6
for Pi=34 mW, Ii=25 mA, T5
for Pi=34 mW, Ii=25 mA, T4-T1
for Pi=64 mW, Ii=25 mA, T6
for Pi=64 mW, Ii=25 mA, T5
for Pi=64 mW, Ii=25 mA, T4-T1
for Pi=169 mW, Ii=52 mA, T6
for Pi=169 mW, Ii=52 mA, T5
for Pi=169 mW, Ii=52 mA, T4-T1
for Pi=242 mW, Ii=76 mA, T6
for Pi=242 mW, Ii=76 mA, T5
for Pi=242 mW, Ii=76 mA, T4-T1
i
i
i
i
The Ex-significant identification is on the enclosed adhesive label
Use is restricted to the following stated conditions
95 nF ; a cable length of 10 m is considered.
100 µH ; a cable length of 10 m is considered.
Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
amb
temperature class, and the effective internal reactance values can be found on the EC-type examination certificate.
The Ex-significant identification is on the enclosed adhesive label
stated conditions
95 nF ; a cable length of 10 m is considered.
100 µH ; A cable length of 10 m is considered.
55 °C (131 °F)
55 °C (131 °F)
55 °C (131 °F)
55 °C (131 °F)
55 °C (131 °F)
55 °C (131 °F)
52 °C (125.6 °F)
52 °C (125.6 °F)
52 °C (125.6 °F)
44 °C (111.2 °F)
44 °C (111.2 °F)
44 °C (111.2 °F)