Pepperl Fuchs NBB10-30GM40-Z0 Data Sheet

Inductive sensor NBB10-30GM40-Z0
Dimensions
M30x1,5
Model Number
NBB10-30GM40-Z0
•10 mm flush
•2-wire DC
Connection
BN
BU
L+
L-
Accessories
BF 30
Mounting flange, 30 mm
EXG-30
Quick mounting bracket with dead stop
LED
37
40
5
S
36
Technical Data
General specifications
Switching element function DC NO Rated operating distance s Installation flush Output polarity DC Assured operating distance sa0 ... 8.1 mm Reduction factor r Reduction factor rCu 0.25 Reduction factor r
Nominal ratings
Operating voltage UB5 ... 60 V Switching frequency f 0 ... 150 Hz Hysteresis H 1 ... 10 typ. 5 % Reverse polarity protected tolerant Short-circuit protection pulsing Voltage drop Ud≤ 5 V Operating current I Lowest operating current I Off-state current I Indication of the switching state all direction LED, yellow
Functional safety related parameters
MTTFd 1710 a Mission Time (T Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Connection type cable PVC , 2 m Core cross-section 0.34 mm Housing material brass, nickel-plated Sensing face PBT Protection degree IP67
Compliance with standards and directives
Standard conformity
Standards
Approvals and certificates
UL approval cULus Listed, General Purpose CSA approval cCSAus Listed, General Purpose CCC approval Certified by China Compulsory Certification (CCC)
0.3
Al
0.7
304
) 20 a
M
10 mm
n
2 ... 100 mA
L
2 mA
m
0 ... 0.5 mA typ.
r
EN 60947-5-2:2007 IEC 60947-5-2:2007
2
Release date: 2012-05-24 11:27 Date of issue: 2012-05-24 088210_eng.xml
Subject to modifications without notice
Copyright Pepperl+Fuchs
1
Loading...