Pepperl Fuchs NCB5-18GM40-Z0-3G-3D-10M Data Sheet

Inductive sensor NCB5-18GM40-Z0-3G-3D-10M
Technical Data
General specifications
Switching function Normally open (NO) Output type Two-wire Rated operating distance sn5 mm Installation flush Output polarity DC
Model Number
NCB5-18GM40-Z0-3G-3D-10M
Features
•5 mm flush
• ATEX-approval for zone 2 and zone 22
Accessories
BF 18
Mounting flange, 18 mm
EXG-18
Quick mounting bracket with dead stop
Assured operating distance s Actual operating distance sr4.5 ... 5.5 mm typ. 5 mm Reduction factor r Reduction factor rCu 0.33 Reduction factor r Output type 2-wire
Nominal ratings
Operating voltage UB5 ... 60 V Switching frequency f 0 ... 350 Hz Hysteresis H 1 ... 10 typ. 5 % Reverse polarity protection reverse polarity tolerant Short-circuit protection pulsing
S
Voltage drop U Operating current I Lowest operating current I Off-state current I Switching state indicator all direction LED, yellow
Functional safety related parameters
MTTFd 1739 a Mission Time (TM) 20 a Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Connection type cable PVC , 10 m Cable version PA Core cross-section 0.34 mm Housing material Stainless steel 1.4305 / AISI 303 Sensing face PBT Degree of protection IP66 / IP67 Cable
Bending radius
General information
Use in the hazardous area see instruction manuals
Category
Compliance with standards and directives
Standard conformity
Standards
Approvals and certificates
UL approval cULus Listed, General Purpose CSA approval cCSAus Listed, General Purpose CCC approval Certified by China Compulsory Certification (CCC)
Al
304
Dimensions
0.37
0.7
0 ... 4.05 mm
a
5 V
d
2 ... 100 mA
L
2 mA
m
0 ... 0.5 mA typ.
r
2
> 10 x cable diameter
3G; 3D
EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
Release date: 2018-03-22 11:01 Date of issue: 2018-03-22 211266_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
M18x1
4
24
LED
37
40
1
Inductive sensor NCB5-18GM40-Z0-3G-3D-10M
Electrical Connection
BN
BU
L+
L-
Equipment protection level Gc (nA)
Certificate PF 15CERT3754 X
CE marking
ATEX marking ¬ II 3G Ex nA IIC T6 Gc
Standards EN 60079-0:2012+A11:2013, EN 60079-15:2010
The Ex-related marking can also be printed on the enclosed label.
Ignition protection category "n" Use is restricted to the following stated conditions
Special conditions
Maximum operating current I
Maximum operating voltage U
L
Bmax
Maximum permissible ambient temperature T
at U
at U
at U
=60 V, IL=100 mA
Bmax
=60 V, IL=50 mA
Bmax
=60 V, IL=25 mA
Bmax
The maximum permissible load current must be restricted to the values given in the following list. High load currents and load short-circuits are not permitted.
The maximum permissible operating voltage UB max is restricted to the values in the following list. Tolerances are not permissible.
dependant of the load current I
Umax
Information can be taken from the following list.
and the max. operating voltage U
L
50 °C (122 °F)
56 °C (132.8 °F)
60 °C (140 °F)
Equipment protection level Dc (tc)
CE marking
Bmax
ATEX marking ¬ II 3D Ex tc IIIC T80°C Dc
Standards EN 60079-0:2012+A11:2013, EN 60079-31:2014
General The corresponding datasheets, declarations of conformity, EC-type examination certificates, certifications, and
The Ex-related marking can also be printed on the enclosed label.
Protection by enclosure "tc" Some of the information in this instruction manual is more specific than the information provided in the datasheet.
control draw see datasheets), form an integral part of this document. These documents can be found at The maximum surface temperature of the device was determined without a layer of dust of the information in this instruction manual is more specific than the information provided in the datasheet.
Special conditions
Maximum permissible ambient temperature T
at U
at U
at U
=60 V, IL=100 mA
Bmax
=60 V, IL=50 mA
Bmax
=60 V, IL=25 mA
Bmax
dependant of the load current I
Umax
Information can be taken from the following list.
50 °C (122 °F)
56 °C (132.8 °F)
60 °C (140 °F)
and the max. operating voltage U
L
Bmax
Equipment protection level Dc (tD)
General The apparatus has to be operated according to the appropriate data in the data sheet and in this instruction manual.
The maximum surface temperature has been determined in accordance with method A without a dust layer on the equipment. The data stated in the data sheet are restricted by this operating instruction! The special conditions must be adhered to!
Special conditions
Maximum permissible ambient temperature T
at U
at U
at U
=60 V, IL=100 mA
Bmax
=60 V, IL=50 mA
Bmax
=60 V, IL=25 mA
Bmax
dependant of the load current IL and the max. operating voltage U
Umax
Information can be taken from the following list.
50 °C (122 °F)
56 °C (132.8 °F)
60 °C (140 °F)
Bmax
Release date: 2018-03-22 11:01 Date of issue: 2018-03-22 211266_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2