Pepperl Fuchs NCB2-12GM40-E2-3G-3D-5M Data Sheet

Inductive sensor NCB2-12GM40-E2-3G-3D-5M
Technical Data
General specifications
Switching function Normally open (NO) Output type PNP Rated operating distance sn2 mm Installation flush Output polarity DC
Model Number
NCB2-12GM40-E2-3G-3D-5M
Features
•Comfort series
• ATEX-approval for zone 2 and zone 22
Accessories
BF 12
Mounting flange, 12 mm
EXG-12
Quick mounting bracket with dead stop
Assured operating distance s Actual operating distance sr1.8 ... 2.2 mm typ. Reduction factor r Reduction factor rCu 0.21 Reduction factor r
Nominal ratings
Operating voltage UB10 ... 30 V Switching frequency f 0 ... 1000 Hz Hysteresis H 1 ... 10 typ. 3 % Reverse polarity protection reverse polarity protected Short-circuit protection pulsing Vol tag e d rop Ud≤ 3 V Vol tag e d rop at I
Vol tage dro p IL = 100 mA, switching ele-
ment on U Operating current I No-load supply current I Time delay before availability t Switching state indicator LED, yellow
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F) Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Connection type cable PVC , 5 m Core cross-section 3 x 0.34 Housing material Stainless steel 1.4305 / AISI 303 Sensing face PBT Degree of protection IP67 Cable
Bending radius
General information
Use in the hazardous area see instruction manuals
Category
Compliance with standards and directives
Stan dard conf ormit y
Sta ndar ds
Approvals and certificates
UL approval cULus Listed, General Purpose CSA approval cCSAus Listed, General Purpose CCC approval CCC approval / marking not required for products rated 36 V
0.23
Al
0.7
304
L
d
0 ... 1.62 mm
a
1.2 ... 2.5 V
0 ... 200 mA
L
11 mA
0
20 ms
v
> 10 x cable diameter
3G; 3D
EN 60947-5-2:2007 IEC 60947-5-2:2007
Dimensions
Electrical Connection
BN
BK
BU
M12 x 1
4
37
17
40
LED
L+
L-
Release date: 2016-11-07 10:13 Date of issue: 2016-11-07 211256_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
1
Inductive sensor NCB2-12GM40-E2-3G-3D-5M
Equipment protection level Gc (nA)
Instruction Manual electrical apparatus for hazardous areas
Device category 3G (nA) for use in hazardous areas with gas, vapour and mist
Certificate of Compliance PF 15CERT3754 X CE marking
ATEX marking ¬ II 3G Ex nA IIC T6 Gc
Standards EN 60079-0:2012+A11:2013, EN 60079-15:2010
Ge n e r a l The apparatus has to be operated according to the appropriate data in the data sheet
Installation, commissioning Laws and/or regulations and standards governing the use or intended usage goal must
Maintenance No changes can be made to apparatus, which are operated in hazardous areas.
Special conditions
Maximum operating current I
Maximum operating voltage U
Maximum permissible ambient temperature T
at U at U at U at U at U at U at U
=60 V, IL=200 mA
Bmax
=60 V, IL=100 mA
Bmax
=60 V, IL=50 mA
Bmax
=30 V, IL=200 mA
Bmax
=30 V, IL=150 mA
Bmax
=30 V, IL=100 mA
Bmax
=30 V, IL=50 mA
Bmax
L
Bmax
Umax
Protection from mechanical danger Protection from UV light
Protection of the connection cable
Protection against transients
Electrostatic charge
Material selection accessories
The Ex-related marking can also be printed on the enclosed label.
Ignition protection category "n" Use is restricted to the following stated conditions
and in this instruction manual. The data stated in the data sheet are restricted by this operating instruction! The special conditions must be obser ved!
be observed. If the Ex-related marking is printed only on the supplied label, then this must be attached in the immediate vicinity of the sensor. The sticking surface for the label must be clean and free from grease. The attached label must be legible and indel­ible, including in the event of possible chemical corrosion.
Repairs to these apparatus are not possible.
The maximum permissible load current must be restricted to the values given in the fol­lowing list. High load currents and load short-circuits are not permitted.
The maximum permissible operating voltage UB max is restricted to the values in the following list. Tolerances are not permissible.
dependant of the load current I Information can be taken from the following list.
and the max. operating voltage U
L
Bmax
43 °C (109.4 °F) 47 °C (116.6 °F) 50 °C (122 °F) 53 °C (127.4 °F) The sensor must not be exposed to ANY FORM of mechanical danger. The sensor and the connection cable must be protected from damaging UV-radiation.
This can be achieved when the sensor is used in internal areas. The connection cable must be prevented from being subjected to tension and torsional
loading. Ensure transient protection is provided and that the maximum value of the transient pro-
tection (140% of 85 V) is not exceeded. Electrostatic charges must be avoided on the mechanical housing components. Dan-
gerous electrostatic charges on the mechanical housing components can be avoided by incorporating these in the equipotential bonding.
When selecting accessories, ensure that the material allows the temperature of the enclosure to rise to up to 70 °C.
Release date: 2016-11-07 10:13 Date of issue: 2016-11-07 211256_eng.xml