Pepperl Fuchs NBN40-L2-A2-V1-3G-3D Data Sheet

Inductive sensor NBN40-L2-A2-V1-3G-3D
Technical Data
General specifications
Switching function complementary Output type PNP Rated operating distance sn40 mm Installation non-flush Output polarity DC
Model Number
NBN40-L2-A2-V1-3G-3D
Features
• Sensor head bidirectional and rotatable
• 40 mm non-flush
•4-wire DC
• Quick mounting bracket
•4-way LED indicator
• ATEX-approval for zone 2 and zone 22
Accessories
MHW 01
Modular mounting bracket
MH 02-L
Mounting aid
Assured operating distance s Actual operating distance sr36 ... 44 mm Reduction factor r Reduction factor rCu 0.31 Reduction factor r Reduction factor r Output type 4-wire
Nominal ratings
Operating voltage UB10 ... 30 V DC Switching frequency f 0 ... 100 Hz Hysteresis H typ. 5 % Reverse polarity protection reverse polarity protected Short-circuit protection pulsing Voltage drop Ud≤ 2 V Design data Operating current I Off-state current I No-load supply current I Time delay before availability t Operating voltage indicator LED, green Switching state indicator LED, yellow
Functional safety related parameters
MTTFd 1237 a Mission Time (TM) 20 a Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 85 °C (-13 ... 185 °F) Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Connection type Connector plug M12 x 1 , 4-pin Housing material PA Sensing face PA Degree of protection IP69K Mass 130 g
General information
Use in the hazardous area see instruction manuals
Category
Compliance with standards and directives
Standard conformity
Standards
Approvals and certificates
Protection class II
Rated insulation voltage U
Rated impulse withstand voltage U UL approval cULus Listed, General Purpose CSA approval cCSAus Listed, General Purpose CCC approval CCC approval / marking not required for products rated 36 V
0.33
Al
0.74
304
0.41
Brass
Dimensions
0 ... 32.4 mm
a
0 ... 200 mA
L
0 ... 0.5 mA
r
20 mA
0
80 ms
v
3G; 3D
EN 60947-5-2:2007 IEC 60947-5-2:2007
253 V
i
4000 V
imp
LED yeLED gnLED ye
Release date: 2016-11-07 10:02 Date of issue: 2018-02-19 130625_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
28
7
ø 5.5
20
M12 x 1
30
4
40
67
LED gn
40
5.5
46
60
1
Inductive sensor NBN40-L2-A2-V1-3G-3D
Electrical Connection
Pinout
1
L+
4
2
3
L-
1
2
4
3
Wire colors in accordance with EN 60947-5-2
1 BN 2 WH 3 BU 4 BK
(brown) (white) (blue) (black)
Equipment protection level Gc (nA)
Certificate PF 15CERT3754 X
CE marking
ATEX marking ¬ II 3G Ex nA IIC T6 Gc
Standards EN 60079-0:2012+A11:2013, EN 60079-15:2010
Special conditions
Maximum operating current I
Maximum operating voltage U
Maximum permissible ambient temperature T
at U
at U
at U
at U
Equipment protection level Dc
CE marking
ATEX marking ¬ II 3D IP69K T 107 °C (224.6 °F) X
Standards EN 50281-1-1
Special conditions
Maximum heating (Temperature rise)
at U
at U
at U
at U
Equipment protection level Dc (tc)
CE marking
=30 V, IL=200 mA
Bmax
=30 V, IL=100 mA
Bmax
=30 V, IL=50 mA
Bmax
=30 V, IL=25 mA
Bmax
=30 V, IL=200 mA
Bmax
=30 V, IL=100 mA
Bmax
=30 V, IL=50 mA
Bmax
=30 V, IL=25 mA
Bmax
L
Bmax
The Ex-related marking can also be printed on the enclosed label.
Ignition protection category "n" Use is restricted to the following stated conditions
The maximum permissible load current must be restricted to the values given in the following list. High load currents and load short-circuits are not permitted.
The maximum permissible operating voltage UB max is restricted to the values in the following list. Tolerances are not permissible.
dependant of the load current I
Umax
Information can be taken from the following list.
48 °C (118.4 °F)
50 °C (122 °F)
51 °C (123.8 °F)
52 °C (125.6 °F)
The Ex-significant identification is on the enclosed adhesive label
Protection via housing Use is restricted to the following stated conditions
dependant of the load current IL and the max. operating voltage U Information can be taken from the following list. The maximum surface temperature at maximum ambient temperature is given in the Ex identification of the apparatus.
22 K
19 K
18 K
17 K
and the max. operating voltage U
L
Bmax
Bmax
ATEX marking ¬ II 3D Ex tc IIIC T80°C Dc
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
The Ex-related marking can also be printed on the enclosed label.
2
Release date: 2016-11-07 10:02 Date of issue: 2018-02-19 130625_eng.xml