Pepperl Fuchs NCN15-30GM40-Z1 Data Sheet

Inductive sensor NCN15-30GM40-Z1
Technical Data
General specifications
Switching element function DC NC
Model Number
NCN15-30GM40-Z1
Features
• 15 mm non-flush
•2-wire DC
Accessories
BF 30
Mounting flange, 30 mm
Rated operating distance s Installation non-flush Output polarity DC Assured operating distance sa0 ... 12.2 mm Actual operating distance s Reduction factor rAl 0.38 Reduction factor r Reduction factor r
Nominal ratings
Operating voltage UB5 ... 60 V Switching frequency f 0 ... 100 Hz Hysteresis H 1 ... 10 typ. 5 % Reverse polarity protection reverse polarity tolerant Short-circuit protection pulsing Vol tag e d rop U Operating current I
S
Lowest operating current I Off-state current I Switching state indicator all direction LED, yellow
Functional safety related parameters
MTTFd 1751 a Mission Time (TM) 20 a Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Connection type cable PUR , 2 m Core cross-section 0.34 mm Housing material Stainless steel 1.4305 / AISI 303 Sensing face PBT Degree of protection IP67
Compliance with standards and directives
Stan dard conf ormit y
Sta ndar ds
Approvals and certificates
UL approval cULus Listed, General Purpose CSA approval cCSAus Listed, General Purpose CCC approval Certified by China Compulsory Certification (CCC)
0.35
Cu
0.68
304
15 mm
n
13.5 ... 16.5 mm typ.
r
5 V
d
2 ... 100 mA
L
2 mA
m
0 ... 0.5 mA typ.
r
EN 60947-5-2:2007 IEC 60947-5-2:2007
2
Dimensions
Electrical Connection
M30x1,5
18
37
5
36
BN
LED
L+
40
Release date: 2016-04-07 14:41 Date of issue: 2016-04-07 089272_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
BU
L-
1