General specifications
Switching function Normally closed (NC) Output type NAMUR Rated operating distance sn8 mm Installation flush Assured operating distance sa0 ... 6.48 mm
0102
Model Number
NCB8-18GM40-N0-V1
Features
• Usable up to SIL 2 acc. to IEC 61508
Accessories
V1-W-N-2M-PUR
Female cordset, M12, 2-pin, NAMUR, PUR cable
V1-G
Female connector, M12, 4-pin, field attachable
V1-W
Female connector, M12, 4-pin, field attachable
EXG-18
Quick mounting bracket with dead stop
V1-G-N-2M-PUR
Female cordset, M12, 2-pin, NAMUR, PUR cable
BF 18
Mounting flange, 18 mm
Actual operating distance s Reduction factor rAl 0.39 Reduction factor r Reduction factor r Output type 2-wire
Nominal ratings
Nominal voltage Uo8.2 V (Ri approx. 1 kΩ) Switching frequency f 0 ... 1500 Hz Hysteresis H 1 ... 15 typ. 5 % Reverse polarity protection reverse polarity protected Short-circuit protection yes Suitable for 2:1 technology yes , Reverse polarity protection diode not required Current consumption
Measuring plate not detected Measuring plate detected
Switching state indicator Multihole-LED, yellow
Functional safety related parameters
MTTFd 2660 a Mission Time (T Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 100 °C (-13 ... 212 °F) Storage temperature -40 ... 100 °C (-40 ... 212 °F)
Mechanical specifications
Connection type Connector plug M12 x 1 , 4-pin Housing material Stainless steel 1.4305 / AISI 303 Sensing face PBT Degree of protection IP66 / IP67
General information
Use in the hazardous area see instruction manuals
Category
Compliance with standards and directives
Standard conformity
NAMUR
Electromagnetic compatibility Standards
Approvals and certificates
EAC conformity TR CU 012/2011 FM approval
Control drawing UL approval cULus Listed, General Purpose CSA approval cCSAus Listed, General Purpose CCC approval CCC approval / marking not required for products rated 36 V
0.36
Cu
0.71
304
) 20 a
M
Dimensions
7.2 ... 8.8 mm typ. 8 mm
r
2.2 mA 1 mA
1G; 2G; 3G; 1D
EN 60947-5-6:2000 IEC 60947-5-6:1999 NE 21:2007 EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
116-0165
Release date: 2018-04-19 08:14 Date of issue: 2018-04-19 181089_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
4
24
LED
M12x1
M18x1
40
45
55
6
1
Inductive sensor NCB8-18GM40-N0-V1
Electrical Connection
Pinout
1
2
L+
L-
1
2
4
3
Wire colors in accordance with EN 60947-5-6
1 BN 2 BU
(brown) (blue)
Equipment protection level Ga
CE marking 0102
ATEX marking ¬ II 1G Ex ia IIC T6T1 Ga The Ex-related marking can also be printed on the enclosed label.
Standards EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety"
Appropriate type NCB8-18GM...-N0...
Effective internal inductivity C
Effective internal inductance L
Ambient temperature Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
Equipment protection level Gb
CE marking 0102
ATEX marking ¬ II 1G Ex ia IIC T6T1 Ga
Standards EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety"
Appropriate type NCB8-18GM...-N0...
Effective internal inductivity C
Effective internal inductance L
Maximum permissible ambient temperature T
i
i
i
i
Use is restricted to the following stated conditions
120 nF ; a cable length of 10 m is considered.
50 µH ; a cable length of 10 m is considered.
temperature class, and the effective internal reactance values can be found on the EC-type examination certificate.
Note:
Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already
been applied to the temperature table for category 1.
The Ex-significant identification is on the enclosed adhesive label
Use is restricted to the following stated conditions
120 nF ; a cable length of 10 m is considered.
50 µH ; a cable length of 10 m is considered.
Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
amb
temperature class, and the effective internal reactance values can be found on the EC-type examination certificate.
Release date: 2018-04-19 08:14 Date of issue: 2018-04-19 181089_eng.xml