Pepperl+Fuchs KVF-F User Manual

MANUAL
Fat Level Sensor KVF-F
PROCESS AUTOMATION
ISO9001
Fat Level Sensor KVF-F
With regard to the supply of products, the current issue of the following document is applicable:
The General Terms of Delivery for Products and Services of the Electrical Industry, published by
the Central Association of the Electrical Industry (Zentralverband Elektrotechnik und
Elektroindustrie (ZVEI) e.V.) in its most recent version as well as the supplementary clause:
Fat Level Sensor KVF-F
EN
Contents
1 Safety................................................................................... 2
1.1 General safety instructions ...........................................................................2
1.2 Used Symbols...............................................................................................2
1.3 Declaration of Conformity .............................................................................3
1.4 Intended Use ................................................................................................3
1.5 Delivery, Transport and Storage ...................................................................4
1.6 Installation and Commissioning ....................................................................4
1.7 Maintenance.................................................................................................4
1.8 Repair...........................................................................................................4
1.9 Disposal........................................................................................................5
1.10 Applied Standards and Directives.................................................................5
2 Product Specifications ...................................................... 6
2.1 Function........................................................................................................6
2.2 Product Program...........................................................................................6
2.3 Design and Dimensions................................................................................7
3 Installation .......................................................................... 8
3.1 Mounting of the Sensors...............................................................................8
3.2 Mounting the KVF-F Fat Level Sensor........................................................10
3.3 Connection of the Sensor ...........................................................................12
4 Operation .......................................................................... 13
4.1 Emptying (Disposal) of the Container .........................................................13
5 Maintenance and Repair.................................................. 14
5.1 Function Testing .........................................................................................14
6 Troubleshooting ............................................................... 15
6.1 Sensor Maintenance...................................................................................15
7 Technical Specifications ................................................. 16
7.1 Fat Level Sensor KVF-F..............................................................................16
266860 2014-04
EN - 1
Fat Level Sensor KVF-F
EN
Safety

1Safety

1.1 General safety instructions

Responsibility for planning, assembly, commissioning, operation, maintenance, and dismounting lies with the system operator.
Installation and commissioning of all devices must be performed by a trained professional only.
Protection of operating personnel and the system is not ensured if the product is not used in accordance with its intended purpose.
Laws and regulations applicable to the usage or the intended purpose must be observed. The devices are only approved for appropriate and intended use. Ignoring these instructions will void any warranty and absolve the manufacturer from any liability.
The Declaration of Conformity, Certificate of Compliance, Statement of Conformity, EC-type-examination certificate and data sheets are an integral part of this document.
The data sheet contains the electrical data of the Declaration of Conformity, the Certificate of Compliance and the EC-type-examination certificate.
The documents mentioned are available from http://www.pepperl-fuchs.com or contact your local Pepperl+Fuchs representative.

1.2 Used Symbols

Safety-relevant Symbols
Danger!
This symbol indicates an imminent danger.
Non-observance will result in personal injury or death.
Warni ng!
This symbol indicates a possible fault or danger.
Non-observance may cause personal injury or serious property damage.
Caution!
This symbol indicates a possible fault.
Non-observance could interrupt devices and any connected facilities or systems, or result in their complete failure.
266860 2014-04
2 - EN
Fat Level Sensor KVF-F
EN
ISO9001
Safety
Informative Symbols
Note!
This symbol brings important information to your attention.
Action
This symbol indicates a paragraph with instructions.

1.3 Declaration of Conformity

All products were developed and manufactured under observance of the applicable European standards and guidelines.
Note!
A Declaration of Conformity can be requested from the manufacturer.
The product manufacturer, Pepperl+Fuchs GmbH, 68307 Mannheim, has a certified quality assurance system that conforms to ISO 9001.

1.4 Intended Use

The fat level sensor KVF-F (referred to as "sensor" in the following sections) is a suspended sensor for monitoring fat layer thickness in grease interceptors.
The sensor must always be connected to an warning device of type NVD-111 (see product program).
1.4.1 Marking
Fat Level Sensor
Pepperl+Fuchs GmbH
Lilienthalstrasse 200, 68307 Mannheim, Germany
KVF-F
266860 2014-04
EN - 3
Fat Level Sensor KVF-F
EN
Safety

1.5 Delivery, Transport and Storage

Check the packaging and contents for damage.
Check if you have received every item and if the items received are the ones you ordered.
Keep the original packaging. Always store and transport the device in the original packaging.
Always store the device in a clean and dry environment. The permitted storage temperature (see data sheet) must be considered.

1.6 Installation and Commissioning

1.6.1 Installation of the Sensor
The sensor and warning device must be free of voltage during installation and maintenance. The warning device must only be connected to the supply voltage after complete mounting and connection of the sensors.
The sensor has IP68 protection and is weather- and oil/fat-resistant. It can therefore be installed in grease interceptors.
When installing the device in oil/petrol separators, observe the permissible ambient temperature in the range from -20 °C ... 60 °C (253 K ... 333 K).
1.6.2 Sensor Cable
Sensor cables must not be installed in cable or conductor bundles together with other current circuits. Avoid installing sensor cables parallel to other cables that may transmit interfering signals, which impair the sensor signal and thus the alarm function. The sensor itself must not be grounded.
If you extend the sensor cable, observe the applicable specifications with regard to color, quality and durability. Use unshielded cables.

1.7 Maintenance

For operation of grease interceptors, there may be standards, directives or laws that define regular system or sensor tests. Check the operation of the sensor at least twice a year and more frequently in the event of unfavorable environmental conditions.
When the grease interceptor is being emptied (disposal), the sensor must always be washed and dried. The sensor must not be cleaned with caustic fluids. A badly contaminated sensor can trip a wrong alarm or, in certain circumstances, fail to trip an alarm.

1.8 Repair

The devices must not be repaired, changed or manipulated.
If there is a defect, the product must always be replaced with an original device.
266860 2014-04
4 - EN
Fat Level Sensor KVF-F
EN
Safety

1.9 Disposal

Disposal of devices and their packaging material must be performed in compliance with the applicable laws and guidelines of the corresponding country.
The devices do not contain batteries which need to be disposed of separately from the products.

1.10 Applied Standards and Directives

EN 61000-6-4:2007
EN 61326-1:2013
EMC Directive 2004/108/EC
266860 2014-04
EN - 5
Fat Level Sensor KVF-F
EN
Product Specifications

2 Product Specifications

2.1 Function

The sensor has an integrated electronic circuit which, via an oscillator circuit, emits a weak HF signal that changes depending on whether the sensor element is surrounded by water or fat.
The sensor is mounted suspended and immersed in liquid.
The sensor can distinguish between water and floating fat, oil and grease (FOG).

2.2 Product Program

Warni ng devic e
Description Type code
Warning device, 230 V AC NVD-111
Sensors
Description Type code
Fat level sensor, for detecting fat layer thickness in an aqueous emulsion with small lumps of fat or a hardened layer of fat
Fat level sensor, for detecting fat layer thickness in a liquid layer of fat
Overflow sensor, for detecting excessively high liquid level KVF-O
FAU-104
KVF-F
Accessories
Description Type code
Cable connector IP68 for one sensor LAL-SK2
Mounting set for one sensor NVO5-B
Installation housing with DIN mounting rail NVO5-KV
266860 2014-04
6 - EN
Fat Level Sensor KVF-F
EN
3
1
6
4
5
2
138
25
300
Ø31.6
Product Specifications

2.3 Design and Dimensions

Fat level sensor KVF-F
Figure 2.1
266860 2014-04
1 Lower section with laser marking
2 Middle section
3 Upper section
4 Cable
5 Shrink tubing
6 Switching point
EN - 7
Fat Level Sensor KVF-F
EN
Installation

3 Installation

3.1 Mounting of the Sensors

Read the chapter on Safety and, in particular, the section on Installation and Commissioning (see chapter 1.6) before mounting the sensor. Do not remove the identification plate.
Warni ng!
Risk of short circuit
Injuries and damage to the device are possible when working with live parts.
n Before working on the device, always disconnect the supply voltage. n Connect the device to the supply voltage only after completion of the work.
During installation, read the instructions provided by the grease interceptor manufacturer. Ensure that the suspension mechanism keeps the sensor permanently at the correct height. Where possible, secure the device in a position where it can be reached from the manhole opening so that it can be removed when emptying (disposal) or carrying out maintenance work on the grease interceptor.
266860 2014-04
8 - EN
Fat Level Sensor KVF-F
EN
2
1
Installation
The oil/petrol separator can be made of various materials. We therefore recommend using the following methods to secure the device in a suspended position:
n If mounting the device in concrete containers, use the NVO5-B mounting
set. See the figure below.
n If mounting the device in containers made from other materials, such as
plastic or metal, use other suspension devices as appropriate, for example, screws and screw anchors.
Figure 3.1 Mounting using cable connector and mounting set
1 Mounting set for one sensor NVO5-B
2 Cable connector for one sensor LAL-SK2
266860 2014-04
EN - 9
Fat Level Sensor KVF-F
EN
Installation

3.2 Mounting the KVF-F Fat Level Sensor

The sensor must be immersed a few centimeters when the liquid is at its normal level (water zero line).
The exact immersion depth depends on
n the type of grease interceptor, n its design, n its capacity n and the height of the maximum fat layer thickness.
The sensor must always be immersed in the liquid. The switching point of the sensor is located between the insulated connecting piece and the top metal section.
Caution!
Damage to the cable as a result of aggressive greases
The sensor cable must not be in continuous contact with grease or with water that contains grease. The sensor is therefore fitted with shrink tubing. The shrink tubing protects the cable from the effect of the grease to a fat layer thickness of 30 cm.
If fat layer thicknesses of more than 30 cm occur in your application, protect the cable with additional shrink tubing.
266860 2014-04
10 - EN
Fat Level Sensor KVF-F
EN
L
S
B
C
A
1
2
300
X
Installation
Figure 3.2 Mounting the fat level sensor
1 Fat level sensor KVF-F
2 Shrink tubing
A Air
B Fat, oil, grease (FOG)
C Water
L Water zero line
S Sensor switching point
266860 2014-04
X Alarm limit (maximum fat layer thickness)
EN - 11
Fat Level Sensor KVF-F
EN
Installation

3.3 Connection of the Sensor

Read the chapter on Safety and, in particular, the section on Installation and Commissioning (see chapter 1.6) before connecting the sensor.
Warni ng!
Risk of short circuit
Injuries and damage to the device are possible when working with live parts.
n Before working on the device, always disconnect the supply voltage. n Connect the device to the supply voltage only after completion of the work.
Take care not to reverse the polarity when connecting the sensor cable. The loop resistance of the extension cable should not exceed 20 for the sensors.
For extending the sensor cable, use cable connector LAL-SK2.
Note!
Avoid routing the sensor cable parallel to other cables, as these cables may transmit interfering signals. These interfering signals may affect the sensor signal and impair the alarm function. Use unshielded 2-strand cables for each sensor.
To ensure the warning device functions correctly, do not exceed the following maximum sensor cable lengths:
n With a cable cross section of 0.75 mm
190 m.
n With a cable cross section of 1 mm
2
, the maximum cable length is
2
, the maximum cable length is 250 m.
Note!
Further information on connection of the sensors to the warning device is available in the manual of the warning device NVD-111.
266860 2014-04
12 - EN
Fat Level Sensor KVF-F
EN
Operation

4Operation

4.1 Emptying (Disposal) of the Container

The sensor is a sensitive component. Therefore always observe the following safety information during emptying (disposal):
Caution!
Malfunction or damage through mechanical stress of the sensor.
In case of nonobservance, the safety and operation of the sensor or the entire alarm system is not guaranteed.
n Before emptying (disposal) the grease interceptor, remove the sensor from
the container.
n Protect the sensor against impacts, knocks and unnecessary tensile forces
in the cable.
n Insert the sensor in the grease interceptor only after it has been filled.
266860 2014-04
EN - 13
Fat Level Sensor KVF-F
EN
Maintenance and Repair

5 Maintenance and Repair

5.1 Function Testing

Test frequency
The sensor is maintenance-free. However, to guarantee perfect operation of the complete alarm system check the operation of the sensor at least once a year, or more frequently in the event of unfavorable environmental conditions.
Checking the normal status
1. Switch DIP switch 1 to position OFF.
2. Remove the sensor from the grease interceptor.
3. Wash and dry the sensor.
4. Hold the sensor in your hand (no gloves). Only touch the upper and lower metal section or
5. Immerse the sensor in water.
The green "SYSTEM OK" LED on the warning device flashes or lights up.
Checking the alarm situation
1. Switch DIP switch 1 to position OFF.
2. Suspend the fat level sensor freely in air.
The red "FAT LAYER ALARM" LED lights and, if applicable, an acoustic
signal sounds.
Note!
Further information on connection of the sensors to the warning device is available in the manual of the warning device NVD-111.
266860 2014-04
14 - EN
Fat Level Sensor KVF-F
EN
Troubleshooting

6 Troubleshooting

6.1 Sensor Maintenance

Caution!
Malfunction or false alarm caused by a contaminated sensor
If the sensor is very dirty, this may trigger a false alarm or mean that no alarm is triggered under certain circumstances.
n Clean and dry the sensor when emptying/disposing of the oil/petrol
separator or container.
n Do not clean the sensor with corrosive liquids.
Cleaning the Sensor
The sensor is maintenance free. To ensure the entire alarm system functions correctly, clean the sensor at the following intervals:
1. Clean the sensor at least once a year.
2. Pay particular attention to cleaning the sensor tips of all oil, grease, and other dirt residues using a grease-dissolving cleaning agent.
3. If the sensor is used in difficult conditions, clean the sensor more often.
266860 2014-04
EN - 15
Fat Level Sensor KVF-F
EN
Technical Specifications

7 Technical Specifications

7.1 Fat Level Sensor KVF-F

Power supply
Rated voltage 13 V DC
Ambient conditions
Ambient temperature -20 °C … 60 °C (253 K 333 K)
Mechanical specifications
Protection degree IP68
Connection cable
Material stainless steel
Cable 5m
Mass approx. 520 g
Dimensions 31.6 mm x 138 mm
266860 2014-04
16 - EN
Subject to modifications Copyright PEPPERL+FUCHS • Printed in Germany
www.pepperl-fuchs.com
PROCESS AUTOMATION – PROTECTING YOUR PROCESS
Worldwide Headquarters
Pepperl+Fuchs GmbH 68307 Mannheim · Germany Tel. +49 621
776-0
E-mail: info@de.pepperl-fuchs.com
For the Pepperl+Fuchs representative closest to you check www.pepperl-fuchs.com/contact
266860 DOCT-2421A
04/2014
Loading...