Pepperl Fuchs KFU8-UFC-Ex1.D User manual

Frequency Converter with Trip Values

2
Zone 0, 1, 2 Div. 1, 2

KFU8-UFC-Ex1.D

3-
1+
16 17 18
10 11 12
I
II
19+ 20-
III
13+ 14-
7­8+
IV
AC/DC
23 24
mA
10 k 10 k
400 Ω ≤ R 2 k
Germany: +49 621 776 2222Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0002 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com
KFU8-UFC-Ex1.D
1-channel isolated barrier
<
Universal usage at different power supplies
<
Input for NAMUR sensors or dry contacts
<
Input frequency 1 mHz ... 5 kHz
<
Current output 0/4 mA ... 20 mA
<
<
Start-up override
<
Line fault detection (LFD)
<
Up to SIL 2 acc. to IEC 61508/IEC 61511
<
48 V AC ... 253 V AC/20 V DC ... 90 V DC

Function

This isolated barrier is used for intrinsic safety applications. The device is a universal frequency converter that changes a digital input signal into a proportional free adjustable 0/4 mA ... 20 mA analog output signal and functions as a switch amplifier and a trip alarm. The functions of the switch outputs (2 relay outputs and 1 potential free transistor output) are easily adjustable [trip value display (min/max alarm), serially switched output, pulse divider output, error signal output]. The device is easily configured by the use of keypad or with the PACTware configuration software. A fault is signalized by LEDs acc. to NAMUR NE44. For additional information, refer to the manual and www.pepperl-fuchs.com.

Connection

Technical Data

General specifications
Signal type Digital Input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Supply
Connection terminals 23, 24 Rated voltage U Power dissipation/power consumption ≤ 2 W ; 2.5 VA / 2.2 W ; 3 VA
Interface
Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 231197_eng.pdf
r
20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz
1
Frequency Converter with Trip Values KFU8-UFC-Ex1.D
Germany: +49 621 776 2222Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0002 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com

Technical Data

Programming interface programming socket
Input
Connection side field side Connection Input I: intrinsically safe: terminals 1+, 3-
Input I sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
Pulse duration > 50 µs Input frequency 0.001 ... 5000 Hz Line fault detection breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
Input II startup override: 1 ... 1000 s, adjustable in steps of 1 s
Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA Open circuit voltage/short-circuit current 18 V / 5 mA
Output
Connection side control side Connection output I: terminals 10, 11, 12
Output I, II signal, relay
Contact loading 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A Mechanical life 5 x 107 switching cycles Energized/De-energized delay approx. 20 ms / approx. 20 ms
Output III electronic output, passive
Contact loading 40 V DC Signal level 1-signal: (L+) - 2.5 V (50 mA, short-circuit/overload proof)
Output IV analog
Current range 0 ... 20 mA or 4 ... 20 mA Open loop voltage max. 24 V DC Load max. 650 Ω Fault signal downscale I ≤ 3.6 mA , upscale ≥ 21.5 mA (acc. NAMUR NE43)
Transfer characteristics
Input I
Measurement range 0.001 ... 5000 Hz Resolution 0.1 % of the measurement value , ≥ 0.001 Hz Accuracy 0.1 % of the measurement value , > 0.001 Hz Measuring time < 100 ms Influence of ambient temperature 0.003 %/K (30 ppm)
Output I, II
Response delay ≤ 200 ms
Output IV
Resolution < 10 µA Accuracy < 20 µA Influence of ambient temperature 0.005 %/K (50 ppm)
Galvanic isolation
Input I/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V Mutual output I, II, III reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V Output III/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V Output III/start-up override basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V Output III/IV basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V Output IV/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V Start-up override/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V Interface/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V Interface/output III basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V
Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 231197_eng.pdf
Input II: non-intrinsically safe: terminals 13+, 14-
output II: terminals 16, 17, 18 outout III: terminasl 19+, 20­output IV: terminals 8+, 7-
0-signal: switched off (off-state current ≤ 10 µA)
eff
eff
eff
eff
eff
eff
eff
eff
eff
eff