Inductive sensor NCB40-FP-N0-P1
Technical Data
General specifications
Switching function Normally closed (NC)
Output type NAMUR
Rated operating distance sn40 mm
Installation flush
Assured operating distance sa0 ... 32 mm
0102
Model Number
NCB40-FP-N0-P1
Features
• 40 mm flush
Actual operating distance s
Reduction factor rAl 0.35
Reduction factor r
Reduction factor r
Output type 2-wire
Nominal ratings
Installation conditions
F
Nominal voltage U
Switching frequency f 0 ... 80 Hz
Hysteresis H 0 ... 5 typ. 3 %
Reverse polarity protection reverse polarity protected
Short-circuit protection yes
Current consumption
Measuring plate not detected
Measuring plate detected
Time delay before availability t
Switching state indicator LED, yellow
Functional safety related parameters
MTTFd 2360 a
Mission Time (T
Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 100 °C (-13 ... 212 °F)
Storage temperature -40 ... 100 °C (-40 ... 212 °F)
Mechanical specifications
Connection type screw terminals
Information for connection A maximum of two conductors with the same core cross section
Core cross-section up to 2.5 mm
Minimum core cross-section
Maximum core cross-section
Housing material PBT
Sensing face PBT
Degree of protection IP66 / IP67
General information
Use in the hazardous area see instruction manuals
Category
Compliance with standards and
directives
Standard conformity
NAMUR
Electromagnetic compatibility
Standards
Approvals and certificates
EAC conformity TR CU 012/2011
FM approval
Control drawing
UL approval cULus Listed, General Purpose
CSA approval cCSAus Listed, General Purpose
CCC approval CCC approval / marking not required for products rated ≤36 V
0.35
Cu
0.8
304
) 20 a
M
36 ... 44 mm typ. 40 mm
r
100 mm
8.2 V (Ri approx. 1 kΩ)
o
≥ 3 mA
≤ 1 mA
≤ 20 ms
v
may be mounted on one terminal connection!
tightening torque 1.2 Nm + 10 %
without wire end ferrule 0.5 mm2 , with connector sleeves 0.34 mm
without wire end ferrule 2.5 mm
1G; 2G; 1D
EN 60947-5-6:2000
IEC 60947-5-6:1999
NE 21:2007
EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
116-0165
2
2
, with connector sleeves 1.5 mm
2
2
Release date: 2018-04-19 08:12 Date of issue: 2018-04-19 106293_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
1

Inductive sensor NCB40-FP-N0-P1
Dimensions
14
40
10
83
80
65
Electrical Connection
M20 x 1.5
65
ø 9.5
7
ø 5.3
LED
1
2
Equipment protection level Ga
CE marking 0102
ATEX marking ¬ II 1G Ex ia IIC T6…T1 Ga
Standards EN 60079-0:2012+A11:2013, EN 60079-11:2012
Appropriate type NCB40-FP-N0..
Effective internal inductivity C
Effective internal inductance L
Highest permissible ambient temperature Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
Special conditions
Equipment protection level Gb
CE marking 0102
ATEX marking ¬ II 1G Ex ia IIC T6…T1 Ga
Standards EN 60079-0:2012+A11:2013, EN 60079-11:2012
Appropriate type NCB40-FP-N0..
Effective internal inductivity C
Effective internal inductance L
Maximum permissible ambient temperature T
Special conditions
i
i
i
i
L+
L-
The Ex-related marking can also be printed on the enclosed label.
Ignition protection "Intrinsic safety"
Use is restricted to the following stated conditions
≤ 220 nF ; a cable length of 10 m is considered.
≤ 360 µH ; a cable length of 10 m is considered.
temperature class, and the effective internal reactance values can be found on the EU-type examination certificate.
Note:
Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already
been applied to the temperature table for category 1.
The Ex-related marking can also be printed on the enclosed label.
Ignition protection "Intrinsic safety"
Use is restricted to the following stated conditions
≤ 220 nF ; a cable length of 10 m is considered.
≤ 360 µH ; a cable length of 10 m is considered.
Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the
amb
temperature class, and the effective internal reactance values can be found on the EU-type examination certificate.
Release date: 2018-04-19 08:12 Date of issue: 2018-04-19 106293_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2