Pepperl Fuchs NBB8-18GM60-B3B-V1 Data Sheet

Inductive sensor NBB8-18GM60-B3B-V1
Dimensions
M18x1
4
Model Number
NBB8-18GM60-B3B-V1
AS-Interface
Features
• 8 mm embeddable
• Cylindrical
• A/B slave with extended addressing possibility for up to 62 slaves
• NO/NC selectable
• On/Off delay (disconnectable)
Connection
1
3
(+)
(-)
Pinout
1
2
4
3
Accessories
BF 18
Mounting flange, 18 mm
EXG-18
Quick mounting bracket with dead stop
V1-G-BK0,3M-PUR-U-V1-G
Connection cable, M12 to M12, PUR cable, 4-pin
V1-G-BK1M-PUR-U-V1-G
Connection cable, M12 to M12, PUR cable, 4-pin
24
M12x1
60
75
Technical Data
General specifications
Nominal ratings
Operating voltage UB26.5 ... 31.9 V via AS-i bus system Switching frequency f 0 ... 200 Hz Hysteresis H 1 ... 15 typ. 5 % Reverse polarity protected reverse polarity protected No-load supply current I Indication of the switching state dual-LED, yellow Fault indication dual-LED, red
Functional safety related parameters
MTTFd 926 a Mission Time (TM) 20 a Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F) Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Connection type Device connector M12 x 1 , 4-pin Housing material brass, nickel-plated Sensing face PBT Protection degree IP67
Compliance with standards and directives
Standard conformity
Standards
Approvals and certificates
UL approval cULus Listed, General Purpose CSA approval cCSAus Listed, General Purpose CCC approval Products with a maximum operating voltage of 36 V do not bear a
0.4
Al
0.7
303
0.5
Brass
8 mm
n
25 mA
0
EN 60947-5-2:2007 IEC 60947-5-2:2007 EN 50295:1999
CCC marking because they do not require approval.
Release date: 2011-07-21 08:34 Date of issue: 2011-07-21 226334_eng.xml
Subject to modifications without notice
Copyright Pepperl+Fuchs
1
Inductive sensor NBB8-18GM60-B3B-V1
Programming Instructions
Adress 00 preset, alterable via Busmaster or programming units IO-Code 0 ID-Code A ID1-Code 7 ID2-Code E
Data bit Bit Function
D0 Switching state D1 ­ D2 ­ D3 -
Parameter bit Bit Function
P0 ON / Off delay activated* / deactivated P1 Switching element function NO* / NC P2 not used P3 not used
*
Standard setting
Programming Instructions
Adress 00 preset, alterable via Busmaster or programming units IO-Code 0 ID-Code A ID1-Code 7 ID2-Code E
Data bit Bit Function
D0 Switching state D1 ­ D2 ­ D3 -
Parameter bit Bit Function
P0 ON / Off delay activated* / deactivated P1 Switching element function NO* / NC P2 not used P3 not used
*
Standard setting
Release date: 2011-07-21 08:34 Date of issue: 2011-07-21 226334_eng.xml
Subject to modifications without notice
Copyright Pepperl+Fuchs
2