Pepperl Fuchs KFD2-SL2-Ex2.B Technical Data

Solenoid Driver

Zone 2
Div. 2
Zone 0, 1, 2 Div. 1, 2

KFD2-SL2-Ex2.B

I
II
24 V DC
14+ 15-
Power Rail
24 V DC
2-
3-
1+
5-
6-
4+
7
8 (+/-)
9
I
II
V
Germany: +49 621 776 2222Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0002 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com
KFD2-SL2-Ex2.B
2-channel isolated barrier
<
24 V DC supply (Power Rail)
<
Output 45 mA at 11.7 V DC
<
Logic input, non-polarized
<
Up to SIL 2 acc. to IEC 61508
<
without lead monitoring

Function

This isolated barrier is used for intrinsic safety applications. The device supplies power to solenoids, LEDs and audible alarms located in a hazardous area. It is controlled via logic signals. The inputs have two defined states: 1-Signal = 16 V DC ... 30 V DC, 0-Signal = 0 V DC ... 5 V DC. The current consumption of the input is about 3 mA. At full load, 11.7 V at 45 mA is available for the hazardous area application.

Connection

Technical Data

General specifications
Signal type Digital Output
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Supply
Connection Power Rail or terminals 14+, 15­Rated voltage U Power consumption max. 3.3 W at 45 mA output current
Input
Connection side control side Connection terminals 7, 8, 9
Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 184259_eng.pdf
r
20 ... 30 V DC
1
Solenoid Driver KFD2-SL2-Ex2.B
Germany: +49 621 776 2222Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0002 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com

Technical Data

Input current approx. 3 mA at 24 V DC Signal level 1-signal: 16 ... 30 V DC
Output
Connection side field side Internal resistor Ri272 Ω Current I Voltage Ue≥ 11.7 V Open loop voltage Usmin. 24 V Connection terminals 1+, 2-, 3- channel 1 ,
Output rated operating current 45 mA Output signal These values are valid for the rated operating voltages from 20 ... 30 V DC. Energized/De-energized delay ≤ 20 ms / ≤ 20 ms
Galvanic isolation
Input/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V Input/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V Power supply/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Indicators/settings
Display elements LEDs Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibility NE 21:2006 Degree of protection IEC 60529:2001 Protection against electrical shock EN 61010-1:2010
Ambient conditions
Ambient temperature -20 ... 50 °C (-4 ... 122 °F)
Mechanical specifications
Degree of protection IP20 Connection screw terminals Mass approx. 150 g Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-Type Examination Certificate ZELM 00 ATEX 0024
Marking 1 II (1)G [Ex ia Ga] IIC
Output Ex ia Voltage U Current I Power P
Supply
Maximum safe voltage U
Input
Maximum safe voltage U
Collective error message
Maximum safe voltage U
Certificate TÜV 02 ATEX 1820 X
Marking 1 II 3G Ex nA IIC T4 Gc
Galvanic isolation
Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 184259_eng.pdf
0-signal: 0 ... 5 V DC
≤ 45 mA
e
terminals 4+, 5-, 6- channel 2
1 II (1)D [Ex ia Da] IIIC 1 I (M1) [Ex ia Ma] I
28 V
o
110 mA
o
770 mW (linear characteristic)
o
40 V (Attention! The rated voltage can be lower.)
m
60 V (Attention! The rated voltage can be lower.)
m
40 V (Attention! The rated voltage can be lower.)
m
eff
eff
eff
2
Loading...