Pepperl Fuchs KFD2-USC-1.D Users Guide

Signal Converter with Trip Value

KFD2-USC-1.D

10 11 12
I
II
7-
8+
9-
2+
V
1+
3-
24 V DC
14+ 15-
Power Rail
24 V DC
mA
mA
V
Germany: +49 621 776 2222Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0002 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com
KFD2-USC-1.D
1-channel signal conditioner
<
24 V DC supply (Power Rail)
<
Scaleable current or voltage input
<
Current or voltage output
<
Relay contact output
<
<
Line fault detection (LFD)
<

Function

This signal conditioner is suitable for the connection of current and voltage signals and provides isolation for non-intrinsically safe applications. The input ranges include 0 mA ... 20 mA, 0 V ... 10 V or 0 mV ... 60 mV. Subranges from the input ranges are selectable. The output measuring signals are 0/4 mA ... 20 mA, 0/2 V ... 10 V or 0/1 V ... 5 V. The output relay serves as trip value contact. On the display the measured value can be indicated in various physical units. The unit is easily programmed by the use of a keypad located on the front of the unit. For additional information, refer to the manual and www.pepperl-fuchs.com.

Connection

Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 192797_eng.pdf
1
115
105 7
119
20
Signal Converter with Trip Value KFD2-USC-1.D
Germany: +49 621 776 2222Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0002 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com

Dimensions

Technical Data

General specifications
Signal type Analog input
Supply
Connection terminals 14+, 15- or Power Rail
Rated voltage U
Rated current I
Power consumption ≤ 1.6 W
Input
Connection side field side
Connection terminals 1+, 3- : mV, V ; terminals 2+, 3- : mA
Input resistance voltage: 1 MΩ , current: max. 100 Ω
Limit 30 V
Current 0 ... 20 mA
Voltage 0 ... 10 V / 0 ... 60 mV
Resolution 15 Bit
Output
Connection side control side
Connection output I: terminals 10, 11, 12
Output I signal, relay
Contact loading 250 V AC/2 A/cos φ 0.7; 40 V DC/2 A
Mechanical life 2 x 107 switching cycles
Energized/De-energized delay approx. 10 ms / approx. 10 ms
Output II analog
Load current: max. 550 Ω , voltage: min. 1 kΩ
Analog voltage output 0/1 ... 5 V , 0/2 ... 10 V
Analog current output 0/4 ... 20 mA
Transfer characteristics
Deviation 0.1 % of full-scale value
Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 192797_eng.pdf
20 ... 30 V DC
r
≤ 80 mA DC
r
output II: terminals 7-, 8+, 9-
2
Loading...
+ 2 hidden pages