Inductive sensor NCB5-18GM60-B3B-V1
Dimensions
M18x1
Model Number
NCB5-18GM60-B3B-V1
Features
• Comfort series
•5 mm flush
• A/B slave with extended addressing
possibility for up to 62 slaves
• Cylindrical
• NO/NC selectable
• Stability control warning
• Installation help
• On/Off delay (disconnectable)
• Oscillator monitoring
Connection
1
3
(+)
(-)
Pinout
1
2
4
3
Accessories
BF 18
Mounting flange, 18 mm
V1-W-2M-PUR
Cable socket, M12, 4-pin, PUR cable
V1-G
4-pin, M12 female field-attachable connector
EXG-18
Quick mounting bracket with dead stop
V1-W
4-pin, M12 female field-attachable connector
V1-G-2M-PUR
Cable socket, M12, 4-pin, PUR cable
4
24
M12x1
44
60
70
6
Technical Data
General specifications
Switching element function NO/NC programmable
Rated operating distance s
Installation flush
Output polarity AS-Interface
Assured operating distance sa0 ... 4.05 mm
Reduction factor r
Reduction factor rCu 0.15
Reduction factor r
Slave type A/B slave
AS-Interface specification V3.0
Required master specification ≥ V2.1
Nominal ratings
Operating voltage UB26.5 ... 31.9 V via AS-i bus system
Switching frequency f 0 ... 100 Hz
Hysteresis H 1 ... 15 typ. 5 %
Reverse polarity protected reverse polarity protected
No-load supply current I
Operating voltage display dual-LED, green
Indication of the switching state dual-LED, yellow
Fault indication dual-LED, red
Functional safety related parameters
MTTFd 926 a
Mission Time (TM) 20 a
Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Connection type Device connector M12 x 1 , 4-pin
Housing material Stainless steel 1.4305 / AISI 303
Sensing face PBT
Protection degree IP67
Compliance with standards and directives
Standard conformity
Electromagnetic compatibility
Standards
Approvals and certificates
UL approval cULus Listed, General Purpose
CSA approval cCSAus Listed, General Purpose
CCC approval Products with a maximum operating voltage of ≤36 V do not bear a
0.2
Al
0.62
304
5 mm
n
≤ 25 mA
0
EN 50295:1999-10
EN 60947-5-2:2007
IEC 60947-5-2:2007
CCC marking because they do not require approval.
Release date: 2012-05-09 10:22 Date of issue: 2012-05-09 226333_eng.xml
Subject to modifications without notice
Copyright Pepperl+Fuchs
1

Inductive sensor NCB5-18GM60-B3B-V1
Programming Instructions
Adress 00 preset, alterable
via Busmaster
or programming units
IO-Code 0
ID-Code A
ID1-Code 7
ID2-Code E
Data bit
Bit Function
D0 Switching state
D1 Prefailure message (dynamic)
D2 Oscillator monitoring
D3 Object too close
Parameter bit
Bit Function
P0 ON / Off delay
activated* / deactivated
P1 Switching element function
NO* / NC
P2 not used
P3 not used
*
Indicators
Standard setting
LED red
UAI
LED red
FAULT
LED yellow
OUT
LED green
POWER
Release date: 2012-05-09 10:22 Date of issue: 2012-05-09 226333_eng.xml
Subject to modifications without notice
Copyright Pepperl+Fuchs
2