Rotation Speed Monitor

2

KFU8-DWB-1.D

10 11 12
16 17 18
14-
13+
I
II
AC/DC
23 24
3
1
2
+
-
+
-
+
-
+
-
+
-
Germany: +49 621 776 2222Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0002 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com
KFU8-DWB-1.D
1-channel signal conditioner
<
Universal usage at different power supplies
<
Dry contact or NAMUR inputs
<
Input frequency 1 mHz ... 12 kHz
<
2 relay contact outputs
<
<
Configurable by keypad
<
Line fault detection (LFD)
<
Up to SIL 2 acc. to IEC 61508/IEC 61511
<
48 V AC ... 253 V AC/20 V DC ... 90 V DC

Function

This signal conditioner monitors an overspeed or underspeed condition of a digital signal (NAMUR sensor/ mechanical contact) by comparing the input frequency to the user programmed reference frequency. An overspeed or underspeed condition is signaled via the relay outputs. Line fault detection of the field circuit is indicated by a red LED and relay. The startup override feature sets relay outputs to default conditions programmed by the user for up to 1,000 seconds. The unit is easily programmed by the use of a keypad located on the front of the unit. For additional information, refer to the manual and www.pepperl-fuchs.com.

Connection

Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 231209_eng.pdf
1
115
119
40
105 7
Rotation Speed Monitor KFU8-DWB-1.D
Germany: +49 621 776 2222Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0002 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com

Dimensions

Technical Data

General specifications
Signal type Digital Input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Supply
Connection terminals 23, 24
Rated voltage U
Rated current I
Power dissipation/power consumption ≤ 1.8 W ; 2 VA / 1.8 W ; 2 VA
Input
Connection side field side
Connection Input I: 2-wire sensor: terminals 1+, 3- three wire sensor: terminals 1+, 2- and 3
Input I 2- or 3-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
Open circuit voltage/short-circuit current 22 V / 40 mA
Input resistance 4.7 kΩ
Switching point/switching hysteresis logic 1: > 2.5 mA ; logic 0: < 1.9 mA
Pulse duration > 50 µs
Input frequency 0.001 ... 12000 Hz
Line fault detection breakage I ≤ 0.15 mA; short-circuit I > 4 mA
Input II startup override: 1 ... 1000 s, adjustable in steps of 1 s
Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA
Open circuit voltage/short-circuit current 18 V / 5 mA
Output
Connection side control side
Connection output I: terminals 10, 11, 12
Output I, II signal, relay
Contact loading 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A
Mechanical life 5 x 107 switching cycles
Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 231209_eng.pdf
20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz
r
approx. 100 mA
r
input II: terminals 13+, 14- start-up override;
output II: terminals 16, 17, 18
2
Loading...