Pepperl Fuchs KFD2-WAC2-1.D Technical Data

Strain Gauge Converter

KFD2-WAC2-1.D

10 11 12 16 17 18
3+ 5+
1+ 2-
6­4-
7­8+ 9-
I
II
III
RS 485
24 V DC
23+ 24-
20
GND
21-
19+
Power Rail
RS 485 24 V DCERR
14­15+
13+
mA
Germany: +49 621 776 2222Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0002 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com
KFD2-WAC2-1.D
1-channel signal conditioner
<
24 V DC supply (Power Rail)
<
Strain gauge input (full or half bridge)
<
Output 0 mA ... ± 20 mA or 0 V ... ± 10 V
<
2 relay contact outputs
<
<
Configurable by PACTware or keypad
<
RS-485 interface
<
Line fault detection (LFD)
<
24 V DC

Function

This signal conditioner provides the galvanic isolation between field circuits and control circuits. The device is used with strain gauges, load cells and resistance measuring bridges. Designed to provide 5 V excitation voltage, this barrier’s high quality A/D converter allows it to be used with those devices requiring 10 V. Up to four 350 strain gauges connected in parallel may be powered and evaluated. The device is easily configured by the use of keypad or with the PACTware configuration software. The current measurement for tare, zero point, and final value can be entered in this manner. A fault is signalized by LEDs and a separate collective error message output. For additional information, refer to the manual and www.pepperl-fuchs.com.

Connection

Technical Data

General specifications
Signal type Analog input
Supply
Connection Power Rail or terminals 23+, 24-
Rated voltage U
Ripple within the supply tolerance
Power consumption max. 3 W
Interface
Connection Power Rail or terminals 19+, 20 GND, 21-
Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 231223_eng.pdf
r
20 ... 35 V DC
1
Strain Gauge Converter KFD2-WAC2-1.D
Germany: +49 621 776 2222Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0002 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com

Technical Data

Type RS-485
Programming interface programming socket
Field circuit
Connection terminals 1+, 2-, 3+, 4-, 5+, 6-
Lead resistance max. 25 Ω per line
Input I
Connection terminals 1+, 2-
Sensor supply 1 ... 5 V
Connection terminals 3+, 4- (supply); 5+, 6- (signal)
Short-circuit current 50 mA
Load ≥ 116 Ω up to 5V, ≥ 85 Ω up to 4V
Input
Connection side field side
Connection Input I: terminals 1+, 2-; Input II: terminals 13+, 14-; Input III: terminals 15+, 14-
Programmable Tare 0 ... 500 % of span
Input I Signal, analog
Input signal -100 ... 100 mV
Input resistance > 1 MΩ for voltage measurement
Input II, III tare adjustment, calibration and zero
Open circuit voltage/short-circuit current 18 V / 5 mA
Active/Passive I > 4 mA/I < 1.5 mA
Output
Connection side control side
Connection Output I: terminals 10, 11, 12; Output II: terminals 16, 17, 18; Output III: terminals 7-,
Output I, II Relay output
Contact loading 253 V AC/2 A/500 VA/cos φ min. 0.7; 40 V DC/2 A resistive load
Mechanical life 2 x 107 switching cycles
Output III Analog output
Current range -20 ... 20 mA
Load max. 550 Ω
Analog voltage output 0 ... ± 10 V; output resistance 500 Ω (bridge between terminal 7 and 9)
Analog current output 0 ... ± 20 mA or 4 ... 20 mA; load 0 ... 550 Ω (terminals 7 and 8)
Line fault detection downscale -21.5 mA (-10.75 V) or 2 mA (1 V), upscale 21.5 mA (10.75 V)
Collective error message Power Rail
Transfer characteristics
Deviation
Resolution/accuracy ≤ ± 0.05 % incl. non-linearity and hysteresis
Temperature effect ≤ ± 0.01 %/K
Reaction time 300 ... 850 ms
Galvanic isolation
Input I/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Output I, II against eachother reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Output III/Input II, III not available
Output III/Programming socket not available
Other circuits from each other functional insulation, rated insulation voltage 50 V
Indicators/settings
Display elements LEDs , display
Control elements Control panel
Configuration via operating buttons
Labeling space for labeling at the front
Directive conformity
Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 231223_eng.pdf
8+, 9-
eff
via PACTware
eff
eff
eff
2
Loading...